Базовый обзор
ABB A2X38/A2X38.2 is a 3-pole AC contactor belonging to the ABB Formula series. A2X38 is an earlier model (прекращено), while A2X38.2 is its upgraded replacement (currently in production). It is mainly used for controlling three-phase squirrel-cage motors and other power loads, and is suitable for industrial automation and building electrical systems. Код заказа: 2TFC200010R2511
- Пояснение кода модели
| Модельный сегмент | Значение |
| A2X | Formula series contactor with compact and cost-effective design |
| 38 | Rated operating current of 38A (АС-3, 400В) |
| 0.2 | Second-generation upgraded version (improved type) |
| 30 | 3-pole main contacts, normally open configuration |
| 11 | Конфигурация вспомогательных контактов: 1 нормально открытый + 1 нормально закрытый |
| 13/25 | Код напряжения катушки: 13 = 380-400VAC, 25 = 220-240VAC |
| 380V50/60HZ | Rated coil voltage and frequency |
III. Основные технические параметры
- Электрические параметры
| Параметр Элемент | Ценить | Примечания |
| Номинальный рабочий ток (АС-3, 400В) | 38А | Controlled motor power: 18.5кВт (50Гц) / 20hp (60Гц) |
| Номинальный рабочий ток (АС-1, 400В) | 50А | резистивная нагрузка |
| Номинальное напряжение изоляции (Уи) | 690В | стандарт МЭК |
| Номинальное рабочее напряжение (Уэ) | 400В (АС-3), 690В (АС-1) | |
| Напряжение управляющей катушки | 220-240ВАК, 380-400ВАК, 110ВАК, 24В переменного/постоянного тока, и т. д.. | Доступно несколько вариантов |
| Coil Frequency | 50/60Гц | Universal design, no adjustment required |
| Механический срок службы | ≥10 миллионов операций | |
| Электрический срок службы (АС-3) | ≥1 миллиона операций | Недооцененная нагрузка |
- Физические характеристики
| Параметр Элемент | Ценить |
| Способ монтажа | Монтаж на DIN-рейку (35стандартная рейка мм), slider design for one-hand disassembly |
| Габаритные размеры (мм) | Approximately 85×105×55 (Width × Height × Depth) |
| Масса | Approximately 0.5kg |
| Класс защиты | IP20 (main body), IP00 for terminal blocks |
| Температура окружающей среды | -25℃~+55℃ (operation), -40℃~+85℃ (хранилище) |
| Степень загрязнения | Степень 3 |
- Основные характеристики продукта
- Компактный дизайн: Маленький размер, saving 30% of installation space, suitable for high-density distribution cabinets.
- High Efficiency and Reliability: Silver alloy contacts with arc resistance, low contact resistance and long service life.
- Простая установка: Quick snap-on fixing, auxiliary contact modules can be directly clipped without tools.
- Safety Assurance: Flame-retardant engineering plastic housing complying with UL94 V0 standard, built-in surge suppression (для некоторых моделей).
- Модульное расширение: Accessories such as auxiliary contacts (до 4 единицы), mechanical interlocks, time-delay heads and surge suppressors can be added.
- Типичные сценарии применения
Direct start and stop control of three-phase asynchronous motors (≤18.5kW/400V)
Electrical control of equipment such as fans, water pumps and compressors
Switch control of non-motor loads such as heating and lighting systems
Building electrical systems and industrial automation production lines
Replacement of old contactors for equipment upgrading and transformation
- Complete Model and Ordering Information
| Полная модель | Напряжение катушки | Вспомогательные контакты | Код заказа | Статус |
| A2X38-30-01 380V | 380ВАК | 0 нормально открытый + 1 нормально закрытый | 10221469 | Снято с производства |
| A2X38.2-30-11-13 | 380-400ВАК | 1 нормально открытый + 1 нормально закрытый | 10242059 | Currently in Production |
| A2X38.2-30-11-25 | 220-240ВАК | 1 нормально открытый + 1 нормально закрытый | 10242060 | Currently in Production |
| A2X38.2-30-00-13 | 380-400ВАК | Нет вспомогательных контактов | 10242058 | Currently in Production |
VII. Installation and Wiring Specifications
Этапы установки:
- Confirm that the installation environment meets the range of -25℃~+55℃, free from severe vibration and corrosive gases.
- Select a 35mm standard DIN rail and ensure the mounting surface is flat.
- Align the contactor’s snap with the rail, press down and slide to fix (one-hand operation).
- Cut off all power supplies before wiring, and use a multimeter to confirm no voltage exists.
- Проводка главной цепи: L1/L2/L3 → input terminals, T1/T2/T3 → output terminals.
- Проводка цепи управления: A1/A2 → coil power supply, 13/14 → normally open auxiliary contacts, 21/22 → normally closed auxiliary contacts.
- After wiring is completed, gently pull the wires to confirm they are connected firmly without loosening.
Terminal Block Specifications:
Главная цепь: M6 bolts, suitable for copper core wires with cross-sectional area of 1.5-16mm²
Схема управления: M3.5 bolts, suitable for copper core wires with cross-sectional area of 0.5-2.5mm²
VIII. Replacement Models and Compatibility
| Оригинальная модель | Direct Replacement Model | Upgraded Replacement Series | Примечания |
| A2X38 | A2X38.2 | AF38 Series | A2X38.2 is fully compatible with A2X38 in terms of installation dimensions and electrical performance |
| A2X38.2 | AF38-30-xx-xx | AF Series | AF series has advantages such as electronic coil (широкий диапазон напряжения) and built-in surge suppression |
| AX38-30-xx | AX Series | Equivalent performance with slightly higher price |
- Руководство по устранению неполадок
| Явление неисправности | Возможные причины | Решения |
| Контактор не втягивается | No voltage/low voltage on coil; Перегорание катушки; Механические помехи | Check the control circuit; Измерьте сопротивление катушки (approximately several hundred ohms under normal condition); Clean foreign objects and lubricate moving parts |
| Excessive noise after pull-in | Низкое напряжение катушки; Oil stain/rust on iron core end face; Broken short-circuit ring | Adjust control voltage to rated value; Clean iron core end face; Replace coil assembly |
| Contact overheating/ablation | Перегрузка нагрузки; Плохой контакт контактов; Ослабленная проводка | Check load current; Polish contacts or replace them; Re-tighten terminal blocks |
| Неисправность вспомогательного контакта | Contact wear; Ошибка проводки | Replace auxiliary contact module; Check wiring polarity |
- Safety and Maintenance Precautions
- Power-off Operation: Cut off all power supplies before installation and maintenance, and hang the “Нет включения” знак.
- Регулярный осмотр: Conduct inspection every 6 месяцы, including contact wear, terminal tightness and coil temperature.
- Contact Replacement: Replace the main contacts in time when the wear amount exceeds 1mm or the surface is severely ablated.
- Экологические требования: Avoid use in humid and dusty environments; install a protective housing if necessary.
- Совместимые аксессуары: Only use auxiliary contacts, interlock devices and other accessories original or certified by ABB to ensure safety performance.