The DTV series is เดลต้า’s dedicated PID valve position controller for electric valves. Unlike conventional temperature controllers for heating/cooling loads, it is specially designed to drive modulating electric actuators with forward/reverse rotation. มิติข้อมูลแผง: 48×96มม (1/8 จาก).
คำจำกัดความของรหัสโมเดล
DTV: Delta Valve Controller series
4896: Panel size W48 × H96 mm
ค: เอาท์พุทรีเลย์ (C=Relay; R variant shares identical panel size with different contact rating/wiring)
Other models in this series include DTV9696C / DTV9696R (96×96 large panel)
คุณสมบัติที่สำคัญ
- Valve-specialized PID: Equipped with two relay outputs for valve opening / valve closing to directly drive forward/reverse rotation of electric actuators. Real-time valve opening percentage display on panel. A/M auto/manual one-touch switching; valve opening can be fixed manually in manual mode.
- Multi-input support
เทอร์โมคัปเปิ้ล: เค, เจ, ต, อี, เอ็น, ร, ส, บี, คุณ, ล, TXK
Platinum RTD: พอต100, JPt100
อนาล็อก: 4~~20mA, 0~~20mA, 0~~5V, 0~~10V
- เตือน: 2 groups of alarm outputs with 17 alarm modes (ขีดจำกัดสูง/ต่ำ, สัญญาณเตือนการเบี่ยงเบน, valve fault, ฯลฯ)
- การสื่อสาร: RS485 ในตัว, Modbus RTU/ASCII. Baud rate 2400~38400bps. Connectable to PLC and SCADA for PV/SV/valve opening and alarm status acquisition.
- แหล่งจ่ายไฟ: 100~240VAC 50/60Hz
- แสดง: ไฟ LED คู่; PV in red, SV in green; ℃/℉ switchable
- Sampling speed: 0.4s for thermocouple/RTD; 0.15s for analog input
การใช้งานทั่วไป
Industrial kilns, heat exchangers, เครื่องปรับอากาศ, textile dyeing, hot water systems, closed-loop temperature control for electric regulating valves, constant temperature water supply/heating and furnace temperature regulation.
Difference from standard DTC/DTA temperature controllers
Standard temperature controllers: SSR/current output for heating loads.
DTV: Dual relay outputs to control forward/reverse motor of electric actuators, with valve-position PID dedicated to modulating valve opening.
Wiring Summary
ออก1: Valve open relay
ออก2: Valve close relay
ALM1/ALM2: Alarm relays
อาร์เอส485: D+, D-, การสื่อสารแบบโมดบัส
Sensor input: เทอร์โมคัปเปิ้ล / พอต100 / สัญญาณอะนาล็อก
บันทึก: DTV outputs are dry relay contacts only. They cannot power the actuator directly. The electric actuator requires external AC220V power supply.
การแก้ไขปัญหาทั่วไป
- Valve no movement: Check ON/OFF operation of OUT1/OUT2 relays; actuator power supply and internal limit switches; improper PID P/I/D parameters.
- Temperature oscillation: Perform PID auto-tuning; reduce proportional band P and increase integral time.
- การสื่อสารล้มเหลว: Verify RS485 A/B wiring, station address, baud rate and parity.
- Abnormal PV reading: Sensor open circuit, mismatched input type, reversed wiring polarity.
ทางเลือกอื่น
ซีรีย์เดียวกัน: DTV4896R (same panel size, contact rating difference, check datasheet)
ทางเลือก: If analog output (4~20mA) for electric valve is required, DTV cannot be used directly. Select DTA/DTB with analog output.
Delta DTV4896C Modbus RTU Register Map (Hex native address from manual)
โปรโตคอล: Modbus RTU / ASCII, ทาส; Function codes: 03H Read Holding Registers, 06H Single Register Write, 01H Read Coils, 05H Force Single Coil
Unit definition: PV/SV = 0.1℃ / 0.1 scale; เช่น. 250 = 25.0℃; Valve opening unit = 0.1%
⚠️ PLC/HMI commonly uses 40001 ชดเชย: Physical address 1000H = HMI address 41001
Word Registers (03ชม / 06ชม)
| ที่อยู่(Hex) | ชื่อ | R/W | คำอธิบาย |
| 1000ชม | PV Process Value | ร | Real-time temperature; Fault codes: 8002H Data acquisition failure /8003H Sensor break /8004H Wrong input type /8006H ADC fault /8007H Memory fault |
| 1001ชม | SV Set Value | R/W | Temperature setpoint, 0.1 scale |
| 1002ชม | Range Upper Limit | ร | Max input range |
| 1003ชม | Range Lower Limit | ร | Min input range |
| 1004ชม | ประเภทเซนเซอร์ | R/W | 0=K,1=J,2=T,3=E,4=N,5=R,6=S,7=B,8=L,9=U, 10=TXK,11=JPt100,12=Pt100,13=0~5V, 14=0~10V,15=0~20mA,16=4~20mA |
| 1005ชม | โหมดควบคุม | R/W | 0=PID;1=ON/OFF;2=Manual;3=Program PID;4=Ramp control |
| 1006ชม | Heat/Cool | R/W | 0 เครื่องทำความร้อน, 1 ระบายความร้อน |
| 1009ชม | PB Proportional Band | R/W | 0.1~999.9 |
| 100อา | Ti Integral Time | R/W | 0~9999 |
| 100บีเอช | Td Derivative Time | R/W | 0~9999 |
| 100ช | Integral Initial Value | R/W | 0~1000 (0.1% หน่วย) |
| 100DH | Proportional Compensation | R/W | Active when Ti=0, 0~1000 (0.1%) |
| 1012ชม | Output Valve Opening | R/W | หน่วย 0.1%; Writable only in manual mode, read-only in auto mode |
| 1018ชม | Valve Full Close to Full Open Time | R/W | Valve stroke time, 0.1~999.9s; critical parameter for systems without valve position feedback |
| 1019ชม | Valve Dead Band | R/W | หน่วย 0.1%, suppress frequent valve chattering |
| 101อา | Valve Feedback Upper Limit | R/W | For AI valve feedback: 0~1024 |
| 101บีเอช | Valve Feedback Lower Limit | R/W | For AI valve feedback: 0~1024 |
| 101ช | PID Group Selection | R/W | 0~4; 4=Auto PID match |
| 101เอ๊ะ | Valve Output Upper Limit | R/W | 0.1% หน่วย, maximum opening limit |
| 101เอฟเอช | Valve Output Lower Limit | R/W | 0.1% หน่วย, minimum opening limit |
| 1020ชม | ALM1 Alarm Mode | R/W | 17 alarm modes |
| 1021ชม | ALM2 Alarm Mode | R/W | 17 alarm modes |
| 1024ชม | ALM1 Upper Threshold | R/W | เตือน 1 threshold |
| 1025ชม | ALM1 Lower Threshold | R/W | เตือน 1 threshold |
| 1026ชม | ALM2 Upper Threshold | R/W | เตือน 2 threshold |
| 1027ชม | ALM2 Lower Threshold | R/W | เตือน 2 threshold |
| 102อา | Panel Status Word | ร | Bit0:℉ Bit1:℃ Bit2:ALM2 Bit4:OUT1 Open Valve Bit5:OUT2 Close Valve Bit6:AT Auto-tuning Bit7:ALM1 |
| 102เอฟเอช | เวอร์ชั่นเฟิร์มแวร์ | ร | V1.00=0100H |
Bit Coils (01H Read / 05H Write Coil)
| ที่อยู่(Hex) | ชื่อ | R/W | คำอธิบาย |
| 0810ชม | Communication Write Enable | R/W | 0=Write disabled (ค่าเริ่มต้นจากโรงงาน), 1=Allow host PC parameter write |
| 0811ชม | Temperature Unit | R/W | 0=℉, 1=℃ |
| 0812ชม | Decimal Point | R/W | 0/1; Not valid for B/R/S thermocouple |
| 0813ชม | PID Auto-tuning AT | R/W | 0 หยุด, 1 Start AT |
| 0814ชม | Control Run/Stop | R/W | 0 หยุด, 1 วิ่ง |
| 0815ชม | Program Control End | R/W | 0 วิ่ง, 1 End |
| 0816ชม | Program Pause | R/W | 0 วิ่ง, 1 Pause |
| 0817ชม | Valve Position Feedback Enable | R/W | 0 No feedback, 1 AI valve feedback enabled |
| 0818ชม | Valve Feedback Auto-calibration | R/W | 0 หยุด, 1 Start stroke auto-calibration (for valves with feedback) |
Communication Basic Parameters (Set inside controller)
- Station address: 1~247
- อัตรารับส่งข้อมูล: 2400 / 4800 / 9600 /19200 /38400
- ความเท่าเทียมกัน: Fixed 8,N,1 (7E1/8O2 not supported)
- โปรโตคอล: Modbus RTU (ที่แนะนำ) / ASCII
Operation Examples (DVP PLC / เอชเอ็มไอ)
Read PV: รหัสฟังก์ชั่น 03, start address `1000H`, อ่าน 1 Word
Modify SV: รหัสฟังก์ชั่น 06, address `1001H`, write target value (เช่น. 250 = 25.0℃)
Write valve opening in manual mode: First set `1005H` =2 (Manual mode), then write `1012H`; เช่น. 500 = 50.0% เปิด
Start PID auto-tuning: 05H write `0813H`=ON
หมายเหตุสำคัญ
- Before host writing parameters, 0810H must be set to 1 (communication write enable) otherwise write commands will fail. Set back to 0 after commissioning to prevent accidental modification.
- DTV is a time-proportional valve position controller, NOT a 4~20mA analog output valve controller. Without valve feedback, valve opening is calculated based on【valve full-close to full-open time】.
- For HMI with 40001 ชดเชย: Physical address 1000H = decimal 4096 → HMI address 44097 (40001+4096)
Delta DTV4896C Fault Code List (PV register read via Modbus)
บันทึก: The DTV panel does not display hex fault codes directly. Fault codes are abnormal values read from PV register `1000H` by host system. Panel typically shows —- or EEE with ALM LED lit.
| รหัสข้อผิดพลาด(Hex) | คำอธิบาย | การแก้ไขปัญหา & การเยียวยา |
| 8002ชม | Measurement not available / Input read timeout | 1. Check loose or broken sensor wiring |
| 2. Inspect terminal oxidation or poor contact | ||
| 3. Confirm sensor type parameter matches field sensor | ||
| 4. Power cycle controller to eliminate transient interference | ||
| 8003ชม | Sensor break (ที่พบบ่อยที่สุด) | ✅Thermocouple: ตรวจสอบขั้ว, วงจรเปิด; |
| ✅Pt100: One wire of 3-wire circuit broken; | ||
| ✅4~20mA analog: Loop open, no current; | ||
| Test continuity, replace sensor or repair wiring | ||
| 8004ชม | Wrong input type configuration | 1. Verify【Sensor Type】parameter (1004ชม) matches actual sensor |
| ตัวอย่าง: K-type sensor cannot be set to Pt100; 4~20mA cannot be set as thermocouple | ||
| 2. อินพุตแบบอะนาล็อก: Internal jumper must be switched to current mode; wrong jumper will trigger 8004H | ||
| 8006ชม | ADC analog-to-digital hardware fault | 1. ปิดเครื่องเพื่อ 5 minutes then restart to clear transient error |
| 2. Disconnect sensor, if fault persists with empty input terminals → ADC hardware damage, replace DTV unit | ||
| 8007ชม | Memory fault (ข้อผิดพลาด EEPROM) | 1. Try factory reset and reload parameters |
| 2. วงจรไฟฟ้า; if fault remains: storage chip damaged, replace controller |
Local Panel Fault Indication (No Modbus required, visual check)
- PV display —-: Sensor open circuit, corresponds to 8003H
- PV display EEE: Input out of range, sensor short circuit or wrong input type (8004ชม)
- ALM LED ON but PV reading normal: Not input hardware fault. ALM1/ALM2 process alarm triggered (temperature limit, deviation or valve fault). Enter alarm menu to check alarm mode and threshold.
Valve Control Functional Faults (Not the above hardware fault codes, DTV specific)
DTV valve controller, valve no movement / frequent chattering, PV reading normal but abnormal valve action, not classified as 80xx hardware faults:
- Valve no movement
Check ON/OFF of OUT1/OUT2 relay contacts with multimeter
Verify actuator AC220V supply and internal limit switches
พารามิเตอร์:【Valve full close to full open time】1018H incorrectly set to zero will disable valve action
- Valve chattering / frequent pulsing
Increase valve dead band (1019ชม, หน่วย 0.1%)
PID proportional band PB too small (overly aggressive P gain) causing oscillation; run AT auto-tuning
- Mismatch between displayed valve opening and actual valve position (with AI feedback)
Enable valve feedback coil (0817H=1), start valve feedback auto-calibration (0818H=1), redefine stroke upper/lower limit 101AH/101BH
General Troubleshooting Workflow (Recommended sequence)
- Power cycle to eliminate transient interference
- Verify sensor wiring and sensor integrity
- Confirm input type setting and hardware jumper (analog input must set jumper correctly)
- Read PV register via host to confirm fault code
- Software fault: Factory reset and reconfigure parameters; ความผิดพลาดของฮาร์ดแวร์ (8006/8007): Replace controller directly
Important Distinction for Alarms
80xx codes = Measurement input / hardware faults (PV cannot be read)
ALM1/ALM2 alarms = Process alarms (temperature limit, ส่วนเบี่ยงเบน, valve fault, PV acquisition normal). Do not confuse the two.
- Model Coding Rule for full DTV series
DTV + มิติข้อมูลแผง + ประเภทเอาต์พุต
- มิติข้อมูลแผง (2 ตัวเลือก)
4896: 48×96มม (1/8 จาก, your current model)
9696: 96×96มม (1/4 จาก)
- Suffix code (Hardware output)
ค: เอาท์พุทรีเลย์ (OUT1 open, OUT2 close, รีเลย์คู่, ที่พบบ่อยที่สุด, DTV4896C)
ร: Basic relay (single channel valve relay)
ล: เอาต์พุตกระแสเชิงเส้น (4~20mA for analog electric actuators)
วี: Voltage pulse output (solid state pulse drive)
Unified power: AC100~240V; all models equipped with RS485 Modbus RTU/ASCII, dual alarm and valve PID control.
- Complete DTV Model List (Mainstream available models)
1)48×96mm (DTV4896 series, slim vertical)
- DTV4896C: Dual relay output (เปิด + Close valve), dedicated for electric valves (main model)
- DTV4896R: Single relay output
- DTV4896L: 4~20mA linear current output
- DTV4896V: Voltage pulse solid-state output
2)96×96mm (DTV9696 series, square large display)
- DTV9696C: Dual relay open/close valve (same logic as DTV4896C, only larger panel)
- DTV9696R: Single relay
- DTV9696L: 4~20mA linear current output
- DTV9696V: Pulse voltage output
Universal input across all series: K/J/T/E/N/R/S/B/L/U/TXK thermocouple, Pt100/JPt100 RTD, 0~~5V/0~~10V/4~20mA analog input.
- Model Suffix Comparison
| คำต่อท้าย | ประเภทเอาต์พุต | แอปพลิเคชัน | Matches your DTV4896C |
| ค | Dual relay (OUT1 Open, OUT2 Close) | Electric actuators with forward/reverse rotation | ✅ Your model |
| ร | Single relay | Single direction valve, simple on-off control | Alternative spare |
| ล | 4~20mA analog signal | Modulating analog electric valves | Analog valve control |
| วี | Voltage pulse | SSR solid state drive, contactless frequent operation | High frequency on-off control |
- ล้าสมัย / Legacy Notes
DTV series only has 4896 และ 9696 two panel sizes, no 4848 หรือ 7272 ตัวแปร;
No derivatives such as DTV4896D, DTV4896E;
Communication registers, fault codes and parameter menus: C/R/L/V share identical firmware logic, only hardware output differs.