​CHINT NXM250S/3200 – 200A molded case circuit breaker

NXM

Series code for CHINT molded case circuit breakers

250

Frame rated current (Inm)

Breaking capacity grade

"ส" represents the standard breaking type (the breaking capacity is usually 35kA; refer to the product manual for specific values). นอกจากนี้, there are grades such as "H" (high breaking capacity) และ "ล" (low breaking capacity). The higher the breaking capacity, the better it can safely cut off the fault large current.

  • รายละเอียดสินค้า

CHINT NXM250S/3200 200Ais the complete model number of a เบรกเกอร์กรณีแม่พิมพ์ (เอ็มซีซีบี) under the CHINT brand. It is mainly used for circuit protection in lowvoltage power distribution systems.

  1. Indepth Analysis of Model Parameters

Each character/number corresponds to the key specifications of the circuit breaker, with specific meanings as follows:

Model SegmentMeaning ExplanationCore Function
NXMSeries code for CHINT molded case circuit breakersIdentifies the product category. The NXM series is a mainstream lowvoltage power distribution protection product of CHINT, featuring high breaking capacity and stable performance.
250Frame rated current (Inm)Indicates that the maximum rated current the circuit breaker shell can withstand is 250A. It means that under thisshell model”, releases with different rated currents (เช่น, 160ก, 200ก, 250ก) can be adapted.
Breaking capacity grade“ส” represents the standard breaking type (the breaking capacity is usually 35kA; refer to the product manual for specific values). นอกจากนี้, there are grades such asH” (high breaking capacity) และ “ล” (low breaking capacity). The higher the breaking capacity, the better it can safely cut off the fault large current.
3200หมายเลขขั้วโลก + Release type The first digit “3”: 3 เสา (suitable for threephase circuits, such as industrial motors and threephase power distribution);
The second digit “2”: thermalmagnetic release (the most commonly used type, which realizes overload protection through athermal bimetal sheetand shortcircuit protection through anelectromagnetic coil”);
The last two digits “00”: No accessories (เช่น, no leakage protection, no auxiliary contacts, ฯลฯ. If it is “01”, it is equipped with auxiliary contacts; if it is “30”, it is equipped with leakage protection).
200กRelease rated current (In)It is the core protection parameter of the circuit breaker, referring to the maximum continuous current allowed when the circuit is working normally. When the circuit current exceeds 200A for a long time (โอเวอร์โหลด), the release will trip with a delay; if the current far exceeds 200A instantaneously (ไฟฟ้าลัดวงจร), it will trip instantly to cut off the circuit.
  1. Core Functions and Protection Characteristics

As asafety guardianof lowvoltage power distribution, its core role is to prevent the expansion of circuit faults. The specific protection functions include:

  1. การป้องกันการโอเวอร์โหลด

When the circuit current continuously exceeds 200A due to excessive load (เช่น, motor stalling, simultaneous startup of multiple devices), thethermal bimetal sheetin the release will deform due to heat, pushing the mechanism to trip with delayed action (to avoid false tripping caused by shortterm overload), thereby protecting wires and equipment from damage due to overheating.

  1. ShortCircuit Protection

When a short circuit occurs in the circuit (เช่น, direct contact between live wires, neutral wires/phase wires), and the current surges to hundreds or even thousands of amperes instantaneously, theelectromagnetic coilin the release will generate a strong magnetic field, which attracts the iron core to push the trip instantaneously. The circuit is cut off within 0.1 วินาที, preventing equipment burnout, fire or electric shock accidents.

  1. Power Distribution Control

In addition to the protection function, it can also be used as aswitchfor normal circuits. Manual closing/opening can realize the onoff control of threephase equipment (เช่น, motors, กล่องกระจายสินค้า).

III. สถานการณ์การใช้งาน

Based on its characteristics of 3 เสา, 200A rated current and standard breaking capacity, it is mainly used in lowvoltage threephase power distribution systems. Typical scenarios include:

Industrial workshops: Used as the main protection switch for threephase motors (เช่น, 2030kW motors) and large machine tools;

Commercial buildings: Used as the main protection or branch protection for threephase power cabinets (เช่น, outdoor air conditioner units, elevator power supplies) in shopping malls and office buildings;

Civil power distribution: Used as the threephase incoming main switch for highrise residential buildings and villas (if the incoming power supply is threephase), or as the protection switch for threephase central air conditioners and energy storage equipment;

Outdoor power distribution: Used for the lowvoltage side protection of street lamp control boxes and small distribution transformers (below 100kVA).

  1. Usage Precautions
  2. Matching Circuit Parameters: Ensure that the rated voltage (usually AC 380V) and load current of the circuit do not exceed the specifications of the circuit breaker. Avoid the situation ofa small horse pulling a big cart” (เช่น, using a 200A circuit breaker to protect a 300A load), which may lead to protection failure;
  3. Adaptation of Breaking Capacity: If the shortcircuit current of the power distribution system is large (เช่น, near the transformer), it is necessary to confirm whether the “35kA breaking capacitymeets the onsite requirements. If not, select theHhighbreaking type;
  4. การตรวจสอบเป็นประจำ: During operation, regularly check whether the circuit breaker has heat generation or abnormal noise. หลังจากสะดุด, it is necessary to troubleshoot the fault (เช่น, ไฟฟ้าลัดวงจร, โอเวอร์โหลด) and do not close the switch blindly;
  5. Professional Installation: It must be installed by certified electricians to ensure firm wiring (loose wiring is prone to heat generation and burnout). นอกจากนี้, the 3pole wiring corresponds to the A, B, and C three phases, and must not be connected incorrectly.