Passive Insertion/Immersion Water Temperature Sensor of Symaro Series
Core element: Pt1000 (Class B per IEC751). Designed for siemes HVAC and Building Management Systems (БМС) to measure liquid temperature in pipelines and water tanks. It does not come with an integrated thermowell and must be installed with a separate thermowell.
Полный код заказа: BPZ:QAE2112.010
- Основные технические характеристики
| Параметр | Спецификация |
| Sensing Element | Pt1000 (Passive Resistance Signal) |
| Диапазон измерения | -30℃ ~ +130℃ |
| Measuring Accuracy | ±0.95K within -30℃ to 130℃ |
| Immersion Probe Length | 100мм (Stainless Steel Shaft) |
| Time Constant | 8s without thermowell; 30s with thermowell |
| Класс защиты | IP42 for sensor body; IP54 after tightening M16 cable gland |
| Электрическое соединение | Винтовой клеммный блок, 2-проводная система |
| Кабельный ввод | M16×1.5 cable gland |
| Housing Dimensions | W80 × H60 × D31 mm |
| Nominal Pressure Rating | PN3 (Must be used with G½ thermowell; Max operating pressure PN10) |
| Материалы | Probe shaft: Нержавеющая сталь; Жилье: Heat-resistant plastic |
III. Пояснение кода модели
QAE2112.010
QAE: Series of immersion/insertion temperature sensors
21: Symaro general-purpose water temperature measurement
1: No integrated threaded thermowell; external thermowell fixed by clips
2: Pt1000 sensing element
010: Immersion length 100mm
Comparison of derivative models in the same series:
- QAE2112.015: Pt1000, 150mm immersion length
- QAE2111.010: Пт100, 100mm immersion length
- QAE2120.010: Built-in G½ threaded thermowell, LG-Ni1000
- Типичные сценарии применения
- Supply/return water temperature monitoring for heating systems & temperature control of mixing valves
- Temperature collection for chilled and hot water pipelines in central air conditioning
- Water temperature measurement for domestic hot water tanks and boilers
- Over-temperature protection for underfloor heating, heat exchange stations and fan coil units
- Matching Siemens DDC controllers (PXC, RWG series, и т. д.) for building BMS systems
- Key Installation Specifications
- Thermowell Mandatory: Original ALT-SS100 stainless steel G½ thermowell is recommended. Weld G½ threaded seats on pipelines in advance. A minimum probe insertion depth of 60mm is required to guarantee measuring accuracy.
- Монтажное положение: Install 1.5~2m downstream of pump outlets or mixing valves with the probe facing the incoming water flow. The cable terminal side must not face upward to prevent water ingress.
- Response Optimization: Apply thermal grease between thermowell and probe to reduce thermal resistance.
- Электропроводка: Direct 2-wire connection to Pt1000 input terminals of DDC controllers (неполяризованный). Shielded twisted pair cable is recommended to minimize interference.
- Электропроводка & Совместимость
Выход: Pure passive resistance signal. Only compatible with controllers supporting Pt1000 input.
Compatible Siemens Controllers: RWG16, PXC series, Climatix controllers
Not Directly Replaceable: Pt100 models (QAE2111), 4-20mA active transmitters (QAE2174)
VII. List of Matching Accessories (Separate Purchase Required)
- ALT-SS100: G½ stainless steel protection thermowell (Standard fit for 100mm probes)
- Thermal grease: Improves temperature measurement response speed
- M16 sealing cable gland (Upgrades protection class to IP54)
VIII. Руководство по устранению неполадок
| Симптом неисправности | Common Causes | Решения |
| Constant / Infinite temperature reading | Обрыв провода датчика, незакрепленные клеммы | Disassemble housing, fasten screws and measure resistance at both ends of probe shaft |
| Severe measurement deviation & медленный ответ | Missing thermowell, no thermal grease, insufficient insertion depth | Install thermowell, apply thermal grease and ensure ≥60mm immersion depth |
| Drifting & fluctuating readings | Unshielded long cables, damp wiring terminals | Replace with shielded cables and tighten cable glands for waterproofing |
Complete Technical Datasheet of SIEMENS QAE2112.010 Immersion Temperature Sensor
- Basic Model Information
Material Model No.: QAE2112.010
Серия продуктов: Symaro QAE21 Passive Insertion / Immersion Temperature Sensor
Тип продукта: Liquid temperature probe for water pipelines and tanks (No integrated thermowell; separate protection thermowell required for installation)
Код заказа: BPZ:QAE2112.010
Segment-by-Segment Model Definition
| Сегмент | Определение |
| QAE | Series of immersion liquid temperature sensors |
| 21 | Sub-series of general passive HVAC temperature probes |
| 12 | Sensing element Pt1000 (11=Pt100, 12=Pt1000) |
| 0.01 | Effective immersion length of probe: 100 мм |
- Core Sensing & Accuracy Parameters
- Temperature Sensing Core
Element: Pt1000, compliant with Class B accuracy per IEC 60751
Диапазон измерения: -30 ℃ ~ +130 ℃
Measuring Error: ±0.95 K (Полный спектр)
- Response Time Constant
Without protection thermowell: τ₀.₅ ≈ 8 с
With standard stainless steel thermowell: τ₀.₅ ≈ 30 с
- Passive Signal Characteristics
Pure resistive passive output with no external power supply required. Directly connect to resistance thermometer input modules of Siemens DDCs, thermostats and PLCs.
III. Механическая структура & Размеры
- Probe Specifications
Effective immersion length: 100 мм
Shaft Material: Нержавеющая сталь
Nominal pressure of matched thermowell: PN3 (Max pressure 3 бар)
- Wiring Housing
Housing Size: 80×60×31 mm (L×W×H)
Cable Outlet: M16 cable gland
Способ подключения: Screw-clamp terminals for 0.5~1.5 mm² cables
Класс защиты: IP42; IP54 with sealing cable gland accessory
- Operating Ambient Conditions
Allowable ambient temperature for housing: -40 ℃ ~ +70 ℃
Compatible Media: Cold water, hot water, glycol HVAC circulating water, domestic hot water
- Mandatory Installation Accessories (Optional Purchase)
This model does not include G1/2 threaded protection thermowell. Thermowell assemblies must be ordered separately:
- Standard protection thermowell: ASZ-100 (G1/2 external thread, fits 100mm probes, PN10 pressure rating)
- Locking clip: Secures probe to thermowell to prevent loosening or detachment
- Cable: 3-экранированный кабель с жилой (Standard 3-wire wiring for Pt1000)
- Electrical Wiring Rules (3-Wire System)
3-wire Pt1000 connection eliminates measurement error caused by cable resistance:
Терминал 1: One end of resistance element
Терминалы 2 & 3: Two parallel wires from the other resistance end to the controller
Compatible Siemens Controllers: RWD62/RWD68, Synco700, Desigo PXC series, Building DDC
- Same-Series Model Differentiation & Варианты замены
Comparison of Similar Models in Series
| Модель | Sensing Core | Immersion Length | Thermowell Configuration |
| QAE2111.010 | Пт100 | 100мм | Probe only, no thermowell |
| QAE2112.010 | Pt1000 | 100мм | Probe only, no thermowell (Эта модель) |
| QAE2112.015 | Pt1000 | 150мм | Probe only, no thermowell |
| QAE2120.010 | LG-Ni1000 | 100мм | Integrated G1/2 thermowell PN10 |
Решения для прямой замены
- Extended Pt1000 version with identical specs: QAE2112.015 (150mm immersion length for thick pipeline walls)
- Integrated pre-assembled version without separate thermowell: QAE2120.010 (Nickel resistance; controller must support Ni1000 signal)
- Cost-effective Pt100 variant: QAE2111.010 (Only applicable if controller supports Pt100 input)
VII. Типичные сценарии применения
ОВК & Building Management BMS Systems:
- Supply/return water temperature monitoring for chillers
- Hot water measurement for boilers and plate heat exchangers
- Over-temperature protection for underfloor heating and fan coil units
- Constant temperature control for domestic hot water tanks and pipelines
- Temperature collection for industrial process cooling water
VIII. Strict Installation Prohibitions
- Never immerse the bare probe directly into pipeline fluid without thermowell — risk of corrosion and non-detachable replacement.
- Medium pressure shall never exceed PN3. Select QAE2120 series with PN10 integrated thermowell for high-pressure pipelines.
- At least 90% of the probe shaft must be fully submerged in fluid; incomplete immersion leads to severe temperature deviation.
- Do not route sensor cables in the same trunking as power cables. Single-end earthing of shielding layer reduces electromagnetic interference.
- Medium temperature shall not exceed 130℃ even temporarily. High-temperature applications require high-temperature resistant thermowells.
- Consumable Matching Spare Parts
- ASZ-100 Stainless Steel Temperature Thermowell G1/2
- M16 Sealing Cable Gland (Upgrade to IP54 protection)
- PTFE sealing tape for thermowells, high-temperature gaskets
Shaft Material of SIEMENS QAE2112.010
Probe (Immersion Shaft) Материал: Нержавеющая сталь
Дополнительные примечания
- All QAE21xx series sensors (QAE2111, QAE2112, QAE2120, и т. д.) adopt uniform stainless steel immersion shafts, resistant to corrosion from HVAC cold/hot water and glycol circulating water, suitable for medium temperatures ranging from -30℃ to +130℃.
- Distinction between two components:
Original thin probe shaft of sensor: Нержавеющая сталь (Factory-fitted, 100mm length)
External optional protection thermowell ASZ-100: Also stainless steel with G1/2 thread and PN10 pressure rating. Mandatory for pipeline installation; never submerge bare shaft directly in pipeline fluid.
- Материал корпуса: ASA engineering plastic (Off-white housing), IP42 protection class.
Application Scenarios of SIEMENS QAE2112.010 (Pt1000 Immersion Water Temperature Sensor)
- HVAC Heating Systems (Most Common Use Cases)
- Temperature Measurement at Boiler / Heat Source Side
Collect supply and return water temperature of gas/oil hot water boilers to interlock boiler start/stop, proportional regulation and over-temperature protection.
- Plate Heat Exchange Stations
Monitor supply & return water of primary municipal heating network and secondary heating loop for automatic temperature control, constant temperature & pressure regulation of heat exchange units.
- Underfloor Radiant Heating
Collect supply/return water temperature of manifold assemblies to interlock mixing centers, prevent floor overheating and stabilize supply water temperature.
- Radiator Heating Systems
Water temperature monitoring for building risers and branch pipes to support zoned or household independent temperature regulation.
- Central Air Conditioning Water Systems
- Chilled Water System of Chillers
Acquire chilled supply and return water temperature to calculate temperature difference, control chiller loading/unloading and variable frequency pump speed adjustment.
- Cooling Water Systems
Measure cooling supply & return water temperature to interlock cooling tower fan start/stop and variable frequency regulation for unit energy saving.
- Fan Coil Units / Air Handling Units
Temperature measurement of chilled/hot water pipelines for air conditioning, cooperating with 2-way & 3-way motorized valves to realize room constant temperature control.
- Air Handling Units (AHU)
Monitor inlet & outlet water temperature of heating and cooling coils, automatically adjust valve opening to stabilize supply air temperature.
III. Domestic Hot Water & Swimming Pool Systems
- Domestic Hot Water Tanks / Storage Water Heaters
Immersed temperature measurement inside tanks and hot water circulation pipelines to control circulation pump and heating equipment operation for all-day constant hot water supply.
- Hot Water Pipe Networks for Hotels & Apartments
Temperature monitoring of main and branch hot water pipes to reduce heat loss and balance hot water temperature across floors.
- Constant-Temperature Swimming Pool Systems
Measure pipeline temperature of pool heat exchangers to maintain steady pool water temperature and interlock plate heat exchangers for heating.
- Industrial Process Water Systems
- Process Cooling Water for Workshops
Temperature monitoring of cooling circuits matched with injection molding machines, machine tools and air compressors, triggering over-temperature alarms and equipment interlock shutdown.
- Purified Water / Process Hot Water in Cleanrooms
Temperature measurement of cleanroom HVAC hot water and process circulating water to meet constant-temperature process requirements of pharmaceutical and electronic workshops.
- Waste Heat Recovery Systems
Temperature detection for waste heat recovery tanks and circulation pipelines to automatically switch recovery/heating modes for energy-efficient operation.
- БМС & Energy Metering Applications
- Building Energy Consumption Monitoring
Collect temperature difference between supply and return pipes of cooling/heating networks. Calculate cooling & heat energy consumption with flow meters for itemized energy statistics.
- Support for Building DDC Automation Systems
Fully compatible with Siemens PXC, RWG and Climatix series controllers as standard water temperature measuring points.
- Intelligent Pump Room Monitoring
Поставлять & return water temperature measurement of primary and secondary pumps for pump variable frequency optimization and pipeline anti-freeze alarming.
- Auxiliary Temperature Control & Protection for Supporting Equipment
- Solar Hot Water Systems
Measure outlet temperature of solar collectors and storage tanks to control circulation pump operation and realize solar temperature-difference circulation.
- Anti-Freezing Monitoring
Detect temperature of buried outdoor heating pipelines and roof chilled water main pipes; automatically activate heat tracing and circulation pumps when temperature drops below setpoint for freeze protection.
- Temperature Sensing for Constant-Temperature Mixing Valves
Collect mixed outlet water temperature for closed-loop regulation of cold/hot water inlet ratio to stabilize outlet temperature and prevent scalding.
Restricted & Inapplicable Scenarios
- Steam pipelines and high-temperature flue gas (Max measuring range 130℃, not suitable for steam service)
- Direct insertion into high-pressure liquid without thermowell (G1/2 thermowell is mandatory)
- Liquids with strong acid/alkali corrosion (Standard stainless steel shaft requires anti-corrosion thermowell replacement)
- Air duct temperature measurement (Use QAM series duct temperature sensors instead; cross-use prohibited)
Контактор,автоматический выключатель,солнечный инвертор,электрический счетчик,солнечные батареи




















NH42-63-318x560.png)