Harmony RM22-L Реле контроля уровня (Conductive Electrode Liquid Level Monitoring)
Интерпретация модели: RM22 series modular control relay; LG = liquid level single detection; 11 = 1 переключающий контакт (C/O); MR = power supply 24~240V AC/DC; MT version for 380~415V AC power supply
✅ Основные функции
Designed for conductive liquids (вода, sewage, и т. д.) for automatic liquid level control. Two operating modes available:
- Fill Mode (Водоснабжение) : When liquid level falls below Min electrode → relay energizes, starts fill pump; when liquid level reaches Max electrode → relay de-energizes, stops pump.
- Drain Mode (Sump Pumping) : When liquid level reaches Max electrode → relay energizes, starts drain pump; when liquid level drops below Min electrode → relay de-energizes, stops pump.
It adopts resistance probe detection, judging liquid level based on liquid conductivity, not float switch. Adjustable detection sensitivity.
📋 Electrical Specifications
Напряжение питания: 24~240 В переменного/постоянного тока (универсальный для переменного тока & округ Колумбия), 50/60Гц; operating range 20.4~264V
Потребляемая мощность: AC 5VA / DC 1.5W
Output contact: 1 changeover contact 1C/O (11-12 нормально закрытый, 11-14 нормально открытый), AC-15/DC-13, 8А при 250 В переменного тока
Power-on delay: 0.6с
Probe circuit: Макс. 12V AC at electrodes, electrode current ≤1mA; maximum probe cable length 1000m
Чувствительность: St standard sensitivity 5kΩ~100kΩ, continuously adjustable via potentiometer
Монтаж: DIN-рейка, width 22.5mm
Защита: Sealing transparent protective cover to prevent on-site misadjustment; built-in diagnostic test button + status LED indicator
📌 Определение терминала
| Терминал | Описание |
| A1,A2 | Relay working power supply |
| Мин | Low liquid level electrode |
| Макс | High liquid level electrode |
| С | Common reference electrode (reference pole) |
| 11 | Contact common terminal |
| 12 | Normally closed NC |
| 14 | Normally open NO |
Примечание по проводке: 3 electrodes inside tank: C common pole, Min minimum liquid level, Max maximum liquid level. Only applicable to conductive liquids; not for insulating oil and other non-conductive media.
🛠️ Типичные применения
Водоснабжение & drainage tanks, sewage pools, градирни, water purification equipment, automatic pump start/stop, DIN rail mounting inside control cabinet.
⚠️ Model Differentiation & Справочник по замене
- RM22LG11MR: 24~240 В переменного/постоянного тока, single changeover contact
- RM22LG11MT: 380~415V AC power supply version
- RM22LA32MR: Dual-contact version, two-channel output
Замена устаревшего оборудования: RM35LM series (прекращено, replace with RM22LG for new projects)
Operating Principle of Шнайдер RM22LG11MR
Основной принцип: AC resistive conductive liquid level detection (Conductivity type)
A low-voltage AC sensing signal is applied between electrodes. The device measures liquid resistance between two electrodes and compares it with the sensitivity threshold set on the front panel. The internal circuit drives output relay action.
Сигнал переменного тока низкого напряжения на стороне зонда во избежание электролитической коррозии электродов, вызванной постоянным током..
- Схема обнаружения
Реле выводит чувствительный сигнал переменного тока низкого напряжения. (около 12 В переменного тока, ток<1 мА) между С (общий электрод), Мин (низкий уровень), Макс (высокий уровень).
Электрод погружен в жидкость → проводящая жидкость образует путь между C и электродом, низкое сопротивление;
Электрод находится над жидкостью → цепь разомкнута, чрезвычайно высокое сопротивление;
Потенциометр устанавливает порог чувствительности (5кОм~100 кОм) : Измеренное сопротивление < пороговое значение → обнаружена жидкость; сопротивление > пороговое значение → жидкость не обнаружена.
👉 Действительно только для проводящих жидкостей. Неприменимо для масла., сверхчистая вода (очень низкая проводимость) и изоляционные жидкости.
- Два режима работы (3-точечный контроль уровня жидкости с логикой памяти гистерезиса)
1) Fill Mode (Подпитка водой)
Уровень жидкости ниже минимального электрода: C-Min circuit open → internal relay energizes, 11-14 NO closes, starts fill pump.
Liquid level rises, submerges Min but not reaching Max: C-Min conductive, internal memory holds status, pump keeps running.
Liquid level reaches Max electrode: C-Max conductive → relay resets, 11-14 открывается, насос останавливается.
If liquid level drops but remains above Min, pump will not start. Two-point start/stop prevents frequent pump cycling.
2) Drain Mode (Sump Drainage)
Liquid level reaches Max electrode: C-Max conductive → relay energizes, 11-14 NO closes, starts drain pump.
Liquid level falls, leaves Max but still higher than Min: memory holds status, pump keeps draining.
Уровень жидкости ниже минимального электрода: C-Min open → relay resets, насос останавливается.
- Single Level Mode (Необязательный, 2 электроды)
Use only C+Max or C+Min for single-point alarm / контроль. Small delay can be enabled to suppress false triggering caused by liquid wave and foam.
- Internal Signal & Выход
- A1/A2 supplies power to relay (24~240V AC/DC wide range), Силовая цепь электрически изолирована от цепи измерения зонда;
- Схема измерения непрерывно измеряет сопротивление между электродами.;
- Логический блок определяет состояние на основе сигналов режима и электродов., диски 1 переключающий контакт (1C/O, 11 общий,12 Северная Каролина,14 НЕТ);
- Светодиод на передней панели указывает состояние выхода; встроенная кнопка тестирования имитирует состояние ввода контура в эксплуатацию.
- Ключевые особенности конструкции
- Измерение переменного тока: На электроды не подается постоянное напряжение, предотвращает электролиз, генерация пузырей, коррозия электродов и ускоренное окалинообразование.
- Регулируемый порог сопротивления: Адаптироваться к канализации / чистая вода с различной проводимостью через ручку чувствительности.
- Гистерезисная логика памяти: Требует признания высокого & точки низкого уровня, позволяет избежать частого переключения реле, вызванного незначительными колебаниями жидкости.
- Максимальная длина электродного кабеля до 1000 м.. Остерегайтесь паразитных емкостных помех при использовании длинных кабелей.; ложное срабатывание имеет тенденцию происходить при высокой настройке чувствительности.
- Соответствие неисправностей на основе принципа
Накипь на электроде → эквивалентное сопротивление жидкости превышает пороговое значение → жидкость присутствует, но устройство сообщает об отсутствии жидкости;
Слой проводящего пенопласта → электрод не касается фактического уровня жидкости, но цепь проводит ток → ложное обнаружение уровня жидкости;
Плохой контакт электрода C → потерян эталон измерения., все определения уровня жидкости недействительны.
Устранение неполадок Schneider RM22LG11MR
Метод предварительной диагностики: Кнопка Т-теста на передней панели. Нажмите T при включении питания, чтобы переключить состояние релейного выхода., чтобы отличить неисправность устройства или внешний электрод / неисправность проводки.
Вина 1: Нет реакции после включения, индикатор питания выключен
Симптом: Напряжение питания A1/A2 в норме, нет светодиодной подсветки, реле без действия
Причины
- Ослабленная проводка A1/A2, плохой контакт клемм; неправильная полярность источника постоянного тока
- Input voltage out of 24~240V AC/DC operating range
- Internal power circuit damaged (молния, transient overvoltage, короткое замыкание)
Решения
- Выключить питание, measure voltage at A1/A2, затянуть клеммы; check polarity for DC supply
- Verify supply within rated range; check upstream MCB and fuse
- Replace unit if LED still off with correct supply voltage
Вина 2: Relay does not act when electrode submerged (liquid detected but no response)
Симптом: Liquid covers Max/Min electrode, relay status unchanged, pump does not start/stop
Причины
- Electrode covered by scaling / sludge, liquid equivalent resistance exceeds sensitivity threshold
- Poor contact of C common electrode (most frequent), measurement reference lost
- Broken electrode cable, loose wiring at Min/Max/C terminals
- Sensitivity set too low (resistance threshold too small for sewage to conduct)
- Medium conductivity too low (сверхчистая вода, insulating liquid, not suitable for this model)
Решения
- Remove electrodes, чистый / polish scale and sludge; regular electrode maintenance
- Priority check C electrode: ensure C is immersed in liquid and wiring secure
- Выключить питание, test cable continuity, tighten Min/Max/C terminals
- Increase sensitivity appropriately (raise resistance threshold, adjustable from 5kΩ~100kΩ)
- For low-conductivity water / масло, use float level switch instead
Вина 3: Relay false action when liquid level below electrode (detects liquid with no actual liquid), pump starts unexpectedly
Симптом: Liquid level below electrodes, relay reports liquid present, pump starts mistakenly
Причины
- Conductive foam / scum on liquid surface closes electrode circuit (common in sewage tank)
- Long electrode cable, stray capacitance causes false trigger (>300m is high risk)
- Sensitivity set too high, minor leakage triggers detection
- Electrode cable routed in parallel with power cable, электромагнитные помехи
- Terminal condensation / leakage between electrodes
Решения
- Поднимите положение установки электрода, чтобы избежать пенообразования.; установить пенопластовую перегородку
- Уменьшите чувствительность; используйте экранированный кабель для длинного сигнального провода, экран с односторонним заземлением; отдельно от силовых кабелей
- Очистка терминалов от конденсата, улучшить влагостойкость шкафа
Вина 4: Частый пуск-стоп насоса, реле болтовня / колебание
Симптом: Уровень жидкости стабильный в пределах диапазона, реле неоднократно подает питание и обесточивает, насос работает быстро
Причины
- Сильная турбулентность жидкости, Поверхность жидкости неоднократно проходит по электродам; прерывистая проводимость пеной
- Грязные электроды, нестабильное сопротивление электродов
- Неправильный режим работы, логика гистерезиса отключена (проводной только один электрод)
Решения
- Выдвижение электродов, установить противопомпажную втулку; установить электроды в спокойной зоне резервуара
- Очистите электроды, тонкая настройка чувствительности и избежание критических настроек
- Стандартная 3-электродная проводка (С+Мин+Макс), включить встроенную логику памяти с гистерезисом, избегать одноточечного контроля
Вина 5: Светодиод реле в норме, но выходной контакт неактивен, насос не запускается
Симптом: Светодиодный индикатор уровня правильный, но выходной контактор / насос не работает
Причины
- Неправильная разводка выходных контактов (11/12/14 клеммы неправильно подключены)
- Контактная нагрузка превышает номинальный ток 8А, контактная эрозия / сварка / разомкнутая цепь
- Нет питания в цепи управления ниже по потоку
Решения
- Выключите питание и проверьте контактную проводку.: 11 общий, 12 Северная Каролина,14 НЕТ
- Нажмите кнопку T test и измерьте непрерывность между 11-14; обрыв цепи = контакт поврежден, заменить реле
- Проверьте источник питания управления насосом. / контактор
Вина 6: Контактная сварка, насос работает постоянно и не может остановиться
Симптом: Уровень жидкости достигает положения остановки, выход остается закрытым, насос не может выключиться
Причины
- Длительная перегрузка, электрическая дуга вызывает контактную сварку
- Нет поглощения перенапряжений для катушки контактора, обратная ЭМП повреждает контакты
Решения
- Немедленно замените RM22LG11MR, если контакты приварились.
- Добавьте RC-демпфер или безынерционный диод для индуктивной нагрузки. (катушка контактора) для защиты внутренних контактов 8А
Рекомендуемая последовательность устранения неполадок на месте
- Включение питания, проверьте светодиод питания; LED off → inspect A1/A2 power supply
- Press T test button and observe output toggle
Output toggles by T: Unit healthy, fault in electrode, cable or liquid medium
No response by T: Relay unit damaged, заменить напрямую
- Verify C common electrode fully immersed and wiring tightened
- Clean electrodes and adjust sensitivity knob
- Check if signal cable runs together with power cable; use shielded cable for long distance
- Confirm mode selection: Fill (водоснабжение) / Drain (дренаж)
Preventive Maintenance
- Sewage application: Clean electrodes every 3~6 months to prevent scaling
- Keep electrode cable length within 500m where possible; reduce sensitivity and adopt shielded cable if longer
- Ensure cabinet moisture-proof to avoid terminal condensation leakage
- Install surge absorption device for inductive load (контактор) to protect 8A contacts
Schneider RM22 Harmony Modular Monitoring Relay Full Series List
Общие характеристики серии: Монтаж на DIN-рейку, width 22.5mm (RM22TG20:17.5мм); equipped with T test button, status LED, sealable transparent cover; рейтинг контактов: 8А при 250 В переменного тока; suffix MR=24~240V AC/DC universal supply; MT=380~415V AC supply
- RM22L Conductivity Level Monitoring Relay (series of your model)
Conductive electrode liquid level detection for high/low level control of water tank and sewage sump
|RM22LG11MR|1C/O (1 переключение)|24~240 В переменного/постоянного тока|Стандартная модель, your reference unit, sensitivity 5k~100kΩ|
|RM22LG11MT|1C/O|380~415 В переменного тока|High voltage supply level relay|
|RM22LA32MR|2C/O (2 переключение)|24~240 В переменного/постоянного тока|Dual-channel output, 3 sensitivity levels: LS/St/HS|
|RM22LA32MT|2C/O|380~415 В переменного тока|Dual-contact high voltage supply level relay|
- RM22T 3-phase Power Monitoring Relay (Последовательность фаз / потеря фазы / 3-фазовый дисбаланс / перенапряжение & пониженное напряжение)
Monitor 3-phase power supply for motor, водяной насос, air compressor protection
|RM22TA31|2C/O|Последовательность фаз, потеря фазы, 3-фазовый дисбаланс|200~240 В переменного тока|
|RM22TA33|2C/O|Последовательность фаз, потеря фазы, 3-фазовый дисбаланс|380~480VAC|
|RM22TU21|2C/O|Последовательность фаз, потеря фазы, пониженное напряжение|200~240 В переменного тока|
|РМ22ТУ23|2C/O|Последовательность фаз, потеря фазы, пониженное напряжение|380~480VAC|
|RM22TR31|2C/O|Последовательность фаз, потеря фазы, разбалансировать, overvoltage/undervoltage with delay|200~240 В переменного тока|
|RM22TR33|2C/O|Последовательность фаз, потеря фазы, разбалансировать, overvoltage/undervoltage with delay|380~480VAC|
|RM22TG20|2C/O|Последовательность фаз, потеря фазы (compact version,17.5мм)|183~528VAC|
- RM22U Single-phase / DC Voltage Monitoring Relay (Перенапряжение & Undervoltage monitoring)
AC/DC single-phase voltage monitoring for DC panel and single-phase power protection
|RM22UA32MR|2C/O|1~100V AC/DC|24~240 В переменного/постоянного тока|
|RM22UA33MR|2C/O|15~500V AC/DC|24~240 В переменного/постоянного тока|
|RM22UA33MT|2C/O|15~500V AC/DC|380~415 В переменного тока|
|RM22UB34MR|2C/O|Wide range single phase voltage|24~240 В переменного/постоянного тока|
- RM22J Current Monitoring Relay (AC current monitoring, перегрузка / undercurrent)
Work with current transformer CT for motor load current monitoring
|RM22JA21MR|1C/O|0.1~5A AC|24~240 В переменного/постоянного тока|
|RM22JA32MR|2C/O|0.1~5A AC|24~240 В переменного/постоянного тока|
- Правило кодирования модели (RM22XXYYZZ)
- 22 ринггита: Series code Harmony modular monitoring relay
- ХХ: Function group
LG: Liquid level, single sensitivity
ТО: Liquid level, multi-range sensitivity
TA/TU/TR/TG: 3-phase power monitoring
UA/UB: Single-phase voltage monitoring
И: Current monitoring
- ГГ: Контактное количество
11: 1 переключающий контакт (1C/O)
32: 2 переключающие контакты (2C/O)
- ZZ: Power supply code
MR: 24~240V AC/DC universal (most widely used in engineering)
МТ: 380~415V AC 3-phase high voltage supply
- Legacy Model Replacement (RM35 → RM22)
RM35LM old level relay → RM22LG / RM22LA
RM35TA/TU old 3-phase protection relay → RM22TA/TR/TU
RM35 series discontinued, select RM22 for new projects
- Таблица быстрого выбора
| Приложение | Рекомендуемая модель |
| Танк / sump conductivity level, single pump start-stop | RM22LG11MR (your reference model) |
| Liquid level control requiring two independent alarm/output channels | RM22LA32MR |
| 3-фазовый двигатель: потеря фазы + последовательность фаз + unbalance protection | RM22TA33 |
| 3-phase power: потеря фазы + последовательность фаз + над & undervoltage full protection | RM22TR33 |
| Motor load current monitoring (CT sensing) | RM22JA21MR |
| DC panel, single phase over & сигнализация пониженного напряжения | RM22UA33MR |