(Altivar Process ATV650)
Объяснение кода модели: ATV650 = Altivar Process IP55 wall-mounted водить машину; D30 = 30 kW normal duty rating; N4 = 3-phase 380~480V, without integrated input disconnect switch (version with switch carries suffix E: ATV650D30N4E)
✅ Core Electrical Specifications
Номинальная мощность: 30 kW normal duty / 22 kW heavy duty (40HP / 25HP)
Поставлять: 3-phase 380…480V, 50/60 Гц
Выходной ток, обычная обязанность: 61.5 А; heavy duty current: 39.2 А (4 kHz carrier frequency)
Размер кадра: Frame B (Frame B covers 30~45 kW range)
Рейтинг корпуса: IP55, wall-mounted design for local field installation, no additional control cabinet required
Охлаждение: Принудительное воздушное охлаждение
Compatible motors: Asynchronous motors, synchronous reluctance motors
Встроенный фильтр ЭМС.: Class C2 (motor cable ≤50 m), Класс С3 (motor cable ≤150 m)
✅ Interfaces & Коммуникация
Integrated Dual-port Ethernet (Модбус TCP) + RS485 Modbus
Цифровой ввод/вывод: 8 ОТ, 3 configurable relay outputs
Аналоговый ввод/вывод: ИИ / К; on-board process PID, flow estimation, energy metering dashboard
Расширение: Supports Profibus-DP, Профинет, EtherNet/IP communication option cards
Стандартные аксессуары: Chinese graphic keypad, QR code for maintenance access, equipment asset monitoring, drift alarm, Останавливаться&Go energy-saving function
✅ Типичные применения
Water supply pumps, wastewater pumps, Вентиляторы ОВиК, градирни, chemical fluid handling, air compressors and other process fluid loads. Focused on energy saving, asset management and predictive maintenance; suitable for dusty, humid field environments (IP55)
✅ Cross-series Comparison & Замены
1. ATV650D30N4E: Same power rating, with integrated load disconnect switch
2. ATV630D30N4: Same power rating, IP20 cabinet-mounted bare drive (no outer enclosure)
3. Замена обновления: ATV660D30N4; для тяжелых ударных нагрузок, select ATV950
✅ Important Notes
IP55 units have stricter heat dissipation requirements; reserve vertical ventilation clearance above and below when wall mounting
Dual rating mode (Обычная обязанность / Сверхмощный) can be switched in parameter group 5.2
Commissioning software: SoMove, firmware version V4.6IE47
ATV650 (Altivar Process ATV600 Series) Fault Code List
1. Поставлять & Input Side Faults
1. IPF / IPL Input phase loss / 3-фазовый дисбаланс
Причина: Отсутствует входная фаза, перегоревший предохранитель, severe 3-phase voltage unbalance, 3-phase detection enabled incorrectly for single-phase supply
Средство: Check incoming circuit breaker / предохранители; set IPL to nO to disable phase loss detection if running on single-phase supply
2. OVF DC bus overvoltage
Причина: Mains voltage too high, deceleration time too short, regenerative energy from high-inertia loads
Средство: Увеличить время торможения; fit braking resistor; activate adaptive deceleration brA
3. ObF Overvoltage stall (trip due to excessive DC bus voltage)
Причина: Быстрое замедление, high load inertia, excessive regenerative energy
Средство: Увеличьте время торможения; enable stall prevention; установить тормозной блок + резистор
4. UVF DC bus undervoltage
Причина: Mains dip, momentary power loss, loose incoming connections, contactor chatter
Средство: Проверьте источник питания; extend undervoltage delay; improve wiring connections
5. PHF Supply phase sequence error
Средство: Swap any two incoming phases L1/L2/L3
2. Выход & Motor Side Faults
1. OCF Output overcurrent
Причина: Motor locked rotor, shorted output cable, пробой изоляции двигателя, rapid acceleration/deceleration
Средство: Disconnect motor and run no-load test; reduce acceleration/deceleration ramps; test cable insulation to earth with megger
2. SCF Output short-circuit / замыкание на землю
Причина: Damaged motor cable shorted to earth, motor winding earth fault, failed drive IGBT
Средство: Disconnect motor and test drive output separately; measure motor winding insulation to earth
3. OPF2 / OPF Output phase loss (потеря фазы двигателя)
Причина: Loose motor terminals, open output contactor, small motor running at light load
Средство: Tighten motor wiring; disable OPL phase loss detection if an output contactor is used; disable phase loss protection for small motors
4. OLF Motor thermal overload
Причина: Continuous overloading, заблокированный ротор, motor thermal current ITH parameter set too low
Средство: Уменьшите нагрузку; adjust motor thermal current ITH; wait for motor to cool before reset
5. OLC Drive hardware current limit overload
Средство: Уменьшите нагрузку; check output for short circuits; lower carrier frequency
6. OTF1 / OTF2 Motor PTC thermistor overheat
Причина: Motor winding overtemperature, broken or shorted PTC probe
Средство: Check motor temperature; measure PTC resistance; disable this protection if no temperature probe is fitted
3. Drive Overheating Faults
1. OHF Drive heatsink overtemperature (common fault)
Причина: Вышел из строя вентилятор охлаждения, clogged filter, insufficient mounting clearance, высокая температура окружающей среды, сильное скопление пыли
Средство: Clean air filter; check cooling fan; set fan permanent ON mode; maintain vertical ventilation clearance; monitor heatsink temperature parameter THD
2. OHFd DC reactor overtemperature
Средство: Уменьшите нагрузку; improve enclosure ventilation
4. Braking Circuit Faults
1. bUF Braking circuit fault
Причина: Open braking resistor, failed braking IGBT, свободная проводка
Средство: Check braking resistor resistance and connections; test braking unit at no load
2. bOF Braking resistor overload
Средство: Select higher resistance braking resistor; увеличить время торможения
5. Safety Circuit Faults (STO Safe Torque Off)
1. SAFF STO safety circuit fault
Причина: Mismatched timing between STOA and STOB (time difference >1 с), broken wiring, internal hardware fault
Средство: Check both STO wiring paths; ensure STOA and STOB switch simultaneously; both paths must be shorted together for bypass
2. SdF Safety function active (normal stop, not a hardware fault)
Статус: STO terminals open, drive locked; reset only after restoring STO wiring
6. Коммуникация & Analog Signal Faults
1. CnF1~CnF4 Communication link fault (Модбус TCP / RS485)
Причина: Поврежденный кабель Ethernet, incorrect termination resistor, IP address conflict, electrical noise interference
Средство: Inspect cables; use shielded communication cable; verify IP settings; reduce baud rate
2. AIF Analog input wire break (4–20 mA current signal)
Причина: Broken sensor cable, разомкнутая цепь, signal below 4 мА
Средство: Check transmitter and signal wiring; lower wire-break threshold if required
3. AOF Analog output fault
7. Internal Hardware Faults (InF series, generally hardware damage)
1. InF8 Internal power supply fault (power board supply abnormal)
Средство: Full power cycle; repeated fault = replace power board
2. InFL (InF21) Real-time clock fault, keypad communication failure
Средство: Remove keypad, remove battery and re-power; replace keypad; if fault persists, replace control board
3. InF1~InF7, InF9~InF30 Other internal hardware errors
Средство: Энергетический цикл; fault cannot be cleared → control board / power board damaged, requires repair or replacement
8. Process-specific Faults (Насос / fluid functions exclusive to ATV650)
1. iPPF Low inlet pressure protection (dry-run / low suction protection)
Причина: Недостаточное давление на входе, faulty pressure transmitter, protection threshold set too high
Средство: Check pipeline suction pressure; calibrate pressure transducer; reduce low-pressure threshold
2. HPF High pressure protection, LPF Low pressure protection, FLF Flow fault
3. DryF Dry-run protection (pump running without fluid)
Средство: Verify pump suction availability; adjust dry-run current threshold
9. Other General Faults
1. FrF Frequency feedback fault (encoder wire break)
2. USF Motor autotune failed on power-up
3. CLF Cooling circuit fault (water-cooled versions only)
4. tJF Motor stall protection
10. Fault Reset Methods
1. Автоматический сброс: Enable automatic retry via parameter Atr
2. Ручной сброс: Assign DI terminal function rSF for remote reset; reset via keypad
3. Internal hardware faults (InF codes): Require full power cycle; some faults need board replacement
Model Prefix Rules
ATV650: Altivar Process IP55 wall-mounted variable speed drive (3-фаза 380~480В)
ты: Low power range (0.75~7.5 kW); Д: Medium power range (11~90 kW); С: High power floor-standing unit (110 kW and above, IP54)
N4: Without integrated disconnect switch; N4E: With integrated load disconnect switch
Рейтинг корпуса: All wall-mounted units = IP55; floor-standing C models = IP54
Wall-mounted IP55 Full Model List (N4 without switch / N4E with switch, main domestic variants)
Frame A (0.75~22 kW)
| Номинальная мощность | Model without switch | Model with switch |
| 0.75 кВт | ATV650U07N4 | ATV650U07N4E |
| 1.5 кВт | ATV650U15N4 | ATV650U15N4E |
| 2.2 кВт | ATV650U22N4 | ATV650U22N4E |
| 3 кВт | ATV650U30N4 | ATV650U30N4E |
| 4 кВт | ATV650U40N4 | ATV650U40N4E |
| 5.5 кВт | ATV650U55N4 | ATV650U55N4E |
| 7.5 кВт | ATV650U75N4 | ATV650U75N4E |
| 11 кВт | ATV650D11N4 | ATV650D11N4E |
| 15 кВт | ATV650D15N4 | ATV650D15N4E |
| 18.5 кВт | ATV650D18N4 | ATV650D18N4E |
| 22 кВт | ATV650D22N4 | ATV650D22N4E |
Frame B (30~45 kW, includes your D30N4)
| Номинальная мощность | Model without switch | Model with switch |
| 30 кВт | ATV650D30N4 | ATV650D30N4E |
| 37 кВт | ATV650D37N4 | ATV650D37N4E |
| 45 кВт | ATV650D45N4 | ATV650D45N4E |
Кадр С (55~90 kW)
| Номинальная мощность | Model without switch | Model with switch |
| 55 кВт | ATV650D55N4 | ATV650D55N4E |
| 75 кВт | ATV650D75N4 | ATV650D75N4E |
| 90 кВт | ATV650D90N4 | ATV650D90N4E |
High Power Floor-standing Units (C range, IP54, вертикальная установка)
Model format: ATV650CxxN4F (all fitted with disconnect switch)
110/132/160/200/250/315 кВт:
ATV650C11N4F, C13N4F, C16N4F, C20N4F, C25N4F, C31N4F
Confusable Series Comparison
1. ATV650: IP55 wall-mounted, for local field installation (the series you are using)
2. АТВ630: Same power rating, IP20 cabinet bare drive, no outer enclosure
3. ATV660: Newer generation, upgrade replacement for ATV650
4. ATV950: Heavy-duty drive, for shock loads other than fans and pumps
Additional Key Information
Suffix U = low power; D = medium power; C = high power floor-standing
Suffix E = integrated load disconnect switch; no E = no switch
Standard features for all units: Dual-port Modbus TCP + RS485, built-in Class C2/C3 EMC filter, Chinese graphic keypad, STO Safe Torque Off
Контактор,автоматический выключатель,датчик,Кодер,ПЛК,Конвертер