Schneider LC1E1801 Contactor

Объяснение кода модели: LC1E = TeSys E series contactor; 18 = rated 18A at 400V under AC-3 duty; 01 = built-in 1 нормально закрытый контакт (1Северная Каролина) ⚠️ The LC1E series has been discontinued (production stopped in July 2020). The standard replacement model is LC1N1801, fully compatible in mounting, terminal layout and performance. Key Specifications Main ...

  • Подробная информация о продукте

Объяснение кода модели: LC1E = TeSys E series контактор; 18 = rated 18A at 400V under AC-3 duty; 01 = built-in 1 нормально закрытый контакт (1Северная Каролина)

⚠️ The LC1E series has been discontinued (production stopped in July 2020). The standard replacement model is LC1N1801, fully compatible in mounting, terminal layout and performance.

Ключевые характеристики

Основные контакты: 3П, 3НЕТ

АС-3 (моторный долг): 18А при 400 В; АС-1 (резистивная нагрузка): 25А

Номинал двигателя: 7.5kW @ 380/400V; 4кВт при 220 В; 9kW @ 440V

Напряжение изоляции Ui: 690В; Импульсное выдерживаемое напряжение Uimp: 6кВ

Вспомогательный контакт: 1Северная Каролина (Нормально закрытый)

Монтаж: DIN-рейка / винтовое крепление опорной пластины

Габаритные размеры: W45mm × H74mm × D80mm, net weight ≈0.3kg

Класс защиты: IP20; Рабочая температура: -5~+55℃; No derating up to 3000m altitude

Механическая жизнь: 10 миллион операций; Электрический ресурс AC-3: 1.2 миллион операций; Максимальная рабочая частота: 1800 циклов/час

Coil suffix definitions (complete model number)

LC1E1801B5: 24 В переменного тока, 50Гц

LC1E1801F5: 110 В переменного тока, 50Гц

LC1E1801M5: 220 В переменного тока, 50Гц (наиболее распространен в Китае)

LC1E1801Q5: AC380В, 50Гц

Суффикс 7 = 50/60Hz universal; суффикс 6 = 60Hz only

Потребляемая мощность катушки (M5 220V example)

Inrush VA: 95Вирджиния; Sealed holding VA: 8.5Вирджиния; Coil heat dissipation: 2~3W

Напряжение срабатывания: 0.85~1.1Uc; Падение напряжения: 0.3~0.6Uc

Момент затяжки & wire gauge

Torque for main circuit and control circuit terminals: 1.2 Н·м

Сплошная проволока: 1.5~6 мм²; Многожильный провод (с наконечником): 1~4mm²

Matching selection reference

Соответствующее тепловое реле перегрузки: LRD07 / LRN07 (current range suitable for 18A)

Аксессуары: LA1EN auxiliary contact block, LA9D coil surge suppressor, mechanical interlock block

Отечественная альтернатива: CJX2-1801 (similar outline, pay attention to mounting hole and marking differences)

Руководство по устранению неполадок

  1. На катушку подается напряжение, но нет втягивания: Check if coil voltage is within 0.85~1.1Uc; inspect broken coil wire and loose terminals
  2. Pulled in but main circuit no continuity: Эрозия основного контакта, contact welding, свободная проводка
  3. Buzzing / болтовня: Пониженное напряжение, large harmonic distortion, dust accumulated on core faces
  4. Failed to drop out after power-off: Welded main contacts, core stuck by oil and dirt

Detailed Installation Procedure for Шнайдер LC1E1801 Contactor

⚠️ Safety precondition: Operated by qualified electricians; cut off all power supply and verify zero voltage before installation. LC1E1801: 3P main contacts with built-in 1NC auxiliary contact. Маркировка клемм: Main circuit L1/L2/L3 (line side, incoming), Т1/Т2/Т3 (сторона нагрузки, outgoing); Coil A1, А2; Вспомогательный контакт: 95, 96 (1Северная Каролина)

  1. Предустановочная подготовка
  2. Проверьте напряжение катушки: LC1E1801M5=AC220V, Q5=AC380V, F5=AC110V. Coil rated voltage must match control circuit voltage to avoid coil burnout.
  3. Визуальный осмотр: No shell cracks, intact terminals, armature moves freely without jamming when pressed manually.
  4. Инструменты: 2 крестовая отвертка, инструмент для зачистки проводов, мультиметр, динамометрический ключ; 35mm standard DIN rail or mounting base plate.
  5. Wire specification

Main circuit solid wire: 1.5~6mm²; Stranded wire with ferrule: 1~4mm²

Схема управления (А1/А2, вспомогательные контакты): 0.75~1.5mm²

Момент затяжки: 1.2 Н·м (avoid over-tightening to prevent thread stripping, or loose connection causing overheating)

  1. Environmental check: Cabinet temperature -5℃~+55℃, keep away from dust, влага и масло. Mount vertically upright. Do NOT install upside down or horizontally.
  2. Исправление (2 methods: DIN-рейка / винтовое крепление опорной пластины)

Метод 1: 35мм Монтаж на DIN-рейку (предпочтительный)

  1. The contactor has upper hooks and a spring locking clip at the bottom.
  2. Hook the upper notch onto the top edge of the DIN rail first.
  3. Press the bottom of the contactor down until you hear a click, the bottom clip locks onto the rail.
  4. Shake lightly to confirm firm fixation. Удаление: Use a flat screwdriver to pry down the bottom clip and pull out the contactor.

Метод 2: Screw mounting on insulated base plate (no rail)

  1. Mark and drill holes on the insulated plate according to the rear mounting holes (for M4 screws).
  2. Insert screws diagonally, pre-tighten, then torque evenly in diagonal sequence; do not force one side to avoid casing deformation.
  3. Accessory Fitting (Необязательный: LA1EN auxiliary block, mechanical interlock etc.)
  4. Top auxiliary contact block: Align with the slots on top of contactor, push vertically down until latched.
  5. Thermal relay LRD/LRN: Clip directly underneath the contactor, align positioning slots; the linkage will engage automatically.
  6. Surge suppressor LA9D: Clip beside coil terminals A1/A2, absorbs back EMF to protect PLC output points.
  7. Последовательность подключения (Main circuit → Auxiliary contacts → Coil control circuit)

Standard routing: Line side on top, load side on bottom. L1/L2/L3 on top for three-phase supply; T1/T2/T3 at bottom for load (мотор).

  1. Проводка главной цепи

Strip insulation 5~6mm, avoid loose copper strands; ferrules are mandatory for stranded wire.

Keep phase sequence L1→T1, L2→T2, L3→T3 as per drawing.

Torque screws to 1.2N·m; only one conductor per terminal.

  1. Built-in auxiliary contact (95-96, Северная Каролина)

Терминалы 95-96: Conductive when coil de-energized, open when contactor pulls in. Usually used in stop circuit or fault feedback for motor control.

If NO contact is required, add LA1EN auxiliary block.

  1. Coil A1, А2 (схема управления)

A1 and A2 have no polarity for AC. For AC220V: one to live, one to neutral; for AC380V: connect to two different phases.

Wire in series with start/stop pushbuttons, thermal relay NC contact or PLC outputs.

Route control wires separately from power cables to reduce interference.

Terminal summary:

Л1/Л2/Л3 (Supply In), Т1/Т2/Т3 (Load Out), A1 A2 (Катушка), 95-96 (Встроенный 1NC)

  1. Проверка перед включением
  2. Визуальная проверка: All terminals tightened, no exposed copper, no short circuit risk, no loose strands touching adjacent terminals.
  3. Проверка непрерывности с помощью мультиметра:

Обесточенное состояние: No continuity between L-T; 95-96 auxiliary contact is conductive.

Manually press armature to simulate pull-in: L-T becomes conductive, 95-96 открывается.

  1. Double-check coil voltage; separate power supply for main circuit and control circuit.
  2. Включение питания
  3. Energize control circuit only, keep main power off: Press start button, contactor should pull-in smoothly without chattering or buzzing; release stop button for reliable drop-out.

болтовня: Низкое напряжение питания, loose wiring or dirty core surfaces.

  1. After control circuit test passes, energize main circuit and run on load.
  2. Temperature check after 10min running: No obvious overheating at terminals (temperature rise indicates poor connection).
  3. Примечания по установке & Запреты
  4. Keep minimum clearance ≥10mm between contactor and fuse / MCB for heat dissipation.
  5. Minimum spacing ≥5mm between multiple contactors; increase spacing for high ambient temperature.
  6. Do not plug or remove auxiliary blocks when energized.
  7. Do not trap wire insulation inside terminal clamps; copper must be fully clamped.
  8. LC1E discontinued, spare replacement: LC1N1801, same mounting size and terminal definition.
  9. Распространенные ошибки при установке

No pull-in after energized: Wrong A1/A2 voltage, broken control wire or open button circuit

Buzzing when pulled in: Пониженное напряжение, dust or rust on magnetic core faces

Cannot drop out after power cut: Welded main contacts or core jammed by oil

Schneider Easy TeSys E (LC1E / EasyPact ТВС) Series Full List

Важное примечание: LC1E series fully discontinued in July 2020. Прямая замена: LC1N series, идентичные монтажные размеры и расположение клемм.

Модельное правило: LC1E + current code + auxiliary contact code (10=1НО; 01= 1 НЗ) + coil suffix

Coil suffix description:

B5=AC24V 50Hz; F5=AC110V 50Hz; M5=AC220V 50Hz; Q5=AC380V 50Hz

B7/F7/M7/Q7=50/60Hz universal; БД=24В постоянного тока; 6=60Hz only

  1. 3P LC1E Contactors (AC-3 при 400 В)
Базовая модельAC-3 ТокMotor Rating @400VBuilt-in Auxiliary Contact
LC1E06106А2.2кВт1НЕТ
LC1E06016А2.2кВт1Северная Каролина
LC1E09109А4кВт1НЕТ
LC1E09019А4кВт1Северная Каролина
LC1E121012А5.5кВт1НЕТ
LC1E120112А5.5кВт1Северная Каролина
LC1E181018А7.5кВт1НЕТ
LC1E180118А7.5кВт1Северная Каролина (your referenced model)
LC1E251025А11кВт1НЕТ
LC1E250125А11кВт1Северная Каролина
LC1E321032А15кВт1НЕТ
LC1E320132А15кВт1Северная Каролина
LC1E381038А18.5кВт1НЕТ
LC1E380138А18.5кВт1Северная Каролина
LC1E401140А18.5кВт1НО+1НЗ
LC1E501150А22кВт1НО+1НЗ
LC1E651165А30кВт1НО+1НЗ
LC1E801180А37кВт1НО+1НЗ
LC1E951195А45кВт1НО+1НЗ
LC1E120120А55кВтНет встроенного, add auxiliary block separately
LC1E160160А75кВтНет встроенного, add auxiliary block separately
LC1E200200А90кВтНет встроенного, add auxiliary block separately
LC1E300300А160кВтНет встроенного, add auxiliary block separately

Example complete model: LC1E1801M7 = 18A, 1Северная Каролина, AC220V 50/60Hz universal

  1. Matching LRE Thermal Overload Relays (plug-on fit for LC1E)

LRE01N~LRE35N (for 06~38A); LRE322N~LRE365N (for 40~300A)

LRE01N: 0.1~0.16A

LRE02N: 0.16~0.25A

LRE03N: 0.25~0.4A

LRE04N: 0.4~0.63A

LRE05N: 0.63~1А

LRE06N: 1~1,6 А

LRE07N: 1.6~2,5 А

LRE08N: 2.5~4А

LRE09N: 4~6А

LRE10N: 6~10А

LRE12N: 10~16А

LRE14N: 16~24A

LRE16N: 24~36A

LRE21N: 28~36A

LRE22N: 36~48A

LRE322N: 55~70A

LRE323N: 63~80А

LRE353N: 80~104A

LRE355N: 104~135A

LRE365N: 130~165A

  1. E-series Accessories
  2. LA1EN: Top-mounted auxiliary contact block (1НЕТ / 1Северная Каролина, stackable)
  3. LAEM1: Модуль механической блокировки (for two contactor interlocking)
  4. LA9D: Ограничитель перенапряжения катушки (Радиоуправляемая сеть / варистор, PLC output protection)
  5. LAEB1N / LAEB3N: Thermal relay independent base (when not mounted under contactor)
  6. LA1EBN: Timed auxiliary contact block (задержка включения / задержка выключения)
  7. 2П / 4P LC1E (single phase, освещение & резистивная нагрузка, АС-1 дежурство)

LC1E0920: 2Вопрос 9А

LC1E2520: 2П 25А

LC1E0940: 4Вопрос 9А

LC1E2540: 4П 25А

LC1E4040: 4P 40A

4P versions commonly used for HVAC, lighting and heating resistive loads

  1. Cross Reference Table
Old LC1E ModelDirect Replacement LC1N
LC1E0601/0610LC1N0601 / LC1N0610
LC1E0901/0910LC1N0901 / LC1N0910
LC1E1201/1210LC1N1201 / LC1N1210
LC1E1801/1810LC1N1801 / LC1N1810
LC1E2501/2510LC1N2501 / LC1N2510
LC1E3201/3210LC1N3201 / LC1N3210
LC1E3801/3810LC1N3801 / LC1N3810
LC1E40~95LC1N40~95