Разбивка кода модели
E5EC QR 2 A S M 820
- E5EC: Ряд, DIN panel mount digital PID temperature controller, dimension 48 мм(ЧАС) × 96 мм(Вт)
- QR: Dual control outputs
вопрос: OUT1 = Voltage pulse output (DC12V, for SSR drive)
Р: OUT2 = SPST relay contact output (1а)
✅ Supports Heating + Cooling dual control
- 2: 2 auxiliary alarm outputs
- А: Power supply AC 100~240 V (50/60 Гц)
- С: Винтовой клеммный блок
- М: Универсальный мультивход
Supports K/J/T/S/R/B/N thermocouples, Pt100/Pt1000 RTD, 4~20 мА / 0~10 V analog signal
- 820: Function option code
Built-in RS485 Modbus communication
No heater burnout detection (CT input), no external event input
Distinction:
800 = No communication; 820 = With RS485; 808/828 = With CT heater current detection
- Key Electrical Specifications
| Элемент | Спецификация |
| Габаритные размеры | 48(ЧАС) × 96(Вт) × 60(Д) мм, panel embedded mounting |
| Источник питания | AC100~240 V, потребляемая мощность ок.. 6.6 Вирджиния |
| Выход управления 1(вопрос) | DC12V±20%, Макс. 21 mA PNP, SSR driving output |
| Выход управления 2(Р) | SPST relay 1a, AC250 V 5 А (резистивная нагрузка) |
| Дополнительные выходы | 2 релейные выходы (for alarm, high/low limit, deviation alarm) |
| Sampling Cycle | 50 РС, high-speed PID calculation |
| Режимы управления | Standard PID, Автонастройка (AT), ON/OFF control, Обогрев & Cooling control |
| Коммуникация | Modbus RTU over RS485 (Standard for suffix -820) |
| Input Accuracy | РТД: ±0,2% полной шкалы; Термопара: ±0.3% FS |
| Операционная среда | 0~50°C, нет конденсата, non-corrosive atmosphere |
- Simplified Terminal Definition
1, 2: AC Power Input
3, 4: OUT1 SSR voltage drive output
5, 6: OUT2 Relay control output
7, 8 / 9, 10: Two groups of auxiliary alarm outputs
Sensor terminals: Universal connection for thermocouple / Pt100 RTD
- Типичные сценарии применения
Mold Temperature Controllers (TCU), Hot Air Ovens, Industrial Ovens, extruder heating & cooling control
Applications requiring SSR for heating + relay for cooling fan / cooling water valve
Automated production lines where PLC reads temperature and writes setpoint via RS485
- Cross-Series Alternative Models
E5EC-QR2ASM-800: Without RS485 communication (hardware identical otherwise)
E5EC-RR2ASM-820: Dual relay outputs, not suitable for high-frequency SSR control
E5EC-QX2ASM-820: Second output is 4~20 mA linear analog output
- Выбор & Меры предосторожности при эксплуатации
- QR configuration is ideal: SSR for heating, relay for cooling loads;
- Relay output is NOT suitable for frequent switching (contact burnout risk); high-frequency loads must adopt Q voltage pulse output;
- Do not reverse A/B polarity of RS485 wiring; terminate resistor can be installed on demand;
- When enabling heating/cooling function, activate 2-PID heating-cooling control in parameters.
Practical Application Cases for OMRON E5EC-QR2ASM-820 Temperature Controller
Recap of core hardware strengths for this model:
✅ OUT1: DC12V voltage pulse output (drives SSR, suitable for high-frequency heating)
✅ OUT2: Relay contact output (drives fan / cooling water valve for cooling control)
✅ 2 independent alarm relay outputs
✅ Built-in RS485 Modbus-RTU (суффикс -820)
✅ Universal input: Pt100 RTD, K/J/T thermocouple, 4~20 mA analog signal
👉 Best fit: Обогрев & Cooling 2-PID control + PLC network communication
Случай 1: Injection Mold Temperature Controller (Most Common Industry Solution)
Working Requirements
Stable mold temperature 40~120°C; cooling water valve activates above set temperature, electric heater turns on below set temperature; PLC remotely reads process temperature & заданное значение; overtemperature alarm.
Hardware Layout
Датчик: Immersion Pt100 RTD
OUT1(вопрос) → SSR Solid State Relay → Electric heating tube
OUT2(Р) → Intermediate Relay → Cooling water solenoid valve (cooling circuit)
ALM1: Absolute high overtemperature alarm; ALM2: Sensor breakage alarm
RS485 connected to Siemens S7-1200 / Mitsubishi FX5U PLC
Critical Controller Parameter Settings
- Режим управления: HEAT/COOL 2-PID
- Action type: Heating Reverse Action, Cooling Direct Action
- Enable AT auto-tuning to auto-calculate heating & cooling gain
- Коммуникация: Модбус РТУ, 9600, 8, Н, 1
Преимущества проекта
Contactless SSR supports frequent cycling and extends heater service life; relay dedicated to cooling water valve; centralized collection of temperature data for multiple TCUs via PLC, production curve monitoring on HMI/SCADA.
Случай 2: Constant-Temperature Circulating Hot Air Oven / Food Baking Oven
Working Requirements
Temperature range 30~220°C; electric heating for temperature rise, exhaust fan activates for overheat ventilation; local panel operation + remote setpoint via HMI; audible & visual alarm when temperature exceeds limit.
Hardware Layout
Датчик: Type K Thermocouple
OUT1(вопрос) → SSR → Heating elements
OUT2(Р) → Relay → Heat exhaust fan
Dual alarms: High absolute limit alarm, deviation alarm
RS485 directly connected to Weinview / Kunlun Tongtai HMI (PLC not mandatory)
Operation Tips
Ovens feature large thermal inertia; appropriately increase derivative time parameter. Set cooling dead band to prevent frequent toggle between heater and exhaust fan.
Случай 3: Auxiliary Zone Temperature Control for Plastic Extruder Barrel
Working Requirements
Thermal holding of extruder barrel section; cooling water jacket enabled when temperature rises excessively; unified communication management via machine main PLC.
Hardware Layout
Type K thermocouple mounted on outer barrel surface
OUT1: SSR control for heating bands
OUT2: Cooling water solenoid valve
RS485 integrated into machine Modbus bus; PLC reads zone process temperatures
Selection Advantage vs RR model
E5EC-QR2ASM-820 outperforms RR type: Contactless SSR on heating channel supports 24/7 continuous production and avoids relay contact ablation.
Случай 4: Small High-Low Temperature Test Chamber / Thermostatic Water Bath
Working Requirements
Precise temperature control ±0.5°C; heating compensation at low temperature, refrigeration activated at high temperature; support simple programmable temperature ramp/soak profile.
Layout
Immersion Pt100 RTD probe
OUT1 = Heating SSR; OUT2 = Refrigeration compressor / chilled water circulation pump
Built-in 2-PID heating-cooling balance suppresses minor temperature fluctuations.
Примечание: Frequent compressor start-stop should be avoided; add start-stop delay logic in PLC program.
Случай 5: Lithium Battery Formation & Aging Thermostatic Cabinet (Новая энергетика)
Working Requirements
Constant aging temperature 45°C; heater turns on when temperature drops, cooling fan activates for overheat; multiple controllers networked, MES system collects temperature data for traceability.
Architecture
Daisy-chain RS485 wiring for multiple E5EC units
PLC acts as Modbus master to poll PV(process value), SV(set value) and alarm status of each controller.
Two alarm outputs wired into safety circuit; overtemperature triggers overall equipment shutdown protection.
Случай 6: Small Rubber Curing Mold Heating Device
Working Requirements
Constant curing temperature 150~170°C; forced water cooling triggered on overtemperature; temperature adjustable locally, recipe parameters downloadable remotely.
Typical Fault Prevention
Cooling channel uses relay output, not suitable for ultra-frequent switching. PID buffering mitigates temperature fluctuation to prevent rapid cycling of cooling water valve.
Universal Wiring Logic (Applicable to all above cases)
- Источник питания: Терминал 1, 2 → AC100~240 V
- OUT1 (3,4): SSR drive → Heating load
- OUT2 (5,6): Relay output → Cooling valve / охлаждающий вентилятор
- 11(А), 12(Б): RS485 communication wires
- Sensor terminals: Wiring for Pt100 RTD / Термопара
Suitable & Unsuitable Application Summary
✅ Recommended to select E5EC-QR2ASM-820
- Systems requiring Heating + Cooling bidirectional control
- High-frequency switching heating loads driven by SSR
- RS485 Modbus communication required with PLC/HMI
- Demand for two independent alarm outputs
❌ Not recommended for this model
- Only heating function required, no cooling (choose E5EC-QX2ASM-800 for cost saving)
- Continuous 4~20 mA analog output required (select QX series)
- Heater burnout detection via CT current transformer required (choose suffix -828 models)
Контактор,автоматический выключатель,солнечный инвертор,электрический счетчик,солнечные батареи