Order Number Coding Breakdown
3RW4435-6BC45
- 3RW: Сименс SIRIUS soft starter series
- 44: High-end heavy-duty full-function model (3-phase thyristors, integrated bypass, Сорт 30 heavy overload support, PTC thermistor protection, soft braking, inside-delta connection compatible)
- 35: Код размера, rated operating current 134A
- 6: Screw terminals for control circuit (2 = spring cage terminals); main circuit connected via copper busbars
- BC: Core function definition
B = Integrated bypass contactor (short-circuits thyristors during operation to reduce heat loss)
C = Full 3-phase controlled thyristors (higher starting torque and balanced current compared to 2-phase BB versions)
- 45: Control supply voltage AC 230V (44 = AC 110V, 46 = AC/DC 24V)
- Core Electrical Rated Parameters (40°C Ambient, Сорт 10 Standard Load)
- Номинальный ток & Matching Motor Power
| Тип подключения | Rated Current Ie | Matching Motor @ 400V | Matching Motor @ 500V | Matching Motor @ 600V |
| Standard Main Circuit (External Motor Connection) | 134А | 75кВт | 90кВт | 110кВт |
| Inside-Delta Connection (Motor Terminal Side) | 232А | 132кВт | 160кВт | 200кВт |
- Схема управления
Control supply: AC 230V ±10% (defined by suffix 45)
Control terminals: Screw fastening; Standard digital start/stop, fault relay, running feedback, PTC thermistor input
- Physical Data & Масса
Вес нетто: 7.9кг
Монтаж: Vertical wall-mounted; Класс защиты IP20 (for cabinet internal installation)
Степень загрязнения 3, соответствует МЭК 60947-4-2
III. Standard Built-In Core Functions (Exclusive to High-End 3RW44 Series)
- Integrated Bypass Contactor
Automatically short-circuits thyristors after motor startup to drastically reduce heat generation, enabling long-duration continuous operation without external bypass equipment.
- Multi-Stage Start/Stop Modes
Dual voltage ramp soft start (initial voltage and ramp-up time independently adjustable)
Пуск с ограничением тока (suppresses inrush current, ideal for sites with limited grid capacity)
Adjustable soft stop; DC braking function (eliminates water hammer during inertial shutdown of fans and water pumps)
- Stepwise Overload Protection
Supports Class 10/10A/20/30 trip curves:
Сорт 10: Стандартные вентиляторы, водяные насосы
Сорт 20: Тяжелые конвейеры, миксеры
Сорт 30: Extra-heavy-duty crushers, шаровые мельницы, воздушные компрессоры
- Motor PTC Thermistor Protection
Directly connects to embedded motor temperature sensors; immediate shutdown upon overtemperature to cover blind spots of current-only protection.
- Inside-Delta Connection Support
The soft starter is installed between star-delta motor terminals, capable of driving motors with nearly double power under the same frame size, greatly reducing cabinet footprint and procurement costs.
- Comprehensive Fault Diagnostics: Phase loss, thyristor short circuit, перегрев, перегрузка двигателя, PTC overtemperature, start timeout; passive relay fault output.
- Load Selection Limits (Startup Frequency Restrictions, 40°С)
| Класс поездки | Max Starts Per Hour | Permitted Continuous Start Duration | Applicable Loads |
| Сорт 10 (Стандартный) | 12 times/h | ≤10s | Водяные насосы, centrifugal fans, general conveyors |
| Сорт 20 (Heavy-Duty) | 6 times/h | ≤20s | Миксеры, винтовые конвейеры, компрессоры |
| Сорт 30 (Extra-Heavy-Duty) | 3 times/h | ≤30s | Crushers, шаровые мельницы, heavy-duty centrifuges |
- Типичные сценарии применения
- Водоснабжение & Дренаж: High-power centrifugal pumps, circulating water pumps (soft braking eliminates water hammer)
- ОВК: Large centrifugal fans, вытяжные вентиляторы
- Горное дело & Строительные материалы: Ball mills, дробилки, heavy-duty belt conveyors
- Air Compressor Stations: Screw/piston air compressors, чиллеры
- Химическая промышленность: Heavy-duty motors for mixing and extruders
- Информация о поэтапном отказе & Direct Replacement Model
- Product Status: The entire 3RW44 series is gradually phased out; Siemens’ new upgraded generation is the 3RW55 series
- Perfect drop-in replacement with identical specifications: 3RW5535-6HA14
Identical AC230V control supply, винтовые клеммы, integrated bypass, 134Номинальный ток
Full functional coverage of 3RW44 plus optional communication interfaces (Modbus/Profinet), more compact dimensions and optimized heat dissipation
- Примечания по замене: Control terminal definitions are largely compatible; ramp and current limit parameters can be reused directly. Cabinet mounting cutouts match, requiring no modification to internal copper busbars.
VII. Operation Prohibitions & Ключевые моменты установки
- Derating is mandatory for ambient temperatures above 40°C; только 75% rated current is allowed at 60°C. Derating is also required for altitudes above 1000m.
- Upside-down vertical or horizontal flat mounting is forbidden; upper and lower heat dissipation air ducts must remain unobstructed.
- A cabinet cooling fan is recommended for Class 30 heavy-duty operation to avoid overheating faults.
- Inside-delta connection requires 6-wire motors and cannot be used with standard 3-wire motors.
- Torque for tightening main circuit copper busbar bolts must strictly follow the manual to prevent terminal burnout from overheating.
- The AC230V control supply must not be mistakenly connected to 380V, otherwise the control board will burn out instantly.
VIII. Differentiation of Derivative Models with Identical Frame Size (Only Suffix/Terminal Differences)
| Model No. | Тип терминала | Control Supply | Описание различий |
| 3RW4435-6BC45 | Screw control terminals | 230 В переменного тока | Mainstream in-stock model (this unit) |
| 3RW4435-2BC45 | Spring cage control terminals | 230 В переменного тока | Preferred for mass cabinet wiring factories |
| 3RW4435-6BC44 | Винтовые клеммы | 110 В переменного тока | Matched with imported equipment |
| 3RW4435-6BC46 | Винтовые клеммы | 24 В переменного/постоянного тока | For PLC DC control systems |
Classification of Complete Control Modes for Siemens 3RW4435-6BC45 Soft Starter
Three major external control methods are available: Local HMI panel control, hardwired digital terminal control, and fieldbus remote control. Тем временем, 6 built-in motor start-stop process control modes are integrated, explained separately below.
- External Command Control Modes (Send Start/Reset/Mode Switch Commands)
- Local Control via Onboard Panel (On-Site Operation)
The front panel is equipped with an LCD screen and 4 function keys for direct on-site operation without external wiring:
Функции: Local start, local stop, fault reset, parameter modification, switching between 3 motor parameter sets, real-time monitoring of operating current and fault codes
Приложения: On-cabinet commissioning, manual single-machine startup/shutdown, maintenance mode
Access Permission: Local/remote switch can be configured via terminals or bus communication; panel and remote control are interlocked, with only one control source active at a time.
- Hardwired Digital Input Terminal Control (Самый распространенный, for PLC/Button Relays)
Secondary control terminals: Л+ (24VDC common positive), 4 programmable digital inputs IN1/IN2/IN3/IN4 with screw terminals (standard for model 6BC45) for freely assignable functions:
Factory Default Terminal Assignment
IN1: Forward start (Parameter Set 1)
IN2: Reverse start (Parameter Set 1)
IN3: Low-speed mode
IN4: Fault reset
Customizable Terminal Functions (Configurable as Required)
Local manual mode, emergency start, quick stop, switching of 3 independent motor parameter sets, аварийная остановка, interlock reset triggered by external faults, и т. д..
Typical Wiring Scenarios
- Cabinet-mounted start/stop pushbuttons: IN1 connected to normally-open start contact, IN4 connected to reset contact
- PLC digital output control: PLC DO channels drive IN1/IN2 for startup and shutdown
- Multi-motor switching: IN1~IN4 toggle 3 distinct motor startup curves
- On-site emergency stop and interlocked shutdown via external thermal relays
- PROFIBUS-DP Fieldbus Remote Control (Optional Communication Module Required)
A PROFIBUS communication card can be fitted to the 3RW44 series for remote control via Siemens PLCs (S7-200 SMART/1200/1500/300/400):
- Remote Commands: Начинать, останавливаться, reset and parameter set switching transmitted via bus
- Data Exchange: Real-time upload of operating current, equipment status, fault codes and load percentage
- Process Adaptation: Centralized upper computer monitoring of multiple soft starters, DCS system interlocking, unattended pump houses and fan rooms
- Priority Setting: Permission switching between bus control and local terminals/panel; remote control automatically takes priority.
> Дополнительное примечание: The 3RW44 series has no native Profinet interface; the upgraded replacement 3RW55 series supports Profinet. Only DP communication is optional for the 3RW44 series.
- Built-In Motor Start-Stop Process Control Modes (Motor Voltage Regulation Algorithms, Core Operation Logic)
Selectable via panel, terminals or bus communication to match diverse loads including pumps, фанаты, crushers and conveyors; 4 standard start modes plus 3 stop modes are integrated:
(1) Four Soft Start Control Modes
- Voltage Ramp Start (Standard Mode for Fans & Насосы)
Linear voltage rise from a preset initial voltage to rated voltage for smooth torque build-up without current spikes; ramp time adjustable from 0.1 к 60 секунды.
- Current-Limited Start (For Sites with Insufficient Grid Capacity)
Maximum inrush startup current is capped (adjustable between 150%~600% Ie) во избежание перегрузки сети, suitable for simultaneous startup of multiple motors or undersized transformers.
- Kick Voltage Start (High Static Friction Loads: Screw Conveyors, Crushers, Ball Mills)
Short-duration high voltage output at startup instantaneously breaks static friction, then switches to ramp current limiting to prevent failed startup due to locked rotor.
- Dual-Ramp Start (Heavy-Duty Air Compressors, Centrifuges)
Two-stage voltage rise curve: slow ramp at low speed followed by fast ramp at high speed, balancing low inrush and fast acceleration.
(2) Three Stop Control Modes
- Soft Stop (Voltage Ramp Stop, Standard for Pumps to Prevent Water Hammer)
Voltage decreases gradually for smooth motor deceleration, eliminating pipeline water hammer and inertial fan impact; stop time adjustable from 0.1 к 60 секунды.
- DC Braking Stop (Фанаты & High-Inertia Loads)
DC current injected into stator after cutting off 3-phase AC supply for rapid braking to shorten coasting time; DC braking is disabled for inside-delta connection.
- Coasting Stop
Thyristor output cut off directly; motor freewheels to rest by inertia, applicable to general conveyors with no shock control requirements.
III. Auxiliary Supporting Control Functions
- 3 Independent Motor Parameter Set Switching Control
IN1~IN4 terminals or fieldbus switch 3 complete sets of motor parameters (номинальный ток, ramp time, current limit value, класс поездки), enabling one soft starter to serve alternating motors of different power ratings.
- PTC Motor Thermistor Temperature Control
Embedded motor temperature sensors connected to terminals T1/T2 trigger automatic shutdown on overtemperature, forming closed-loop temperature protection.
- Stepwise Overload Protection Control
Four trip curves Class10/10A/20/30 with software closed-loop current monitoring for automatic tripping under overload conditions.
- Automatic Bypass Control (Model Equipped with BC Integrated Bypass Contactor)
Bypass contactor closes automatically once startup completes and rated speed is reached to deactivate thyristors; the bypass opens automatically upon fault or stop command.
- Сравнение & Selection Guide for the Three External Control Methods
| Метод управления | Применимые сценарии | Преимущества | Ограничения |
| Onboard Local Panel | On-site commissioning, manual single-unit local operation | No wiring required, intuitive operation | Incapable of remote automatic interlocking |
| Hardwired Digital Terminals | PLC control cabinets, pushbutton on-site startup/shutdown | Бюджетный, быстрый ответ, stable with no communication interference | Heavy cabling required for centralized monitoring of multiple devices |
| PROFIBUS-DP Communication | Centralized upper computer/DCS control of multiple soft starters | Single cable transmits startup/stop signals and real-time data; remote parameter modification available | Extra communication module purchase required; complex wiring and commissioning |
Supplementary Model-Specific Explanations (3RW4435-6BC45)
- BC stands for full 3-phase controlled thyristors with independent 3-phase voltage regulation, delivering superior torque balance compared to 2-phase BB variants.
- Control supply AC230V; terminal L+ outputs 24VDC to directly drive passive on-site pushbuttons without auxiliary power supplies.
- Three passive relay feedback outputs (Бег, Bypass Closed, General Fault) available for connection to indicator lamps and alarm circuits.
Six Official Standard Start-Stop Process Modes for Siemens 3RW4435-6BC45 (Combination of 4 Start Modes + 2 Main Stop Logic Types; 6 Complete Process Combinations Defined in Official Manual)
- Four Standard Start Control Modes (Core Voltage Regulation Algorithms)
- Voltage Ramp Start (Factory Default)
Basic linear voltage ramp logic with uniform rise from preset initial voltage to rated voltage without harsh current surges; ramp time adjustable 0.1~60s.
Приложения: Centrifugal pumps, standard centrifugal fans, light-duty conveyors; sites with sufficient grid capacity and no kick start demand.
Optional auxiliary Kick Start Pulse: Short-duration output of approx. 80% rated voltage prior to startup to overcome static friction for lightly seized loads.
- Voltage Ramp + Current Limiting Start
Maximum startup current locked throughout the entire voltage ramp phase (adjustable 150%~600% Ie) to balance smooth acceleration and grid protection.
Приложения: Undersized transformers, simultaneous multi-motor startup, factory sites sensitive to grid voltage drop.
- Torque Ramp Start
Linear regulation of motor output torque (instead of pure voltage adjustment) for smooth torque curves, minimal startup jitter and precise torque control.
Приложения: Precision conveyors, центрифуги, mixing equipment, loads with strict anti-vibration startup requirements.
- Torque Ramp + Current Limiting Start
Closed-loop torque control paired with full-range dual current limitation to prevent locked rotor and suppress inrush current under heavy-duty operation.
Приложения: Class20/30 extra-heavy-duty equipment including ball mills, дробилки, heavy screw conveyors and air compressors.
Two Supplementary Special Start Modes (Independent Menu Selections, Not Used for Standard Processes)
1) Прямой онлайн (DOL) Full-Voltage Start: Thyristors fully conductive to replicate direct contactor startup, only for maintenance testing.
2) Motor Heating Mode: Continuous low-frequency low-voltage micro-current output for anti-freezing and moisture prevention of idle motors in cold winter; no load startup capability.
- Matching Stop Control Modes (3 Stop Algorithms, Freely Combinable with Any of the 4 Start Modes to Form 6 Complete Start-Stop Processes)
Stop Mode Classification
- Coasting Stop
Thyristor output cut off; motor freewheels to rest by inertia with zero braking torque.
Matching Loads: General belt conveyors with no shock mitigation requirements.
- Torque Soft Stop / Pump Stop
Gradually declining voltage/torque output after stop command for slow deceleration; pump stop mode features optimized dedicated curves exclusively designed to eliminate pipeline water hammer.
Matching Loads: Water supply & drainage pumps, большие поклонники, prevents water hammer and material spillage.
- DC Braking Stop / Combined Braking
3-phase AC supply disconnected; DC current injected into stator windings to generate braking magnetic field for fast halting of high-inertia loads; DC braking is unavailable for inside-delta connection.
Matching Loads: Exhaust fans, large centrifugal units to shorten coasting duration.
III. Six Complete Start-Stop Process Combinations Defined in Official Manual (Industry-Wide Term: Six Start-Stop Process Modes)
- Voltage Ramp Start + Coasting Stop
Universal standard process for light-duty fans and general conveying equipment.
- Voltage Ramp Start + Pump Soft Stop
Standard factory preset process for centrifugal water pumps to eliminate water hammer.
- Voltage Ramp + Current-Limited Start + Coasting Stop
For medium/small fans and pumps installed at sites with insufficient grid capacity.
- Torque Ramp Start + Torque Soft Stop
Low-vibration start and stop for precision conveyors, mixing equipment and centrifuges.
- Torque Ramp + Current-Limited Start + Coasting Stop
For heavy-duty crushers, ball mills and screw air compressors.
- Torque Ramp Start + DC Braking Stop
Fast braking process for high-inertia exhaust fans and centrifugal units.
- Adjustable Key Parameters for Each Mode
- Voltage Ramp: Initial voltage, ramp-up time, kick start voltage/kick duration
- Current Limiting Mode: Maximum startup current percentage
- Torque Control Mode: Initial startup torque, final torque, acceleration duration
- Soft Stop: Deceleration time, minimum stop torque
- DC Braking: Braking current, braking duration
- Key Operation Restrictions
- DC braking only supports standard 3-wire external motor connection and cannot be activated for 6-wire inside-delta motor wiring.
- Kick start pulse cannot be enabled for extended periods; limited to 0~1s short output to avoid grid impact.
- Torque ramp + current-limited start is the preferred selection for Class30 extra-heavy-duty loads to reduce locked rotor fault probability.