Allen-Bradley 1756-PA75 Backplane Power Supply

1756-PA75 1756: ControlLogix 5000 Chassis Series PA: AC Input Backplane Power Supply 75: Maximum backplane output power 75W Derivative Models: 1756-PA75K: PCB with conformal coating (for corrosive and humid environments) 1756-PA75R: Redundancy-specific power supply. Cannot be directly used interchangeably with PA75. Requires 1756-PSCA2 Adapter + 1756-CPR2 Cable > ⚠️ Critical Note: The standard 1756-PA75 does ...

  • تفاصيل المنتج

1756-PA75

1756: ControlLogix 5000 Chassis Series

السلطة الفلسطينية: AC Input Backplane مزود الطاقة

75: Maximum backplane output power 75W

Derivative Models:

1756-PA75K: PCB with conformal coating (for corrosive and humid environments)

1756-PA75R: Redundancy-specific power supply. Cannot be directly used interchangeably with PA75. Requires 1756-PSCA2 Adapter + 1756-CPR2 Cable

> ⚠️ Critical Note: The standard 1756-PA75 does not support native redundancy! PA75R kit must be selected for redundant configurations.

  1. المواصفات الكهربائية الأساسية

Input Ratings

جهد الإدخال: 85~265 VAC (wide-range, compatible with 120V/240V systems)

تكرار: 47~63 Hz

Maximum input apparent power: 100 فرجينيا

Maximum inrush current: 20 أ

Multi-rail DC Backplane Output (75W full load at 0~60℃)

Output RailMaximum Current
5.1 في العاصمة13.0 أ
3.3 في العاصمة4.0 أ
1.2 في العاصمة1.5 أ
24 في العاصمة (Auxiliary Backplane)2.8 أ

ميكانيكية & المواصفات البيئية

Form Factor: Standard single-slot 1756 وحدة الطاقة, installed in the leftmost slot of ControlLogix chassis

أبعاد: 140 × 112 × 145 مم

وزن: تقريبا. 1.45 كجم

درجة حرارة التشغيل: 0~+60 ℃; درجة حرارة التخزين: -40~+85 ℃

رطوبة: 5%~95%, غير التكثيف

العزل: Reinforced insulation between input and backplane, rated for continuous 250V withstand

الشهادات: أول, م, سي سي سي, وكالة الفضاء الكندية, إلخ.

ميزات الحماية: الجهد الزائد, التيار الزائد, على درجة الحرارة, حماية ماس كهربائى

  1. Front Panel Indicators
  2. نعم (أخضر)

Steady ON: Power supply healthy

عن / Flashing: Fault detected

  1. FAULT (أحمر)

Illuminated: الزائد, على درجة الحرارة, internal failure

  1. إنذار (Relay Dry Contact)

Passive alarm contact, can be wired to external alarm circuits.

  1. Comparison with Similar Models
نموذجنوع الإدخالتصنيف القوةRedundancy Capabilityسيناريوهات التطبيق النموذجية
1756-PA7585–265V AC75دبليوStandard standalone unit, not directly redundantGeneral single-chassis systems
1756-PA75K85–265V AC75دبليوStandalone, conformal coated PCBرطب, مغبر, corrosive enclosures
1756-PA75R85–265V AC75دبليوSupports dual-unit redundancy (requires PSCA2+CPR2)Critical production lines requiring zero downtime
1756-PB7518–32V DC75دبليوStandalone DC input power supplySites with only 24VDC available
1756-PA7285–265V AC72دبليوLegacy model, lower load capacityReplacement for obsolete equipment
  1. Key Selection Rules & تجنب المأزق
  2. Do not judge load solely by total 75W power rating!

Calculate current consumption of all modules in the chassis for each voltage rail (5.1V/3.3V/1.2V). Exceeding the limit on any single rail will trigger FAULT shutdown.

  1. Installation position: Must be mounted in the first leftmost slot of the chassis; cannot be placed in middle or right slots.
  2. Thermal management: Avoid long-term enclosure temperature above 55℃; derate power in high-temperature environments.
  3. Hot Swapping: Hot-swap capable. It is recommended to stop controller logic before swapping to prevent transient interference to communication modules.
  4. Redundancy Misconception: Two standard PA75 units cannot be paralleled directly to achieve redundancy. PA75R redundancy kit is mandatory.
  5. استكشاف الأخطاء وإصلاحها الشائعة
  6. FAULT red light ON, OK light OFF

Step1: Remove all modules from chassis, leave only power supply and power on.

If fault persists under no load → Power supply failure.

If normal under no load → Short circuit or overload from chassis modules.

  1. Circuit breaker trips immediately after power-up

The unit has high inrush current on startup; select D-curve MCB for upstream protection. Check L/N/PE wiring for short circuits.

  1. Intermittent FAULT alarm after continuous operation

Insufficient cabinet ventilation, dust accumulation; overtemperature protection triggered due to long-term near-full-load operation.

  1. Typical Industry Applications

Chemical industry, معالجة المياه, automotive production lines, علم المعادن, التعامل مع المواد, زيت & غاز, large building DCS/PLC systems (power supply for ControlLogix L7x/L8x controller chassis).

Overload Capability of 1756-PA75 (Based on Rockwell Official Document 1756-TD005)

  1. Critical Premise

75W = Continuous rated output power (0~60℃ ambient temperature), NOT peak power. Continuous overload operation is not officially permitted.

The power supply adopts independent multi-rail current limiting protection.

Protection triggers once any single rail exceeds current limit, regardless of total power consumption.

Continuous rated current hard limits for each backplane rail:

Output RailContinuous Rated Current
5.1 VDC13.0 أ
3.3 VDC4.0 أ
1.2 VDC1.5 أ
لوحة الكترونية معززة 24 VDC Auxiliary2.8 أ
  1. Overload Classification & Actual Endurance

2.1 Continuous Overload (Long-term operation above rating)

❌ Not supported or approved by Rockwell

If any rail runs continuously above rated current, or total power exceeds 75W:

  1. Internal temperature rises steadily;
  2. FAULT indicator illuminates and output shuts down for protection once threshold is reached;
  3. Long-term marginal overload accelerates aging of internal capacitors and power semiconductors, shortens service life and voids warranty.

> Field Experience: Continuous load between 70~75W is already the design ceiling. Long-term operation at this level is not recommended. Operation above 75W is strictly prohibited.

2.2 Transient Short-duration Overload (Module power-on inrush, pulse loads)

1756-PA75 can withstand limited short-term peak loads.

Rockwell does not publish precise millisecond overload curves (no specified duration for 120%/150% الزائد).

Summary of official design principles plus extensive field experience:

Capable of sustaining hundreds-of-millisecond transient inrush current (simultaneous power-up surge of chassis modules);

Transient peak current may briefly exceed rated value, but cannot be sustained steadily;

System load design shall never rely on transient overload capability. Load calculation must adopt continuous rated parameters.

2.3 Protection Mechanism & Action Logic

  1. Electronic Current Limiting + Hiccup Protection Mode

الزائد / Short-circuit → Output current clamped → Voltage drop → Temporary shutdown → Automatic retry (hiccup cycling).

  1. Front panel FAULT red indicator steady ON, OK indicator OFF
  2. Alarm relay contact actuates
  3. Automatic recovery is achievable in most cases after overload load is removed. Severe sustained overload may require power cycle to recover.

2.4 Temperature Degradation of Overload Tolerance

Rated 75W output condition: Ambient Temperature 0~60℃

Cabinet temperature >50درجه مئوية: Recommend 5%~10% power derating

Long-term cabinet temperature >55درجه مئوية: Even if total power ≤75W, thermal accumulation easily triggers overtemperature overload protection.

درجة الحرارة المحيطة >60درجه مئوية: Rated output performance is no longer guaranteed; overload endurance drops significantly.

  1. Two Common Critical Misunderstandings

سوء الفهم 1: Parallel two standard 1756-PA75 to increase overload capacity

❌ Absolutely Not Allowed!

Standard PA75 has no current sharing circuit. Parallel connection on backplane is forbidden.

It cannot share load, expand capacity or realize redundancy. Parallel setup will create circulating current and lead to single-point burnout.

For redundancy or capacity expansion: Adopt 1756-PA75R redundancy power supply kit (with 1756-PSCA2 & 1756-CPR2).

سوء الفهم 2: System will not overload as long as total power <75دبليو

❌ Independent current limiting for each voltage rail!

مثال: Total power 68W, but 5.1V rail current reaches 13.5A → Immediate overload shutdown.

✅ Standard load verification method: Calculate total power AND current consumption of every DC rail.

  1. Load Design & توصيات الاختيار
  2. Reserve 15%~25% design margin for steady-state operating load
  3. Sum up backplane power consumption of all modules, tabulate current demand for 5.1V/3.3V/1.2V/24V rails separately
  4. Further increase margin if chassis contains numerous high-inrush I/O modules (مخرجات التتابع, high-speed counters)
  5. If intermittent FAULT flashes occur during operation, priority inspection items: Single rail current close to limit, inadequate cabinet heat dissipation.
  6. Brief Overload Performance Comparison between PA75 and PA75R

PA75 (معيار): Standalone unit, overload protection logic as stated above

PA75R (Redundancy model): Single unit rated power also 75W.

In redundant configuration, one unit must temporarily bear full load after the other fails. Transient load margin is optimized in firmware, yet continuous load cannot exceed single-unit 75W specification.

Complete Model List for 1756-PA75 Family (75W Power Class)

> Model Nomenclature Guide

السلطة الفلسطينية: AC Input; PB: 24V DC Input; PC/PH: Special wide-range DC Input

75: Rated backplane output power 75W

ك: PCB conformal coating (resist humidity & الغاز المسببة للتآكل)

ر: Redundancy dedicated power supply (cannot be used as standalone regular unit)

XT: Extended temperature heavy-duty industrial version

  1. AC Input 75W Series (PA75 Family)
  2. 1756-PA75

Standard AC power supply, 85~265VAC, 75دبليو, most widely used for general applications.

  1. 1756-PA75K

Conformal coated variant. Electrical performance identical to PA75. Suitable for chemical, رطب, dusty and corrosive enclosures.

  1. 1756-PA75R

Redundancy-dedicated AC power supply, equipped with internal hardware for redundant communication. Must be matched with: 1756-PSCA2 (Redundancy Adapter) + 1756-CPR2 Cable.

⚠️ Forbidden to install directly into chassis and operate as standalone unit!

  1. 1756-PA75RK

Redundancy type + conformal coated PCB. Selected for redundant systems deployed in corrosive environments.

  1. 75W DC Input Equivalent Models (For cross-reference replacement)
  2. 1756-PB75: 18~32VDC (24إمدادات العاصمة الخامس) standard power supply
  3. 1756-PB75K: 24V DC input + conformal coating
  4. 1756-PB75R: 24V DC redundancy power supply
  5. 1756-PB75RK: 24V DC redundancy + conformal coating
  6. 1756-PC75: 48V DC dedicated input power supply
  7. 1756-PH75: Wide-range DC 48~125VDC (محطة فرعية, DC panel applications)
  8. 1756-PH75K: Wide-range DC input + conformal coating
  9. Other Power Rating Power Supplies for the Same Chassis (Selection Distinction)

3.1 Legacy 72W Series (Lower 5V rail current, لا ينصح به للمشاريع الجديدة)

1756-PA72 (تكييف), 1756-PA72K

1756-PB72 (العاصمة), 1756-PB72K

3.2 Low-power single-slot models (Same physical slot width, lower power)

1756-PA50 / PB50: 50دبليو

1756-PA30XT / PB30XT: 30دبليو, XT extended temperature series

3.3 XT Extended Temperature Heavy-duty Series (-20℃~70℃ operating range)

1756-PAXT (AC extended temp), 1756-PBXT (DC extended temp)

1756-PAXTR / PBXTR: Redundancy power supply for XT series

  1. Critical Selection Pitfall Notes
  2. 1756-PA75 ≠ PA75R

Two standard PA75 units cannot be paralleled for redundancy. PA75R kit is required for redundant systems.

  1. K suffix only indicates conformal coating. Electrical parameters and backplane load capacity are fully identical to non-K models; direct interchange is supported.
  2. Mechanical dimension: All standard 75W power supplies (PA75/PA75K/PB75 etc.) are single-slot form factor, mounted on leftmost chassis slot.

PA75R redundancy power supply cannot directly power chassis without matching redundancy adapter.

  1. Hardware revision suffix /A /B: Iterative hardware upgrades. Units with same catalog number (A/B revisions) are electrically compatible and directly interchangeable.

جدول الاختيار السريع

نموذجنوع الإدخالConformal Coatingدعم التكرارسيناريوهات التطبيق النموذجية
1756-PA7585~265VAC❌ NoStandaloneStandard control cabinets in general workshops
1756-PA75K85~265VAC✅ YesStandaloneHigh-humidity, coastal & chemical corrosive environments
1756-PA75R85~265VAC❌ NoRedundant (requires accessories)High-reliability production lines intolerant to shutdown
1756-PA75RK85~265VAC✅ YesRedundant (requires accessories)High-reliability systems in corrosive atmosphere