ComponentМодельЗначение
КонтакторCJX2-6511CJX2: Код серии (based on Schneider LC1-D technology)
65: Rated current of main contacts is 65A
11: Auxiliary contact configuration (1 нормально открытый + 1 нормально закрытый)
Thermal Overload RelayNR2-93NR2: Код серии
93: Frame size is 93A (adjustable current range: 23-93А)
/З: With manual/automatic reset selection (standard configuration)

  • Подробная информация о продукте

Technical File of Chint CJX2-6511 + NR2-93

Chint CJX2-6511 + NR2-93 is a standard electromagnetic starter combination, consisting of a CJX2-6511 Контактор переменного тока and an NR2-93 thermal overload relay. It is mainly used for remote control, overload and phase failure protection of AC motors, and is widely applied in industrial automation and electrical control systems.

  1. Интерпретация модели
ComponentМодельЗначение
КонтакторCJX2-6511CJX2: Код серии (based on Schneider LC1-D technology)
65: Rated current of main contacts is 65A
11: Auxiliary contact configuration (1 нормально открытый + 1 нормально закрытый)
Thermal Overload RelayNR2-93NR2: Код серии
93: Frame size is 93A (adjustable current range: 23-93А)
/З: With manual/automatic reset selection (standard configuration)
  1. Основные технические параметры
  2. CJX2-6511 AC Contactor
Параметр ЭлементСпецификация ЗначениеПримечания
Rated Operational Voltage690В и50/60Гц
Rated Operational Current65АUnder AC-3 utilization category and 380V condition
Номинальное напряжение изоляции690В
Номинальное импульсное выдерживаемое напряжение6кВ
Control Coil Voltage24V/36V/110V/220V/380V ACНеобязательный, 220V/380V are common choices
Main Contact Configuration3НЕТ (3 Нормально открытый)For making and breaking the main circuit
Auxiliary Contact Configuration1НЕТ + 1Северная КаролинаFor interlocking of control circuits
Механическая жизнь 10 миллион операций
Электрическая жизнь 1 миллион операцийUnder AC-3 utilization category
Способ монтажаScrew mounting / 35mm standard DIN railCompatible with DIN rail
Температура окружающей среды-5℃ ~ +40 ℃24-hour average temperature ≤ +35℃
  1. NR2-93 Thermal Overload Relay
Параметр ЭлементСпецификация ЗначениеПримечания
Rated Operational Voltage690В и50/60Гц
Размер кадра93А
Adjustable Current Range23-32А, 30-40А, 37-50АMultiple specifications available, matched with 65A contactor
48-65А, 55-70А, 63-80А
80-93А
Trip Class10АOverload protection characteristic (tripping time is 2-10 seconds at 10 раз номинальный ток)
Функция защитыЗащита от перегрузки + phase failure protectionThree-phase bimetallic strip structure
Reset MethodManual/automatic selectableStandard configuration is /Z type
Способ монтажаPlug-in mounting with CJX2 contactorCan be mounted independently
Ambient Temperature CompensationYesEnsures protection accuracy under different ambient temperatures

III. Функциональные особенности

  1. Features of CJX2-6511 Contactor

High-performance Contacts: Silver alloy contacts with excellent conductivity, strong arc erosion resistance and long service life.

Low-noise Design: Optimized electromagnetic system to reduce noise during pull-in and release.

Модульная структура: Expandable auxiliary contacts for flexible installation.

Safe and Reliable: Complies with GB/T 14048.4 and IEC/EN 60947-4-1 стандарты, with short-circuit protection coordination capability.

Wide Voltage Adaptability: Control coil is compatible with multiple voltage levels to meet the requirements of different control circuits.

  1. Features of NR2-93 Thermal Overload Relay

Comprehensive Protection: Provides both overload and phase failure protection to prevent motor burnout due to phase loss operation.

Температурная компенсация: Maintains stable protection characteristics when ambient temperature changes.

Action Indication: Clear trip status indication for easy fault troubleshooting.

Flexible Reset: Manual/automatic reset selection to adapt to different control requirements.

Plug-in Mounting: Perfectly matched with CJX2 contactor for quick installation and space saving.

  1. Advantages of the Combined System

Integrated Control and Protection: The contactor is responsible for circuit on/off and motor starting, while the thermal overload relay provides overload/phase failure protection, forming a complete control and protection unit.

Standardized Design: Complies with international standards and can be seamlessly integrated with other electrical components.

Простое обслуживание: Modular structure allows easy component replacement and reduces maintenance costs.

  1. Область применения
  2. Управление двигателем: Suitable for frequent starting, stopping, forward and reverse rotation control of three-phase AC motors with power below 30kW (380В).
  3. Industrial Equipment: General machinery such as fans, водяные насосы, компрессоры, conveyors and machine tools.
  4. Строительная электротехника: Central air conditioning systems, fire pumps and elevator control systems.
  5. Other Applications: Long-distance controlled power transmission and distribution systems, and electrical circuits requiring overload protection.
  6. Рекомендации по выбору
  7. Basic Selection Principles

Contactor Selection: The rated current of main contacts shall be ≥ 1.2-1.5 times the rated current of the motor (inductive load).

Thermal Relay Selection: The adjustable current range shall cover the rated current of the motor (usually set to 0.95-1.05 times the rated current of the motor).

Напряжение катушки: Selected according to the power supply of the control circuit, 220V or 380V AC are commonly used.

  1. Motor Power Matching Table (380В)
Motor PowerНоминальный токRecommended Thermal Relay SpecificationApplication Scenario
18.5кВт37АNR2-93/Z 37-50AGeneral load
22кВт44АNR2-93/Z 37-50AGeneral load
30кВт60АNR2-93/Z 48-65AHeavy load, frequent starting
37кВт74АNR2-93/Z 63-80ADerating required (65A contactor is close to the limit)
  1. Меры предосторожности при установке и использовании

Mounting Direction: The contactor and thermal overload relay can be installed horizontally or vertically, with an inclination angle not exceeding 5°.

Характеристики проводки: The terminals of the main circuit shall be tightened to avoid heating; the cross-sectional area of the control circuit wire shall be ≥ 1.5mm².

Экологические требования: Избегайте установки во влажных, dusty or corrosive gas environments; altitude ≤ 2000m.

Protection Coordination: Must be used with circuit breakers to provide short-circuit protection.

  1. Поиск неисправностей
Явление неисправностиВозможные причиныРешения
Contactor fails to pull in1. Low coil voltage/phase loss1. Check the power supply voltage to ensure it is within 10% номинальной стоимости
2. Burned-out coil2. Measure the coil resistance and replace the coil if abnormal
3. Mechanical jamming3. Check the iron core and mechanism to remove foreign objects
4. Open circuit in control circuit4. Check the wiring of the control circuit and repair the open circuit
Loud noise after contactor pulls in1. Oil stain/dust on iron core end face1. Clean the iron core end face
2. Broken short-circuit ring2. Replace the iron core or contactor
3. Voltage fluctuation3. Stabilize the power supply voltage
Contact overheating/ablation1. Loose wiring1. Tighten the wiring terminals
2. Severe contact wear2. Replace the contacts or contactor
3. Перегрузка3. Check the load and replace with a contactor of larger capacity if necessary
4. High operating frequency4. Reduce the operating frequency or select a contactor suitable for AC-4 utilization category
Frequent tripping of thermal overload relay1. Excessively small adjustable current1. Adjust the adjustable current to the rated current of the motor
2. Motor overload2. Check the motor load and eliminate faults
3. Phase loss operation3. Check the wiring of the main circuit and repair the phase loss
4. Высокая температура окружающей среды4. Improve ventilation conditions and reduce the ambient temperature
Thermal overload relay fails to trip1. Excessively large adjustable current1. Adjust the adjustable current
2. Damaged heating element2. Replace the thermal overload relay
3. Jammed trip mechanism3. Check and repair the trip mechanism

VII. Substitution and Compatibility

ComponentChint ModelCompatible/Alternative ModelПримечания
КонтакторCJX2-6511Schneider LC1-D6511Compatible in mounting dimensions and electrical parameters
Delixi CDM1-6511
ABB A16-30-11
Thermal Overload RelayNR2-93Schneider LRD3363Similar protection characteristics; attention shall be paid to matching of mounting methods
Delixi JR28-93
ABB TA25DU

VIII. Краткое содержание

Chint CJX2-6511 + NR2-93 is a cost-effective and highly reliable motor control and protection solution, especially suitable for frequent starting and protection applications of small and medium-sized motors. Its modular design, standardized interface and comprehensive protection functions make it an ideal choice in the field of industrial automation. During selection, it is necessary to choose the appropriate adjustable current specification of the thermal overload relay and the coil voltage of the contactor according to the motor power, rated current and control requirements.

Service Life Details of Chint CJX2-6511 + NR2-93

The service life of the Chint CJX2-6511 + NR2-93 combination shall be comprehensively evaluated from three dimensions: mechanical life (no-load operation times), electrical life (on-load operation times) and actual service life, which is also affected by various factors such as operating conditions and maintenance level.

  1. Officially Nominal Life Parameters
  2. CJX2-6511 AC Contactor
Life TypeStandard ValueTest Condition
Механическая жизнь 10 миллион операцийOperation under no-load and rated coil voltage
Электрическая жизнь 600,000 операции (AC-3 utilization category)Controlling three-phase asynchronous motor under 380V and rated operating current of 65A
Электрическая жизнь 100,000 операции (AC-4 utilization category)Frequent starting/reversing/braking conditions with larger current
  1. NR2-93 Thermal Overload Relay
Life TypeStandard ValueTest Condition
Механическая жизнь 1 миллион операцийOperation under no-load and rated control voltage
Электрическая жизнь 100,000 операцииOperation of control circuit under rated working conditions
Heating Element LifeLong-term stable (about 10 годы)Normal use without frequent overload tripping
  1. Key Factors Affecting Service Life
  2. Factors Affecting Contactor Life
  1. FactorInfluence MechanismInfluence Degree
    Operating FrequencyFrequent operation accelerates mechanical wear and contact ablationВысокий (if the frequency is doubled, the life may be halved)
    Тип нагрузкиThe life of AC-4 load (frequent starting/reversing) is 60-80% lower than that of AC-3 loadВысокий
    Колебания напряженияOvervoltage causes coil overheating, and undervoltage causes contact bouncingMedium-High
    Условия окружающей средыТемпература > 40℃, humidity, dust and corrosive gas accelerate agingMedium
    Способ монтажаNon-vertical installation (inclination > 5°) affects heat dissipation and mechanical actionНизкий
    Maintenance LevelRegular cleaning and terminal tightening can extend the service lifeMedium

    Factors Affecting Thermal Overload Relay Life

FactorInfluence MechanismInfluence Degree
Overload FrequencyFrequent overload tripping causes fatigue of bimetallic stripsВысокий
Adjustable CurrentExcessively small adjustable current leads to unnecessary trippingMedium
Температура окружающей средыHigh temperature affects protection accuracy and component lifeMedium
Control Circuit VoltageOvervoltage causes ablation of control contactsНизкий

III. Life Estimation in Practical Application

  1. Calculation of Actual Contactor Life (Пример)

Assumed working conditions: AC-3 utilization category, 100 operations per day, 300 working days per year

Theoretical electrical life: 600,000 операции

Annual operation times: 100 operations/day × 300 days = 30,000 operations/year

Expected service life: 600,000 ÷ 30,000 = 20 годы (ideal working conditions)

If it is AC-4 utilization category with 200 operations per day:

Theoretical electrical life: 100,000 операции

Annual operation times: 200 × 300 = 60,000 operations/year

Expected service life: 100,000 ÷ 60,000 = about 1.7 годы (severe working conditions)

  1. Estimation of Actual Thermal Overload Relay Life

Control Contact Life: With 50 operations per day, the theoretical 100,000 operations can last for about 5.5 годы.

Heating Element Life: Under normal use (less than 5 overload trips per month), it can work stably for 8-10 годы.

Overall Life: Usually determined by the life of the contactor; the thermal overload relay can be replaced as a wearing part.

  1. Practical Suggestions for Extending Service Life
  2. Selection Optimization

The rated current of the contactor shall be ≥ 1.2-1.5 times the rated current of the motor.

For frequent starting/reversing conditions, select AC-4 dedicated contactors or use them with derating.

  1. Installation and Usage Specifications

Install vertically with good ventilation; control the ambient temperature within -5℃ ~ +40℃.

Keep the control coil voltage stable within ±10% of the rated value.

Set the adjustable current of the thermal overload relay to 0.95-1.05 times the rated current of the motor.

  1. Maintenance Measures

Regularly clean the contacts and iron core to remove dust and oil stains.

Check the wiring terminals to prevent loosening and heating.

After 3-5 years of operation of the contactor, the contacts and coil can be replaced.

When the thermal overload relay trips frequently, check the motor load and main circuit.

  1. Краткое содержание

Under standard working conditions (АС-3, 100 operations per day), the electrical life of the contactor in the Chint CJX2-6511 + NR2-93 combination is about 20 годы, and the mechanical life far exceeds the actual service demand; the overall life of the thermal overload relay is about 10 годы. The actual service life mainly depends on the operating frequency, load type and maintenance level, and may be shortened to 1-2 years under severe working conditions. Through reasonable selection, standardized use and regular maintenance, the service life of the equipment can be effectively extended and the replacement cost can be reduced.

Предыдущий:

Следующий:

Оставить ответ

Оставить сообщение