Позиционирование: SLC500 rack EtherNet/IP remote I/O adapter (NOT an SLC processor). It converts the existing 1746 SLC I/O rack into an EtherNet/IP slave, which is scanned and controlled by Logix контролеры (CompactLogix, КонтролЛогикс). It is the most commonly used gateway module for phased upgrades of legacy SLC systems.
✅ Основные характеристики
Ряд: A/B series; Latest firmware V2.003
Порт: 1 × RJ45, 10/100 Mbps auto-negotiation, ЭтерНет/IP (CIP)
Mandatory mounting requirement: Must be installed in Slot 0 of the SLC chassis, replacing the original SLC processor position
Объединительная плата: 1746 SLC backplane with SLC backplane master function
Connection resources: Макс. 96 Сорт 1 (real-time I/O) связи, Макс. 8 Сорт 3 (explicit message) связи
Network topology: Поддерживает звезду, линейный, ДЛР (Device Level Ring)
IP-конфигурация: DIP-переключатель / ВООТП / DHCP; DIP switch set to `888` = factory reset
Источник питания: Powered by the SLC chassis power supply, потребляемая мощность ок.. 5 Вт
Software requirement: Студия 5000 / RSLogix5000 V20 or newer; matching EDS/AOP files required
Manuals: User manual 1747-UM076; Installation manual 1747-IN521
✅ Типичные применения
- Retrofit of legacy SLC systems: Retain all 1746 I/O modules and field wiring. Only replace the Slot 0 processor with 1747-AENTR and upgrade the main controller to CompactLogix/ControlLogix for phased migration without full shutdown.
- Replacement of legacy remote I/O adapters: Substitute 1747-ASB (RIO), 1747-ACN15/ACNR15 (Контрольная сеть).
- Operate as an EtherNet/IP slave for CIP explicit read/write access by HMI or SCADA hosts.
✅ Жизненный цикл & Альтернативы миграции
Статус: окончание срока действия, end-of-production date 2027-02-15. It is an engineering replacement part with no direct pin-compatible drop-in replacement.
Long-term migration options:
Вариант А: Migrate the complete chassis to Compact 5000 ввод/вывод (5069 ряд)
Вариант Б: Keep existing field wiring and adopt 1746-to-5069 adapter base
Spare parts are only available as new-old-stock or used units. For second-hand units, verify firmware, Ethernet-порт, backplane connector and indicator lamps.
✅ Indicator Definitions
ХОРОШО: Статус модуля
LINK: Ethernet link status
ввод/вывод: SLC backplane I/O status
COMM: CIP connection status
FORCE: Force signal active
✅ Key Common Faults
- CIP 0x0010 fault: The controller holds an active connection lock on the module. Inhibit the module in Studio5000 before modifying IP settings, then remove inhibit after configuration.
- Flashing COMM red & RPI timeout: Do not configure a short RPI for SLC analog modules (1746-NI4, OAP12 etc.). Recommended RPI: 50~100 ms, максимум 320 РС; short RPI causes frequent packet loss.
- Invalid DIP IP setting (000 or value >254 and not 888): Module automatically uses BOOTP/DHCP for IP assignment.
- Not all legacy 1746 modules are supported by AENTR; verify the support list in manual before configuration.
✅ Confusing Model Distinction
1794-АЕНТР: Гибкий ввод-вывод (1794) EtherNet/IP adapter for Flex chassis, NOT compatible with SLC 1746 chassis
1747-L5xx: Native SLC processors with backplane master capability, functionally different from AENTR
1747-AENTR Common Faults, Симптомы, Коренные причины & Средства правовой защиты
Предварительное условие: Module must be installed in SLC chassis Slot 0, occupying the processor slot; powered by SLC backplane; mainstream firmware V2.003; Studio5000 minimum V20; not all legacy 1746 modules are supported.
- CIP 0x0010 (Hex 0010) Вина (Самый частый)
Симптом: Error when modifying IP or disabling BOOTP/DHCP via BOOTP/RSLinx; prompt “Set Attribute Single failed”; configuration cannot be written from controller side; IP reverts to DHCP after power cycle.
Первопричина: Класс 1 I/O connection has been established by the controller. The module is connection-locked and rejects configuration writes from external tools.
Remedy Steps
- Go online in Studio5000, right-click 1747-AENTR → Properties → Connection → ✅ Check Inhibit Module, apply, and terminate the I/O connection.
- Modify IP and disable BOOTP/DHCP via BOOTP/RSLinx/web page to save static IP.
- Remove inhibit after configuration is completed to restore communication.
Альтернатива: Put controller in Program mode or disconnect Ethernet cable; cable pull during production is not recommended.
- COMM Red Flashing, I/O Timeout, RPI Timeout, Intermittent Slave I/O Faults
Симптом: ОК, горит зеленым, LINK steady green, COMM red flashing; slave modules (especially 1746-NI4, OAP12 analog modules) drop out periodically; RPI timeout logged.
Первопричина
RPI configured too low for analog modules (по умолчанию 20 РС; SLC backplane bandwidth is limited)
Плохой контакт объединительной платы, insufficient chassis power rating
Incompatible legacy 1746 module present
High backplane bus load or aged module hardware
Средство
- Set analog module RPI to 50~100 ms, максимум 320 РС; adjust the AENTR adapter RPI accordingly.
- Выключить питание, reseat all 1746 modules and clean gold fingers; verify SLC power supply capacity.
- Cross-check against supported module list and remove incompatible modules.
- Check backplane slot timeout counters via embedded web diagnostics to locate faulty slot.
- OK Steady Red, Power-On Self-Test Failure, No Communication
Симптом: OK red solid after power-up, LINK off, module cannot be browsed in RSLinx.
Первопричина
Hardware failure or corrupted firmware
Factory reset via DIP 888 failed
Poor backplane power supply, damaged Slot 0 контакты объединительной платы
Module installed in wrong slot (not Slot 0)
Средство
- Confirm installation in Slot 0 and test with a known-good SLC chassis power supply.
- Set DIP switch to 888, power cycle for factory reset; reassign IP via BOOTP.
- If OK remains red after reset: module hardware failure, заменить блок.
- LINK Off / Мигает, No Network Connectivity, RSLinx Cannot Find Module
Симптом: OK normal, LINK off or amber flashing, ping fails.
Первопричина: Поврежденный кабель Ethernet, defective switch port, speed mismatch, IP subnet mismatch, IP address conflict.
Средство
- Replace with qualified industrial Ethernet cable and change switch port; ensure switch port is 10/100M auto-negotiation (do not force gigabit).
- Set DIP to 000, power up to obtain IP via BOOTP; ensure PC and module are on the same subnet.
- Check network for IP conflict.
- IP Reverts After Power Cycle, Static IP Will Not Save
Симптом: Static IP assigned and BOOTP disabled in BOOTP tool, but IP reverts to DHCP after power cycle.
Первопричина: Only IP address changed, BOOTP/DHCP client toggle not disabled; 0x0010 connection lock prevents the disable command from being written to Flash memory.
Средство: Inhibit module first, then set BOOTP/DHCP to Manually Configure on module configuration page, confirm successful write, then remove inhibit.
- AENTR Disconnect After Program Download (Known Bug for CompactLogix 5370 Л3)
Симптом: Больше, чем 5 I/O modules in chassis; AENTR loses communication after second program download, controller USB/Ethernet port also unresponsive.
Первопричина: Rockwell known firmware defect.
Temporary workaround: Disconnect AENTR Ethernet cable before download; reconnect after controller enters Run mode. Long-term fix: Upgrade controller firmware or replace controller model.
- Electronic Key Fault (Hex 0103)
Симптом: Ошибка модуля, type mismatch / keying failure alarm.
Первопричина: AOP revision or firmware revision in project does not match physical hardware; or configured slot I/O model differs from actual installed module.
Средство
- Read actual firmware revision from module and match firmware version in Studio5000 module definition.
- Verify the part number of every 1746 module in chassis; avoid mixed use with compatible/disabled keying mode.
- Reimport the matching AOP file.
- FORCE Lamp Solid On
Симптом: FORCE indicator illuminated.
Первопричина: One or more I/O tags are forced.
Средство: Clear all force tags in the force window of Studio5000.
- Single Slave I/O Module Fault, Adapter Communication Normal
Симптом: AENTR communicates normally, only one slot module faults while other I/O runs fine.
Первопричина: Failed 1746 модуль, poor base contact, unsupported module model, local module power fault.
Средство: Swap the suspect module to another slot for cross-testing; verify module health; check support list.
Indicator Quick Reference
ХОРОШО: Module status|Green = Normal; Red = Fault / POST fail; Amber = Initializing
LINK: Ethernet link|Solid = Link up; Blinking = Traffic present; Off = No link
COMM: CIP I/O connection|Green = I/O connection healthy; Red blink = Connection fault / тайм-аут
ввод/вывод: SLC backplane I/O status|Red = Backplane / slave module fault
FORCE: Force active
Standard On-Site Troubleshooting Sequence
- Confirm mounting position: Слот 0 только
- Read indicator status to isolate fault domain: network, adapter hardware or backplane I/O
- Browse via RSLinx to confirm module accessibility and read firmware
- If browsable: Inhibit module prior to IP/configuration edit; inspect RPI settings
- If not browsable: Проверьте кабель, выключатель, источник питания, factory reset via DIP
- Single backplane slot fault: Isolate by module swapping
- Firmware corruption: Re-flash firmware with ControlFLASH Plus
Контрольный список проверки подержанного устройства
- Verify factory reset via DIP 888 works reliably
- BOOTP assignment and embedded web page accessible
- Stable steady green OK lamp after power-up, no fault
- Chassis bench test: Mount 1746 DI module, build I/O tree in Studio5000, бегать 30 minutes without RPI timeout
- Inspect Ethernet port and backplane gold fingers for corrosion or bad solder
Allen-Bradley SLC500 Full Model List (1747 Controller Family + 1746 Шасси & I/O Family, All EOL Discontinued)
Примечание: SLC500 consists of two main families: 1747 (Processors, Communication Adapters, Scanners) и 1746 (Шасси, Источники питания, Цифровой ввод/вывод, Аналоговый ввод/вывод, Specialty I/O). The whole platform is discontinued; spare parts are traded as new-old-stock or used hardware.
- 1747 Processors (Процессор)|SLC5/01 ~ SLC5/05
| Номер детали | Семья | Описание |
| 1747-L511 | SLC5/01 | 1K program memory, 485 дирхамов, base unit |
| 1747-L514 | SLC5/01 | 4K program memory, 485 дирхамов |
| 1747-L524 | SLC5/02 | 4K program memory, 485 дирхамов, remote I/O capable |
| 1747-L531 | SLC5/03 | 8К, DH485+DH+ |
| 1747-L532 | SLC5/03 | 16К, DH485+DH+ |
| 1747-L533 | SLC5/03 | 32К, DH485+DH+ |
| 1747-L541 | SLC5/04 | 16К, DH485+DH++RS232 |
| 1747-L542 | SLC5/04 | 32К, DH485+DH++RS232 |
| 1747-L543 | SLC5/04 | 64К, DH485+DH++RS232 |
| 1747-L551 | SLC5/05 | 16К, integrated EtherNet/IP+DH485 |
| 1747-L552 | SLC5/05 | 32К, integrated EtherNet/IP+DH485 |
| 1747-L553 | SLC5/05 | 64К, integrated EtherNet/IP+DH485 (Top-tier SLC processor) |
- 1747 Communication Adapters / Scanners (1747-AENTR Listed Here)
| Номер детали | Описание |
| 1747-АЕНТР | EtherNet/IP adapter for SLC Slot0, converts 1746 I/O to EtherNet/IP slave (Key model) |
| 1747-АСБ | RIO remote I/O adapter (RIO slave) |
| 1747-СН | RIO remote I/O scanner (RIO master) |
| 1747-ACN15 | ControlNet scanner |
| 1747-ACNR15 | ControlNet redundant adapter |
| 1747-DSN | DeviceNet scanner |
| 1747-KE | DH485/RS232 protocol converter |
| 1747-CP3 | Programming cable adapter |
| 1747-С11 | DH485 cable |
| 1747-DU501 | Data storage module |
- 1746 Шасси
| Номер детали | Количество слотов |
| 1746-А4 | 4-slot chassis |
| 1746-A7 | 7-slot chassis |
| 1746-А10 | 10-slot chassis |
| 1746-A13 | 13-slot chassis |
- 1746 Chassis Power Supplies
| Номер детали | Рейтинг |
| 1746-P1 | 120/240V AC input |
| 1746-П2 | 120/240В и |
| 1746-P3 | 24V DC input |
| 1746-P4 | 120/240В и, высокая мощность |
| 1746-P5 | 24V DC high power |
| 1746-P6 | 24В Вашингтоне |
| 1746-Р7 | 120/240В и |
- 1746 Цифровой вход DI
| Номер детали | Рейтинг |
| 1746-IA4 | 120V AC 4-point input |
| 1746-IA8 | 120V AC 8-point input |
| 1746-IA16 | 120V AC 16-point input |
| 1746-IM4 | 240V AC 4-point input |
| 1746-IM8 | 240V AC 8-point input |
| 1746-IM16 | 240V AC 16-point input |
| 1746-ИБ8 | 24V DC sink 8-point |
| 1746-IB16 | 24V DC sink 16-point |
| 1746-ИБ32 | 24V DC sink 32-point |
| 1746-IV8 | 24V DC source 8-point |
| 1746-IV16 | 24V DC source 16-point |
| 1746-IV32 | 24V DC source 32-point |
| 1746-ITB16 | 24V DC high-speed sink 16-point |
| 1746-ITV16 | 24V DC high-speed source 16-point |
| 1746-IC16 | 48V DC 16-point |
| 1746-IH16 | 125V DC 16-point |
| 1746-IG16 | 5V TTL 16-point |
| 1746-IN16 | Universal AC/DC 16-point |
- 1746 Цифровой выход DO
| Номер детали | Рейтинг |
| 1746-OA8 | 120/240V AC 8-point output |
| 1746-OA16 | 120/240V AC 16-point output |
| 1746-OAP12 | 120/240V AC high-current 12-point |
| 1746-OB8 | 24V DC source 8-point |
| 1746-OB16 | 24V DC source 16-point |
| 1746-ОБ32 | 24V DC source 32-point |
| 1746-OB6EI | Isolated DC output 6-point |
| 1746-OW4 | Relay 4-point |
| 1746-OW8 | Relay 8-point |
| 1746-OW16 | Relay 16-point |
| 1746-OX8 | Isolated relay 8-point |
- 1746 Combination I/O (ДИ+ДЕЛО)
| Номер детали | Рейтинг |
| 1746-IO4 | 2DI+2DO 120V AC + реле |
| 1746-IO8 | 4DI+4DO |
| 1746-IO12 | 6DI+6DO AC/relay |
| 1746-IO12DC | DC combination I/O |
- 1746 Analog I/O AI/AO
| Номер детали | Описание |
| 1746-NI4 | 4-channel analog input 4-20mA/0-10V |
| 1746-NI8 | 8-channel analog input |
| 1746-NR4 | RTD 4-channel |
| 1746-NT4 | Thermocouple 4-channel |
| 1746-NT8 | Thermocouple 8-channel |
| 1746-NO4I | 4-channel isolated analog output |
| 1746-NO8V | 8-channel voltage output |
| 1746-NO4V | 4-channel voltage output |
| 1746-NIO4I | 2AI+2AO isolated analog combo |
| 1746-NIO4V | 2AI+2AO voltage analog combo |
- 1746 Specialty Modules (Высокоскоростной счетчик, Позиционирование, BASIC etc.)
| Номер детали | Описание |
| 1746-HSCE | Высокоскоростной счетчик / кодер |
| 1746-HSCE2 | Upgraded high-speed counter |
| 1746-HSTP1 | Stepper positioning module |
| 1746-БАС | BASIC co-processor module |
| 1746-SDN | DeviceNet scanner (chassis mount) |
| 1746-HCA | High-speed counter accessory |
- Аксессуары
1746-C7, 1746-RT25, 1747-бакалавр (Литиевая батарея), клеммные колодки, обложки, expansion cables etc.
Supplementary Notes for Retrofit Projects
- 1747-AENTR Compatibility Limit: Not all 1746 modules are supported. Early specialty modules (legacy HSCE, БАС) may not be recognized; analog module RPI must not be too short.
- Easy Confusion: 1794-AENTR is Flex I/O adapter, not part of SLC500 (1746) family.
- Migration Path: Preferred upgrade route for full SLC replacement: CompactLogix + 5069 Compact5000 I/O.