Schneider CVS100B and CVS100F

Both Schneider CVS100B and CVS100F are 100A frame molded case circuit breakers in the EasyPact CVS series.

The core differences lie in the breaking capacity class and application scenarios.

  1. Core Parameter Comparison (415วีและ)
ItemCVS100BCVS100FKey Difference
Ultimate Short‑Circuit Breaking Capacity (ห้องไอซียู)25ที่36ที่Type F is 44% higher, with stronger short‑circuit withstand capability
Service Short‑Circuit Breaking Capacity (Ics)25ที่ (100% ห้องไอซียู)36ที่ (100% ห้องไอซียู)Same ratio as Icu; Type F is more suitable for harsh short‑circuit environments
Ics at 440V15ที่18ที่Type F maintains better breaking performance at higher voltages
จัดอันดับช่วงปัจจุบัน16–100A16–100ASame; both support TM‑D thermal‑magnetic releases
Pole Configurations3P/3d, 4P/4d/3d3P/3d, 4P/4d/3dSame protective pole configuration
Release TypeTM‑D (Thermal‑Magnetic), ETS (Electronic)TM‑D (Thermal‑Magnetic), ETS (Electronic)Same basic protection functions
Mounting Typeที่ตายตัว, Plug‑inที่ตายตัว, Plug‑inSame mounting compatibility
Wiring TypeFront wiring / Rear wiringFront wiring / Rear wiringSame wiring flexibility
  1. Analysis of Key Differences
  2. Breaking Capacity Class (Most Important Difference)

Type B (Basic): 25kA breaking capacity, suitable for general industrial and commercial buildings and conventional power distribution systems with low short‑circuit current.

ประเภท เอฟ (สูง): 36kA breaking capacity, suitable for high short‑circuit current applications, such as near transformers, frequent starting of large motors, or heavy‑duty industrial environments.

  1. Application Selection
แบบอย่างRecommended ApplicationsUnrecommended Applications
CVS100BCommercial buildings, small factories, civil distribution, secondary distributionLarge industrial plants, near generators/transformers, systems with shortircuit current >25ที่
CVS100FHeavy industry, large motor circuits, primary distribution, near power sourceSimple distribution systems with budget constraints and short ircuit current <25ที่
  1. Other Minor Differences

ราคา: Type F is normally more expensive than Type B (ประมาณ. 10–20%) due to higher breaking capacity.

Internal Structure: Type F uses a reinforced arc extinguishing system and contact design to withstand higher short‑circuit energy.

Accessory Compatibility: Both are compatible with the same accessories, including auxiliary contacts, shunt / undervoltage releases, Vigi earth leakage modules, ฯลฯ.

  1. Selection Guide
  2. Calculate system short‑circuit current: Calculate the expected short‑circuit current based on transformer capacity and line impedance, and select a model with breaking capacity ≥ the calculated value.
  3. Evaluate power supply environment: Prefer Type F when close to transformers or large loads; Type B can be used for secondary / tertiary distribution with low short‑circuit current.
  4. Consider future expansion: Reserve 10–20% margin for short‑circuit current to avoid insufficient breaking capacity after system expansion.
  5. Budget balance: Type B reduces cost when safety requirements are met; Type F is recommended for critical circuits to improve reliability.
  6. Additional Notes

Both models comply with IEC 60947‑2 and provide overload and short‑circuit protection.

The TM‑D thermal‑magnetic release has adjustable overload protection (Ir) and short‑circuit instantaneous protection (Im) to match different load characteristics.

The ETS electronic release provides more precise protection and additional functions (e.g. earth fault, overload alarm), available for both models.