Блок вспомогательных контактов Schneider GVAE11

GVAE11 is a 1NO + 1NC instantaneous auxiliary contact block of Schneider TeSys GV series. It is front-mounted and compatible with GV2/GV3 series motor circuit breakers. With a rated current of 2.5A and IP20 protection degree, it is used for status monitoring and signal feedback of motor control circuits, serving as a standard accessory for ...

  • Подробная информация о продукте

GVAE11 is a 1NO + 1NC instantaneous auxiliary contact block of Schneider TeSys GV series. It is front-mounted and compatible with GV2/GV3 series motor circuit breakers. With a rated current of 2.5A and IP20 protection degree, it is used for status monitoring and signal feedback of motor control circuits, serving as a standard accessory for motor control in industrial automation systems.

Сегмент кодаЗначениеОписание
GVAКатегория продуктаAuxiliary contact block for GV series
ЭМонтажное положениеFront mounting, different from side-mounted models
11Конфигурация контактов1 Нормально открытый (НЕТ) + 1 Нормально закрытый (Северная Каролина) instantaneous contacts with mechanical linkage

Полное определение модели: GVAE11 = Schneider GV series, front-mounted, 1NO+1NC instantaneous auxiliary contact block

  1. Основные технические характеристики
КатегорияТехнические характеристикиПримечания
Общие характеристики
Тип продуктаInstantaneous auxiliary contact blockМеханически связано, operates synchronously with main contacts of circuit breaker
Конфигурация контактов1НЕТ + 1Северная Каролина (Мгновенный)NO/NC status switches in sync with the main circuit of the circuit breaker
Compatible DevicesSchneider TeSys GV2/GV3 series motor circuit breakersCompatible with GV2L, GV2LE, ГВ2МЕ, GV2P, GV2RT, GV3L, GV3P and other models
Способ монтажаFront snap-on installationTool-free assembly & quick removal with precise positioning
Электрические параметры
Номинальное рабочее напряжение24–240 В переменного тока, 24–60V DCSuitable for standard voltages of control circuits
Номинальный рабочий ток2.5А (Это)Continuous current carrying capacity
Номинальное напряжение изоляции690В иComplies with insulation requirements for industrial control circuits
Механическая выносливость100,000 рабочие циклыВысокая надежность при частых операциях
Электрическая выносливость100,000 рабочие циклы (AC-15 2.5A/240V)Meets long-term service requirements of control circuits
Тип терминалаВинтовые клеммыCopper wire cross-section: 0.5–1.5mm²; Момент затяжки: 0.8–1.2Nm
Физический & Параметры окружающей среды
Степень защитыIP20Предотвращает доступ пальцев к токоведущим частям
Размеры (Ш × В × Г)45 × 20 × 15mmКомпактная структура, no extra installation space required for circuit breakers
Рабочая температура-25℃ ~ +60 ℃Широкий температурный диапазон для промышленных сред
ЦветСерыйMatches the appearance of GV series circuit breakers
СертификатыCCC, UL, CSA, ЕАСMulti-standard certifications for global application
Информация для заказа
Номер детали производителя.ГВАЭ11Official Schneider model
Стандартный код заказаГВАЭ11Original imported version
EAN-код3.38911Е+12International universal commodity code
  1. Полный список моделей (GVAE Series Auxiliary Contacts)
МодельКонфигурация контактовМонтажное положениеCompatible DevicesОсновное приложение
GVAE11NO or 1NC (Необязательный)ПереднийGV2/GV3 SeriesSimple status indication, single signal output
ГВАЭ111НЕТ + 1Северная КаролинаПереднийGV2/GV3 SeriesStandard status monitoring, output open/close signals simultaneously
GVAE202НЕТПереднийGV2/GV3 SeriesControl circuits requiring multiple NO signals
GVAE022Северная КаролинаПереднийGV2/GV3 SeriesControl circuits requiring multiple NC signals
GVAE141НЕТ + 1Северная КаролинаСторонаGV2/GV3 SeriesSide mounting for space-limited installations
GVAE242НЕТСторонаGV2/GV3 SeriesSide mounting for multiple NO signal demands
GVAE042Северная КаролинаСторонаGV2/GV3 SeriesSide mounting for multiple NC signal demands
  1. Сменные модели & Сравнение конкурентов

4.1 Internal Schneider Replacements

Оригинальная модельЗапасная модельРазличияСценарии применения
ГВАЭ11GVAE14Different mounting position (боковой монтаж)Insufficient front space, side mounting required
ГВАЭ11ГВ2МЕ + Встроенные контактыИнтегрированный дизайн, no extra assembly neededNew equipment selection for integrated layout
ГВАЭ11ГВ3П + Встроенные контактыUpgraded series with enhanced functionsHigh-standard applications requiring advanced protection

4.2 Межбрендовое сравнение конкурентов

БрендМодельКонфигурация контактовCompatible DevicesОсновные различия
ШнайдерГВАЭ111НЕТ + 1Северная КаролинаGV2/GV3 SeriesPrecise mechanical linkage, защита IP20, высокая совместимость
АББMS132-011НЕТ + 1Северная КаролинаMS132 SeriesSide mounting, номинальный ток 3А, similar price
Сименс3RV2091-1A1НЕТ + 1Северная Каролина3RV20 SeriesВставной монтаж, rated current 2A, complete certifications
ИтонPKZM0-AUX111НЕТ + 1Северная КаролинаPKZM0 SeriesFront mounting, rated current 2.5A, spring terminals
ЧинтNXC-A111НЕТ + 1Северная КаролинаСерия NXCЭкономически эффективный, reliable domestic alternative
  1. Среды приложений & Типичные случаи

5.1 Рекомендуемые приложения

Motor Control Circuit: Feedback circuit breaker ON/OFF status for PLC/DCS system monitoring

Alarm System: Trigger audible and visual alarms via NC contacts when the circuit breaker trips

Блокировочное управление: Prevent simultaneous startup of multiple motors and realize sequence control

Удаленный мониторинг: Transmit status signals to SCADA system for remote diagnosis

Safety Circuit: Form safety protection circuits together with emergency stop buttons

5.2 Нерекомендуемые приложения

Main Circuit Usage: Rated current is only 2.5A, not applicable for motor main circuits

High-frequency Switching: Над 1000 switching cycles per hour will shorten service life

Severe Electromagnetic Interference Environment: Additional shielding is required to avoid malfunction

Humid/Corrosive Environment: Защита IP20 недостаточна; install extra enclosure or select higher protection grade products

5.3 Типичные случаи применения

Случай 1: Pump Unit Control in Wastewater Treatment Plant

Оборудование: 15kW submersible pump, GV2P32 circuit breaker + GVAE11 auxiliary contact

Конфигурация: NO contact of GVAE11 connected to PLC digital input module; NC contact connected to alarm circuit

Исход: Real-time monitoring of pump operating status, automatic alarm and event recording upon faults

Случай 2: Conveyor System in Automotive Production Line

Оборудование: 12 конвейерные линии, each equipped with GV2P32 + ГВАЭ11

Конфигурация: GVAE11 contacts linked with PLC to realize sequential startup and interlock protection for conveyors

Функции: Mechanical linkage ensures accurate status feedback and reduces misjudgment of control systems

  1. Поиск неисправностей & Руководство по техническому обслуживанию

6.1 Распространенные неисправности & Решения

Явление неисправностиВозможные причиныРешения
No change of contact signals1. Improper installation of contact block1. Reinstall the block and ensure the clip is fully engaged
2. Damaged mechanical linkage2. Inspect linkage mechanism and replace damaged unit
3. Burned or oxidized contacts3. Clean or replace the contact block
4. Неправильная проводка4. Check wiring and confirm correct connection of NO/NC contacts
Контактная сварка1. Excessive current in control circuit1. Ensure control circuit current ≤ 2.5A
2. Overheating caused by frequent switching2. Reduce switching frequency or select higher-rated contacts
3. Дуговая эрозия3. Replace with a new contact block
Signal interference1. Control wires not separated from main wires1. Separate control wires from main wires (spacing ≥ 100mm)
2. No shielded cable used2. Use shielded cable with single-end grounding
3. Poor grounding3. Inspect and ensure reliable grounding
Loose installation1. Clip not fully locked1. Reinstall until a click sound is heard
2. Loosening caused by vibration2. Fit shock-absorbing pads or reinforce installation

6.2 Процедуры технического обслуживания

  1. Ежедневный осмотр (Еженедельно)

Check installation condition and ensure no looseness

Inspect terminals for overheating and looseness

Test contact switching to confirm synchronization with circuit breaker

  1. Регулярное техническое обслуживание (Каждый 6 Месяцы)

Power off and remove dust on the contact block

Измерьте контактное сопротивление (shall be ≤ 50mΩ)

Check flexibility of mechanical linkage

  1. Ежегодное обслуживание

Replace frequently used contact blocks

Test insulation performance of control circuits

Retighten all electrical connections

6.3 Советы по быстрой диагностике

Нет сигнала? Check installation and linkage first.

Contact welded? Limit current and cut switching times.

Signal interference? Separate wires, apply shielding and good grounding.

Loose fitting? Re-clip firmly and add shockproof measures for vibrating sites.

  1. Выбор & Рекомендации по установке

7.1 Правила выбора

Совместимость: Confirm matching with GV2/GV3 series circuit breakers; not applicable for other series

Конфигурация контактов: Select 1NO+1NC (ГВАЭ11), 2НЕТ (GVAE20) or 2NC (GVAE02) according to control demands

Монтажное положение: Choose GVAE11 for front mounting, GVAE14 for side mounting

Текущее соответствие: Control circuit current shall not exceed 2.5A; select higher-specification products if overloaded

7.2 Примечания по установке

Installation Sequence: Install circuit breaker first, then attach the contact block and fully lock the clip

Стандарт проводки: Use 0.5–1.5mm² copper wires with tightening torque of 0.8–1.2Nm; avoid over-tightening

Clear Marking: Label NO/NC contacts to prevent wiring errors

Linkage Test: Manually operate the circuit breaker after installation to verify synchronous contact action

Меры защиты: Install extra enclosures for dusty or humid environments

  1. Статус производства & Решения по замене

Current Status of GVAE11: В производстве, нет плана прекращения (по состоянию на июнь 2026)

Обновление & Варианты замены:

  1. Функциональное обновление: GV3 series models with built-in contacts (no extra assembly, fewer fault points)
  2. Интеллектуальное обновление: TeSys T series (with communication function for network-based status transmission)
  3. Внутренняя альтернатива: Compatible domestic GVAE11 models (более низкая стоимость при эквивалентной производительности)