Model Explanation
| Model Part | Description |
| XMLE | CHINT Kunlun Series Residual Current Operated เบรกเกอร์ (MCCB with earth leakage protection) |
| 630 | Frame rating current 630A |
| ส | Breaking capacity class S (25kA at AC400V/415V, ultimate breaking capacity 50kA) |
| 4300ก | 4ป (three-phase four-wire, 3พี+เอ็น), thermal-magnetic trip unit, standard version without accessories |
| 630ก | Rated operational current 630A |
- พารามิเตอร์ที่สำคัญ
| Parameter Category | ค่า | หมายเหตุ |
| พารามิเตอร์พื้นฐาน | ||
| พิมพ์ | Moulded Case Circuit Breaker with Earth Leakage Protection (Residual Current Circuit Breaker) | Provides overload, short-circuit and earth leakage protection |
| Poles | 4ป (3พี+เอ็น) | Three phases + neutral |
| Trip type | Thermal-magnetic (เส้นโค้ง C) | For power distribution protection |
| Rated insulation voltage Ui | 800วีและ | |
| Rated operational voltage Ue | 400V/415V AC (4ป) | |
| Rated frequency | 50/60Hz | |
| Current Parameters | ||
| Frame current Inm | 630ก | |
| Rated current In | 630ก | |
| Residual operating current Iホ馬 | 100/200/300mA adjustable | Selectable per requirements |
| Residual current tripping time | 0.3ส (มาตรฐาน) | Fast personal safety protection |
| ทำลายความจุ | ||
| Rated service breaking capacity Ics | 25ที่ (AC400V) | คลาส S |
| Ultimate short-circuit breaking capacity Icu | 50ที่ (AC400V) | |
| Protection Functions | Long-time overload, short-time delay, instantaneous short-circuit, earth leakage protection | Full protection for circuits and equipment |
- Mounting Dimensions
| Mounting Type | ขนาด (W×H×D, มม) | หมายเหตุ |
| ที่ตายตัว (front/rear connection) | 280×280×100 | Standard 4P dimensions |
| Plug-in type | 280×280×120 | Including plug-in base |
| Mounting mode | ที่ตายตัว / Plug-in | |
| Connection type | Front / Rear connection | Rear connection requires special kit |
| Terminal size | M12 hex socket screw | For large cross-section cables |
- Applications
- Low-voltage distribution systems: Main or branch protection for three-phase four-wire circuits up to 630A
- Industrial equipment protection: Protect motors, transformers and other electrical devices against overload, short-circuit and earth leakage
- Building electrical: Main and sub-distribution boards in commercial buildings and industrial plants
- Personal safety: Indirect contact protection against fatal electric shock
- Electrical fire prevention: Protection against earth fault current induced electrical fires
- Operating Notes
- Ambient conditions:
อุณหภูมิแวดล้อม: -25℃ ~ 70℃
ระดับความสูง: ≤ 2000m (derate if exceeded)
ความชื้น: ≤ 95% (non-condensing)
Avoid flammable, explosive or highly corrosive environments
- Wiring requirements:
Strictly separate N line and phase lines; N line must pass through the leakage detection transformer
Terminals must be securely tightened to avoid overheating
Cable cross-section suitable for 630A (≥ 185mm² copper recommended)
- Selection matching:
Residual current: 300mA for general distribution, 30mA for personal protection (special model)
Breaking capacity must match system short-circuit current; Class S suitable for general industry
- Maintenance:
Test monthly using the test button
Regularly check terminals for overheating
Keep clean to ensure heat dissipation
- การแก้ไขปัญหา
| Symptom | สาเหตุที่เป็นไปได้ | โซลูชั่น |
| Trips immediately after closing | 1. Short circuit | 1. Locate short circuit |
| 2. Residual current too low | 2. Adjust to suitable Iホ馬 | |
| 3. Trip unit fault | 3. Replace trip unit | |
| Fails to trip on overload | 1. Thermal trip failure | 1. Replace thermal trip |
| 2. Over-current setting too high | 2. Reset current setting | |
| Fails to trip on earth leakage | 1. Leakage module fault | 1. Replace leakage module |
| 2. N line not through CT | 2. Rewire correctly | |
| 3. Test button fault | 3. Replace test button | |
| Excessive heating during operation | 1. Loose connections | 1. Tighten terminals |
| 2. Overload | 2. Reduce load | |
| 3. Poor ventilation | 3. Improve cooling |
- Brand Alternatives
| ยี่ห้อ | รูปแบบทางเลือก | ความเข้ากันได้ |
| ชไนเดอร์ | NSX630S TM630D 4P 3D (with Vigi module) | Same breaking capacity and rated current, similar dimensions |
| เอบีบี | Tmax T6H630 PR221DS-LSI R630 4P (with RC221) | Matching protection, separate leakage module required |
| ซีเมนส์ | 3VL630N630 4P (with 30mA leakage add-on) | Same frame and rated current, compatible mounting |
| อร่อย | CDM3L-630S/4300A-630A | Direct Chinese alternative, identical dimensions and parameters |
| Changshu Switch | CM3L-630S/4300A-630A | Matching technical data, compatible mounting |
- สรุป
CHINT NXMLE‑630S/4300A‑630A is a high-performance 4P earth leakage MCCB for 630A three‑phase four‑wire distribution systems. It provides overload, short‑circuit and earth leakage protection, with Class S breaking capacity suitable for general industrial applications. Its thermal‑magnetic trip (เส้นโค้ง C) is ideal for distribution, effectively protecting equipment and personnel. Correct selection of residual current and proper installation are essential; regular maintenance ensures long service life and reliable protection.
CHINT NXMLE-630S/4300A-630A Mounting Dimensions
- Overall Mounting Dimensions
Mounting dimensions vary slightly by installation type. Official standard values:
| Mounting Type | ขนาดโดยรวม (W×H×D, มม) | Panel Cutout (มม) | หมายเหตุ |
| ที่ตายตัว (front/rear) | 280×280×100 | 245×245 (bolt centers) | Standard 4P, front/rear fixed same |
| Plug-in | 280×280×120 | 245×245 (base centers) | Includes base depth |
| Rear connection (special) | 280×280×100 | 245×245 | Requires rear connection kit |
- Key Dimension Details
- Width (ว): 280mm – Standard 4P MCCB width, compatible with mainstream switchgear
- Height (H): 280mm – Including operating handle, consistent with Kunlun 630A frame
- Depth (ดี):
Fixed type: 100มม
Plug-in type: 120มม (body + base)
- Mounting bolts: M12 hex socket for high-current 630A application
- Mounting plate thickness: ≥ 6mm recommended for strength and cooling
- Minimum clearances: ≥25mm left/right, ≥50mm top/bottom for operation and ventilation
- Mounting Methods
- Fixed mounting: Most common, bolted directly to panel; front or rear connection
- Plug-in mounting: Uses dedicated base for fast replacement, suitable for frequent maintenance
- Rear connection: Terminals on rear side, saves front panel space and improves layout
- หมายเหตุการติดตั้ง
Install vertically or horizontally, tilt angle ≤ 15°
Correctly separate N and phase lines; N must pass through leakage transformer
Check and tighten all terminals after installation
Allow sufficient ventilation to prevent overheating