TeSys Deca GV2ME Motor Circuit Breaker (MPCB), push-button operated, screw clamp terminals
✅ Core Technical Specifications
البولنديين: 3ص
Thermal overload setting range: 2.5~4 A
قوة المحرك المتطابقة (400V ثلاث مراحل): 1.5 كيلوواط
تصنيف الجهد التشغيلي Ue: 690الخامس و, 50/60 هرتز
Insulation voltage Ui: 690V; Impulse withstand voltage Uimp: 6كيلو فولت
Magnetic short-circuit trip: تقريبا. 13×In ≈ 51A (حماية ماس كهربائى لحظية)
Rated short-circuit breaking capacity Icu: 100كا @ 400 فولت
Utilization category: ايه سي-3 (for direct-on-line motor starting); built-in isolation function + حماية فقدان المرحلة
يتحكم: Red STOP pushbutton, black START pushbutton, with TEST position
تصاعد: Standard DIN rail; IP20 (finger-safe on front face)
✅ Model Code Definition
جي في 2: TeSys GV2 motor circuit breaker series
ME: Push-button version (rotary knob version: GV2P)
08: Current rating code, corresponding to 2.5–4A
ج: China version with CCC certification
✅ Protection Functions
- الحماية من الحمل الزائد الحراري: Time-delayed tripping for continuous motor overload & الدوار مقفل; adjustable within 2.5~4A via the setting dial
- Magnetic short-circuit protection: Instant trip for phase-to-phase short circuit
- Phase-loss protection: Accelerated tripping when one phase is lost, preventing motor burnout
- Built-in start/stop operation: Can be used alone for small-motor direct start, or paired with contactors for star-delta / auto-transformer starting circuits
✅ Compatible Accessories (Field-mountable)
GVAN: الاتصال المساعد (1لا + 1NC, for ON/OFF & trip status feedback)
GVAX: اتصال إنذار (differentiates overload trip from short-circuit trip)
GVAD: رحلة تحويلة / undervoltage trip coil
GV2AF3: Busbar, adapter & interlock module
✅ الاختيار & مرجع الاستبدال
Same-series knob variant: GV2P08C (identical thermal-magnetic curve & tripping parameters, 2.5-4أ)
البدائل المحلية: Delixi CDM6e-M, شينت NS2-25 08 (2.5~4A motor protector)
Higher frame upgrade: GV3ME series with same current rating
✅ Wiring Guidelines
Line side L1/L2/L3: قم بتوصيل مصدر الطاقة ثلاثي الطور; Load side T1/T2/T3: قم بتوصيل المحرك
اتصالات مساعدة (إذا تم تركيبها): ل بلك fault feedback & pilot lamp circuits
Setting rule: Align the dial with the motor rated current on nameplate; avoid long-term setting near the upper limit of the range
✅ Common Troubleshooting
- Trips immediately on startup: Mostly short circuit. تحقق من لف المحرك & cable insulation; may also be caused by magnetic trip threshold mismatch
- Trips after running for a period: الزائد. Verify actual motor current, load condition and thermal setting; check poor heat dissipation
- Phase-loss tripping: Check three-phase incoming voltage and loose terminal connections
✅ GV2-ME08C (Push-button Type)
عملية: Push-button start/stop (black START, red STOP)
النطاق الحالي: 2.5~4A; same tripping characteristics as GV2P08C
سمات: Small panel cutout; designed for local cabinet operation; no obvious mid-position trip indication
طلب: Standard domestic panel build, ordinary fans & مضخات المياه (most widely used model)
✅ GV2P08C (Rotary Knob Type)
عملية: مقبض دوار (knob control)
النطاق الحالي: 2.5~4A (same as GV2ME08C)
الميزة الرئيسية: Clear trip mid-position; you can distinguish manual opening from fault tripping at a glance; supports external door-mounted extension handle GV2APN
المزايا: Compliant with UL508 Type E; higher SCCR short-circuit rating; ideal for export equipment, door-mounted operation and strict safety specifications
📋 Comparison Table
| غرض | GV2ME08C | GV2P08C |
| عملية | Push-button start/stop | Rotary knob handle |
| Trip indication | No dedicated mid-position | Locked mid-position after trip |
| Door extension handle | غير معتمد | Compatible with GV2APN |
| نوع المحطة | Screw clamp (suffix C) | Screw clamp (suffix C) |
| Trip curve | Identical thermal-magnetic curve | Same tripping parameters |
| Typical usage | Domestic cabinet local operation | Export machines & door-mounted control |
Step-by-Step MPCB Selection Guide
Applicable to GV2ME / GV2P thermal-magnetic motor circuit breakers, only for three-phase asynchronous DOL motors; NOT for resistive loads, soft starters or inverter output circuits.
خطوة 1: Collect 3 key data from motor nameplate
- التصنيف الحالي في (most critical)
- الجهد المقنن (typically 380/400V AC three-phase)
- القوة المقدرة (only for reference; never select purely by power)
Common mistake: Two 1.5kW motors with different pole counts have different rated currents; power-only selection frequently leads to mis-setting.
خطوة 2: Select the thermal setting range (core rule)
The MPCB adjustment range must fully contain the motor rated current, preferably in the middle third of the range
صيغة:
Lower limit of breaker range < Motor rated current < Upper limit of breaker range
توصية: Place In within 30%~70% of the total range; avoid setting near the upper end
✅ Example: Motor rated current = 3.2A
Select GV2ME08C (2.5~4A); set dial to 3.2A.
❌ If In=3.9A, it still fits but sits close to the upper limit; frequent nuisance tripping will occur under continuous heavy load.
Thermal setting principles
Continuous loads (المشجعين, مضخات المياه): Set thermal current = motor nameplate rated current
Long starting inertia (مراوح كبيرة, الكسارات): Increase to 1.05~1.1×In; never exceed 1.1×In
Frequent jogging & shock loads: Do not simply raise the setting; use a separate thermal relay + contactor combination instead
Thermal trip: الزائد, الدوار مقفل & حماية فقدان المرحلة (time-delayed);
Magnetic trip: Fixed non-adjustable short-circuit protection (13× upper range value, لحظية).
خطوة 3: Choose operation type (زر الضغط / مقبض الباب)
GV2MExxC (push-button, على سبيل المثال. GV2-ME08C): تكلفة منخفضة, local cabinet operation, no clear trip mid-position
GV2Pxx (rotary knob): Visible trip mid-position; add external door handle; suitable for export machines & fault identification
خطوة 4: Choose terminal type
Suffix C: Screw clamp terminals (standard for domestic projects)
لاحقة 3: محطات قفص الربيع (no-tool fast wiring; preferred for automated panel mass production)
خطوة 5: التحقق من الجهد, كسر القدرة & utilization category
- الجهد المقنن: Max 690V AC (400V standard)
- Short-circuit breaking capacity Icu: Must exceed the prospective short-circuit current at the installation point
Ordinary end circuits in small control cabinets: 100kA@400V of GV2 is sufficient
Circuits close to transformers with high short-circuit current: Add upstream fuses if Icu is insufficient
- Utilization category AC-3: Only valid for direct-on-line motor starting
❗ Not applicable: Star-delta starters, مبتدئين لينة, inverter output terminals, محركات التيار المستمر, resistive heating loads, heavy-duty reversing mechanisms.
خطوة 6: Configure accessories based on control scheme
- Local direct start (no PLC): Use MPCB alone with built-in pushbuttons
- Remote PLC control: MPCB only for isolation & حماية, paired with contactors; add GVAN auxiliary contacts (1لا + 1NC) for running/fault feedback; add GVAX alarm contacts to separate overload trip from short-circuit trip
Optional extras: Shunt trip GVAD10, undervoltage trip GVAD01, interconnection busbar GV2AF3
خطوة 7: Exclude unsuitable applications
❌ Inverter output side
❌ DC motors
❌ Resistive loads (سخانات, إضاءة)
❌ Frequent forward/reverse operations (prone to false tripping; use separate thermal relays)
❌ Outdoor / تآكل / dusty environments (must install inside an IP-rated enclosure)
ملخص الاختيار السريع
- Read motor rated current from nameplate (primary data; power is only reference)
- Pick a GV2 model whose current range covers In, keep In away from the upper limit
- Select operation: Push-button GV2ME / Rotary knob GV2P
- Select terminals: Screw C / ربيع 3
- Check short-circuit current to confirm breaking capacity is adequate
- Add auxiliary contacts / trip contacts according to control requirements
Practical Example
محرك: 3-phase 400V, 1.5كيلوواط, rated current = 3.0A
Current range match: 2.5~4A → GV2ME08C
Set dial to 3.0A
Cabinet local operation without door handle → Push-button type
→ Final model: GV2-ME08C