ACS580-01-246A-4
- ACS580: ايه بي بي new generation general wall-mounted VFD مسلسل
- 01: Standard integrated wall-mounted unit (non-cabinet modular type 04)
- 246أ: Rated output current 246 أ
- 4: 3-phase input voltage class 380~480 V AC
Optional protection suffixes:
No suffix = IP21 standard version; +B056 = IP55 high-protection dustproof and waterproof version
حجم الإطار: R8
Order material numbers: 3AUA0000080507 (IP21), 3AUA0000083582 (IP55)
- القوة المقدرة / Current Ratings (400 V Grid)
| نوع التحميل | تيار الإخراج | قوة المحرك المتطابقة | Overload Specification |
| معيار / Light Load (المشجعين & مضخات) ILd | 234 أ | 132 كيلوواط | 110% ل 1 min every 10 دقيقة |
| Rated Nominal Current In | 246 أ | 132 كيلوواط | Continuous rated operation |
| Heavy Load (الناقلون / Extruders) IHd | 206 أ | 110 كيلوواط | 150% ل 1 min every 10 دقيقة |
Apparent output capacity: 170 كيلو فولت أمبير; Overall efficiency ≥ 98%
ثالثا. المعلمات الكهربائية الأساسية
- Input Power Supply
Phases: 3-مرحلة (3PH)
الجهد االكهربى: AC 380~480 V ±10%
Mains frequency: 47.5~63 Hz
Power factor correction: Built-in DC choke (standard for R8 frame)
- Output Drive
الجهد الناتج: 0~Uin (0~480 V)
Output frequency: 0~500 Hz
Control algorithms: Scalar V/F + Sensorless Flux Vector Control
Torque performance: 100% rated torque available at 0.5 هرتز; Torque response <10 ms
- Standard Built-in I/O Terminals (Onboard Control Board)
| يكتب | كمية | Specification Description |
| Analog Input AI | 2 القنوات | Switchable 0~10 V / 4~20 mA |
| Analog Output AO | 2 القنوات | 0~10 V / 4~20 mA |
| Digital Input DI | 6 القنوات | 24 VDC NPN/PNP compatible |
| Digital Output DO | 3 القنوات | Relay dry contacts (250 بطالة / 2 أ) |
| Communication Port | 1 × RS485 | Modbus RTU standard; expandable to Profinet/Profibus/EtherNet/IP |
| منفذ يو اس بي | 1 قناة | PC commissioning, parameter upload & download |
- Full Standard Protection Functions
التيار الزائد, الجهد الزائد, انخفاض الجهد, الزائد, IGBT overtemperature, motor stall, خطأ الأرض, خسارة المرحلة, حماية المماطلة, cooling fan fault, حماية ماس كهربائى, parameter loss alarm.
- الأبعاد الميكانيكية & وزن
IP21 Standard Wall-mounted (ACS580-01-246A-4)
Overall size: ح 615 × W 270 × D 250 مم
Net weight: 21 كجم
IP55 High-protection Model (ACS580-01-246A-4+B056)
Overall size: ح 965 × W 300 × D 452 مم
Net weight: 77 كجم
تصاعد: تركيب الجدار العمودي; leave ≥200 mm ventilation space top and bottom for heat dissipation
- Environmental Operation Specifications
- درجة حرارة التشغيل: -15℃ ~ +50℃ (derate output by 5% at 50℃)
- تخزين / transport temperature: -40℃ ~ +70℃
- فئة الحماية: Base IP21; upgrade to IP55 with +B056 option
- ارتفاع: Full power up to 1000 م; derate 1% per additional 100 m above 1000 م
- رطوبة: 5~95% RH, لا التكثيف, no corrosive gas
- Standard Built-in & الملحقات الاختيارية
Factory Standard Built-in Components
Detachable Chinese assistant control panel
Integrated DC choke
Basic I/O control board, مودبوس ار تي يو
Bottom cooling fan
Optional Expansion Parts
- Braking resistor / braking unit: Mandatory for high-inertia start-stop and overhauling loads
- Communication adapters: بروفيبوس موانئ دبي, Profinet IO, إيثرنت/IP
- EMC filters: الفئة أ / الفئة ب, compliant with industrial EMC standards
- خارجي 24 V power supply module, remote panel extension cable
- Complete IP55 cabinet kit (model suffix +B056)
سابعا. سيناريوهات التطبيق النموذجية
- التدفئة والتهوية وتكييف الهواء & معالجة المياه (Light Load 132 كيلوواط)
Cooling fans, tunnel exhaust fans, constant-pressure water supply main pumps, sewage agitators, أبراج التبريد; variable-torque energy-saving operation.
- التعامل مع المواد & Building Materials (Heavy Load 110 kW Class)
سيور ناقلة, bucket elevators, cement mixers, بثق, أجهزة الطرد المركزي; frequent start-stop and shock loads.
- الآلات العامة
Large compressors, wire drawing machines, mixing mills, paper production lines; precise speed regulation + multi-speed logic.
- التعدين & الموانئ
Belt transfer equipment, dust removal fans; ideal IP55 model for wide voltage tolerance and strong dust resistance.
ثامنا. Adjacent Power Model Comparison within the Same Series
| نموذج | التصنيف الحالي | Standard Power | Heavy Load Power |
| ACS580-01-206A-4 | 206 أ | 110 كيلوواط | 90 كيلوواط |
| ACS580-01-246A-4 | 246 أ | 132 كيلوواط | 110 كيلوواط |
| ACS580-01-293A-4 | 293 أ | 160 كيلوواط | 132 كيلوواط |
- Core Product Advantages
- Fully integrated functions: Built-in choke, مودبوس, multi-channel I/O; ready for complete set without extra options
- Chinese assistant panel: Guided commissioning wizard, one-click motor identification
- Wide grid compatibility: Universal 380~480 V, compatible with domestic 380 V and overseas 400/440 V grids
- Dual control modes: Simple V/F control + sensorless vector, suitable for both fan and heavy-duty equipment
- Optional IP55 high protection; direct wall mounting outdoors or in humid workshops without separate control cabinet
- Comprehensive energy-saving algorithms: Sleep mode, flow optimization, soft start-stop, cutting fan and pump energy consumption by over 30%
- Compatible with mainstream industrial buses, seamlessly connected to PLC systems such as Siemens, ميتسوبيشي, ابتكار
- Key Installation & مواصفات الأسلاك
- أسلاك الدائرة الرئيسية
مدخل: L1/L2/L3 connected to 3-phase 380 V; Output U/V/W connected to 3-phase asynchronous motor; PE earth terminal reliably connected to cabinet ground.
- Control Cable Requirements
Route shielded analog signal cables separately with a minimum spacing of 30 cm from power cables; single-end shielding grounding for digital twisted-pair cables.
- Mandatory Heat Dissipation Rules
Vertical mounting for R8 frame; top ventilation gap ≥200 mm, side gaps ≥50 mm; blow filter screens monthly in dusty environments.
- Braking Selection Reminder
Braking resistors must be fitted for high inertia shutdown and overhauling loads, otherwise frequent DC overvoltage faults will occur.
- Quick Troubleshooting Checklist
- Overcurrent OL: كشك المحرك, output short circuit, cable earth breakdown, insufficient derating for heavy loads
- Overvoltage OV: No braking resistor fitted for inertial loads, transient grid high voltage
- Overtemperature OT: Blocked air ducts, ambient temperature over 50℃, faulty cooling fan
- خسارة مرحلة الإخراج: Loose motor wiring, broken wire on U/V/W one phase
- Communication Loss: Poor shield grounding, missing bus terminating resistor
All Control Modes of ABB ACS580-01-246A-4
All ACS580 drives share one unified control core with no functional cuts for the 246 أ (R8 frame) نموذج. Three major control categories are supported: Scalar V/F, ناقل بدون مستشعر, Vector with Encoder, subdivided into 5 operation modes to cover fans/pumps, general heavy loads and high-precision positioning applications.
- Scalar V/F Control (المعلمة 99.04 = SCALAR)
- Linear V/F (Default for Light Load Fans & مضخات)
Voltage rises linearly with frequency with uniform voltage boost from 0~50 Hz. Suitable for fans, blowers, pumps and general centrifugal loads.
سمات: هيكل بسيط, multi-motor parallel drive (one VFD driving multiple asynchronous motors); weak low-speed torque, zero torque at 0 هرتز.
التطبيقات: أنظمة التدفئة والتهوية وتكييف الهواء, constant-pressure water supply, multi-pump parallel systems.
- Quadratic V/F (Square Curve, Dedicated for Fans & مضخات)
Voltage increases proportional to the square of frequency, matching the torque characteristic of fans and pumps for optimal energy efficiency.
سمات: Greatly reduces motor excitation loss and reactive power under light load; even weaker low-speed torque.
Typical scenarios: Cooling tower fans, circulation pumps, dust extraction blowers.
- Boostable Torque V/F (Voltage Boost V/F)
Raises output voltage at low frequencies to compensate insufficient low-speed torque.
التطبيقات: سيور ناقلة, mixing equipment, light starting resistance loads.
- Sensorless Flux Vector Control (المعلمة 99.04 = SENSORLESS)
The primary general heavy-load control of ACS580; no encoder required, standard for this 246 A model with no extra options needed.
Core Performance
- 100% rated torque output at 0.5 هرتز; high starting torque to overcome static friction
- Torque response <10 ms, far superior dynamic speed regulation over V/F control
- Supports precise current limiting, anti-stall protection and continuous heavy-load operation
- Static & rotating motor identification supported, compatible with new and old motors
Applicable Loads
الناقلون, خلاطات, بثق, الضواغط, woodworking machinery, single heavy-duty motor drives.
القيود
Cannot maintain full torque at zero speed (0 هرتز); precise closed-loop speed control unavailable without encoder feedback.
ثالثا. Vector Control with Encoder (المعلمة 99.04 = ENCODER)
Requires optional FEN-01 / FEN-11 encoder interface module installed in the VFD expansion slot.
- Supports pulse encoders: HTL / TTL incremental encoders
- Closed-loop speed control with 100% continuous rated torque at 0 هرتز
- Speed control accuracy ±0.01% of rated speed
- Enables simple positioning, jog operation and tension control
التطبيقات
Wire drawing machines, winding/unwinding equipment, high-precision transmission, machinery requiring zero-speed load holding.
- Two Operation Reference Modes (Speed Command Source, Independent of Above Motor Control Algorithms)
- Local Control (Panel Reference)
Frequency set via control panel knob / أزرار; local start-stop and speed adjustment for single-unit commissioning.
- التحكم عن بعد (External Reference, Mainstream for Engineering)
Speed commands and start-stop signals come from external channels with flexible combinations:
- Analog reference: AI1/AI2 (0–10 V / 4-20 مللي أمبير)
- Multi-speed DI digital terminal reference: حتى 7 fixed preset speeds
- Pulse frequency reference (optional IO module required)
- Fieldbus reference: مودبوس ار تي يو (معيار), بروفيبوس موانئ دبي, بروفينيت, إيثرنت/IP, إلخ.
- PID closed-loop reference: Built-in process PID for closed-loop constant control of pressure/flow/temperature (core function for constant-pressure pump & fan water supply)
- Special Process Control Modes (Built-in Functions Based on Vector / V/F Core)
- PID Process Control
Independent onboard PID regulator; no external PLC required for automatic constant pressure and flow control of pressure, liquid level and temperature.
- Multi-pump Cycling Soft Start (HVAC Special Function)
One-drive-multiple circulating water supply, automatic alternation of main and auxiliary pumps, energy saving via sleep & wake-up logic.
- JOG Jogging Control
Low-speed jog triggered via DI terminals for equipment maintenance and commissioning.
- DC Pre-excitation
DC pre-magnetization before startup to boost instantaneous starting torque in vector mode.
- كشك / Anti-overcurrent Torque Limiting
Automatic torque limitation to avoid overcurrent faults under heavy load.
- اختيار سريع & Distinction Table
| Control Type | Encoder Required | Low-speed Torque | الاستخدام النموذجي |
| Quadratic V/F | لا | قليل | Energy-saving control for fans & مضخات |
| Linear V/F | لا | معتدل | Multi-motor parallel driving |
| ناقل بدون مستشعر | لا | عالي (Full torque at 0.5 هرتز) | الناقلون, خلاطات, general heavy loads |
| Vector with Encoder | FEN Module Required | عالية جدًا (Zero-speed torque holding) | Winding equipment, high-precision transmission & تحديد المواقع |
Applicable Scenarios of Closed-Loop Vector Control with Encoder for ABB ACS580-01-246A-4
Preface
This control mode uses parameter code 99.04=ENCODER. Optional FEN-01 (HTL) / FEN-11 (TTL) incremental encoder modules are mandatory. Real-time speed feedback from the motor shaft encoder delivers three core advantages:
- مستمر 100% rated torque holding at 0 هرتز (sensorless vector cannot hold load at zero speed)
- Speed control accuracy ±0.01% rated speed with no low-speed jitter or step loss
- Supports precise tension closed-loop control, multi-axis synchronization, simple positioning and constant-torque processes
Closed-loop vector control is only selected for working conditions requiring zero-speed load holding, high low-speed precision, stable tension, multi-axis synchronization and slip-free heavy start-stop. Standard fans, pumps and single ordinary conveyors can operate reliably with sensorless vector or V/F control only.
- Winding & Unwinding Industry (Most Typical High-power Application, مطابقة 132 kW Class 246 A Model)
المعدات المطبقة
Paper rewinders, plastic film extrusion winders, rubber calender winding/unwinding machines, non-woven slitting machines, metal foil wire drawing & آلات اللف, cable stranding machines
Mandatory Process Requirements for Closed-Loop Vector
- Smooth low-speed startup and constant tension maintenance during shutdown; no loose rolls, stretching or material breakage at zero speed
- Automatic constant tension as roll diameter dynamically changes between large and small reels, speed follows upstream master machine
- No tension fluctuation during high-low speed switching to prevent wrinkling or stretching deformation of web materials
- Multi-section linkage: Synchronized operation of unwinding-traction-winding three axes
Open-loop Disadvantages: Insufficient low-speed torque without encoder leads to web slipping and out-of-control tension.
- تحديد المواقع بدقة عالية / Intermittent Reciprocating Heavy-duty Equipment
المعدات المطبقة
Large gantry feeders, heavy plate translation positioning tables, stone cutting feeders, cement block stacking conveyors, large packaging reciprocating cross-cutting machines
Process Requirements
- Precise stop at target positions with minimal repetitive positioning error; frequent jog & inching maintenance operations
- No position shifting or slipping when stationary under full load
- No speed overshoot during acceleration & deceleration; no jitter or impact on heavy start-stop
ثالثا. High-inertia Overhauling / Vertical Lifting Constant-torque Loads (High-power 110/132 kW Heavy-duty Conditions)
المعدات المطبقة
Downward mine belt conveyors, large bucket elevators, heavy vertical mixers, lifting silo discharge drives
Process Pain Points Unsolvable by Open-loop Control
Reverse load generated by material self-weight requires full torque braking maintained at zero shutdown speed; overhaul runaway and overvoltage alarms easily occur at low descending speeds. Encoder closed-loop corrects speed in real time to suppress regenerative impact and stabilize DC bus voltage with braking units.
- Multi-motor Synchronized Production Lines (Long-distance High-power Synchronous Transmission)
المعدات المطبقة
Cement kiln chain conveyors, long-distance multi-drive mine belts, multi-layer drying synchronized roller tables, continuous metal pickling lines
Process Requirements
Rigid synchronization of multiple motors with minimal speed deviation across sections to avoid plate stretching, belt deviation and tearing. Closed-loop vector with encoder feedback achieves far superior multi-motor synchronization accuracy compared to open-loop sensorless vector.
- Heavy-duty Equipment for Extrusion, Kneading & High-viscosity Mixing
المعدات المطبقة
Plastic single/twin-screw extruders, rubber internal mixers, chemical high-viscosity reactor agitators, main asphalt mixing machines
Process Requirements
- Extremely high starting resistance for low-temperature high-viscosity materials; full torque output at 0 Hz to avoid startup stalling
- Constant extrusion torque throughout operation for uniform output thickness
- No torque ripple under steady low-speed operation for consistent product thickness
- أجهزة الطرد المركزي & High-speed Precision Rotating Equipment
المعدات المطبقة
Large chemical separation centrifuges, high-speed paper dehydration centrifuges, large horizontal food centrifuges
Process Requirements
High-precision stable speed across wide speed ranges with minimal speed fluctuation during acceleration/deceleration. Real-time speed correction via encoder feedback at high operating speeds eliminates resonance and uneven material stratification.
سابعا. High-power Stenter, جلسة & Padder Equipment for Textile Printing & Dyeing
المعدات المطبقة
High-power stenters, water squeezing & calendering machines, continuous dyeing long lines
Process Requirements
Synchronized drafting of multiple rollers without fabric stretching or shrinkage; zero-speed load holding during low-speed fabric threading to avoid fabric accumulation and slipping; stable tension throughout operation.
ثامنا. Scenarios Unsuitable for Closed-Loop Vector Control (Select V/F or Sensorless Vector Directly)
- المشجعين, أبراج التبريد, circulation pumps, dust extraction blowers (variable-torque loads with no zero-speed load holding demand)
- Single light-duty belt conveyors, small mixers, الضواغط (no high-precision synchronization or tension control requirements)
- One-drive-multiple parallel multi-motor systems (only scalar V/F control applicable; encoder closed-loop cannot support multi-motor parallel driving)
Quick Application Selection Reference Table
| Core Working Condition Requirement | Recommended Control Mode | التشفير (FEN Module) Required |
| المشجعين, مضخات, multi-motor parallel driving | Scalar V/F | لا |
| Ordinary conveyors, خلاطات, الضواغط | ناقل بدون مستشعر | لا |
| Winding/unwinding, tension control, zero-speed load holding | Closed-loop Vector with Encoder | FEN-01/FEN-11 Required |
| تزامن متعدد المحاور, precision positioning, high-inertia overhauling loads | Closed-loop Vector with Encoder | FEN Module Required |
| High-viscosity extrusion, kneading, high-power centrifuges | Closed-loop Vector with Encoder | FEN Module Required |
Supplementary Supporting Hardware (ACS580-01-246A-4 R8 Frame)
- HTL incremental encoder: Select FEN-01
- TTL differential encoder: Select FEN-11
- Braking resistors / braking units must be fitted for high-inertia overhauling scenarios to eliminate regenerative overvoltage faults
المقاولين,قاطع الدائرة,العاكس للطاقة الشمسية,عداد كهرباء,البطاريات الشمسية



















NH42-63-318x560.png)