Schneider MiCOM P127BA0V6D3FE0 Overcurrent and Earth Fault Protection Relay Schneider MiCOM Px20 series 3-phase and earth fault comprehensive protection relay, Type B earth current input (1A rated), V6 voltage module (57-130V), D3 communication module (dual-port), FE0 output configuration (8 المرحلات القابلة للبرمجة). It supports 24-250V DC / 48-240V AC power supply with IP50 ingress protection. Applied ...

  • تفاصيل المنتج

Schneider MiCOM P127BA0V6D3FE0 Overcurrent and Earth Fault Protection Relay

Schneider MiCOM Px20 series 3-phase and earth fault comprehensive protection relay, Type B earth current input (1A rated), V6 voltage module (57-130V), D3 communication module (dual-port), FE0 output configuration (8 المرحلات القابلة للبرمجة). It supports 24-250V DC / 48-240V AC power supply with IP50 ingress protection. Applied for the protection of feeders, محولات, motors and other equipment in medium and low-voltage power systems. Part number: P127BA0V6D3FE0.

  1. تعريف الجزء النموذجي
الجزء النموذجيوصف
P127سلسلة المنتجات: MiCOM Px20 series, full 3-phase and earth fault protection relay
بEarth current input type: النوع ب, rated current Ion=1A, measuring range 0.01–8 Ion
A0Auxiliary function code: التكوين القياسي, no special extended functions
V6Voltage module type: V6, input range 57-130V, compatible with PT secondary voltage
D3Communication module type: D3 dual communication ports (front RS232 / rear RS485); supports Modbus / IEC60870-5-103 / DNP3.0
FE0Output configuration: FE0 type, 8 programmable relay outputs (مشتمل 1 master trip output RL1)
P127BA0V6D3FE0Schneider official part number, globally unique identifier
  1. Full Version Technical Specification
فئة المعلمةتحديدملاحظات
Basic Info3-مرحلة & earth fault protection relay, ANSI 50/51/50G/51G protection functionsFor medium/low voltage feeder protection
Part NumberP127BA0V6D3FE0Order strictly by this code
أبعادW144mm × H144mm × D190mmFlush mount, fits standard 19-inch cabinet
مزود الطاقة24-250في العاصمة / 48-240الخامس وWide voltage input for various power systems
Current InputPhase current: 5أ (معيار) / 1أ (خياري); Earth current: 1أ (النوع ب)فئة الدقة 0.2; measuring range 0.01–8× rated value
Voltage Input57-130V (V6 module)Matches PT secondary; phase/line voltage selectable
وظائف الحمايةPhase Overcurrent Stage I/II/III, Earth Overcurrent Stage I/II, Directional Protection, Auto-reclosing, Cold Load Pickup8 setting groups for flexible configuration
تكوين الإخراج8 programmable relay outputs (RL1-RL8), RL1 as master trip outputContact rating: 5A @ 250V AC / 30في العاصمة
واجهة الاتصالاتFront port: RS232 (local commissioning); Rear port: RS485 (system communication)Supports Modbus RTU, IEC60870-5-103, DNP3.0
وظائف القياسحاضِر, الجهد االكهربى, قوة, تكرار, طاقة; dynamic average/peak value recording250 event records, 25 fault records (1600Hz sampling)
Ambient ConditionsOperating: -25درجة مئوية ~ +70 درجة مئوية; Storage: -40°C ~ +85°C; Humidity ≤95% (غير التكثيف)Industrial grade for harsh environments
الشهاداتم, أول, وكالة الفضاء الكندية, اللجنة الانتخابية المستقلة 60255Complies with global power equipment safety standards
خدمة الحياةRelay mechanical life: 10⁵ operationsالحياة الكهربائية: 10⁴ cycles at rated load
وزنتقريبا. 3.5كجمخفيفة الوزن لسهولة التركيب
  1. MiCOM P127 Full Model List
Part NumberنموذجEarth Current InputVoltage Moduleوحدة الاتصالاتتكوين الإخراجSpecial Features
P127BA0V6D3FE0P127النوع ب (1أ)V6 (57-130V)D3 (Dual-port)FE0 (8 المرحلات)Standard feeder protection
P127AA0V6D3FE0P127النوع أ (5أ)V6 (57-130V)D3 (Dual-port)FE0 (8 المرحلات)5A phase current for standard CT
P127BA0Z1D3FE0P127النوع ب (1أ)Z1 (24-60V)D3 (Dual-port)FE0 (8 المرحلات)Low voltage module for special power supply
P127BA0V6D1FE0P127النوع ب (1أ)V6 (57-130V)D1 (Single-port)FE0 (8 المرحلات)Single communication port, فعالة من حيث التكلفة
P127BA0V6D3GE0P127النوع ب (1أ)V6 (57-130V)D3 (Dual-port)GE0 (12 المرحلات)Extended outputs for complex logic
P127BA1V6D3FE0P127النوع ب (1أ)V6 (57-130V)D3 (Dual-port)FE0 (8 المرحلات)With IRIG-B synchronization for precision time control
P127CA0V6D3FE0P127النوع ج (0.1أ)V6 (57-130V)D3 (Dual-port)FE0 (8 المرحلات)High-sensitivity earth input for low-current earthing systems
  1. استبدال & مقارنة بين العلامات التجارية

4.1 Same Brand Direct Replacement

النموذج الأصلينموذج الاستبدالوصفطلب
P127BA0V6D3FE0P127BA0V6D3GE0Upgraded to 12 relay outputs with expanded control capacityComplex protection logic requiring more control outputs
P127BA0V6D3FE0P127BA1V6D3FE0Added IRIG-B time synchronization for higher timestamp accuracyPower system fault analysis requiring precise time stamping
P127BA0V6D3FE0P127CA0V6D3FE0Upgraded to Type C high-sensitivity 0.1A earth inputLow-current earthing systems such as petrochemical and metallurgy
P127BA0V6D3FE0P127BA0Z1D3FE0Replaced with Z1 24-60V low voltage moduleDC systems or special low-voltage power supply environments

4.2 Cross-Brand Equivalent Models

شنايدرايه بي بيسيمنزGEالاختلافات الرئيسية
P127BA0V6D3FE0REF6157SJ60Multilin 369Schneider cost-performance & تكوين مرن
ABB higher integration; Siemens richer protocol support
شنايدر 8 setting groups for multiple protection schemes
GE larger event record capacity (500 records)
  1. بيئة التطبيق & Industry Cases

Recommended Applications

Power System: Substation & distribution feeder protection up to 35kV

الأتمتة الصناعية: محرك, transformer and busbar protection in petrochemical, علم المعادن, coal industries

Railway: التيار الزائد & earth fault protection for traction power supply and station distribution

الطاقة الجديدة: Combiner box and inverter protection for PV and wind farms

المباني التجارية: Standby power system protection for shopping complexes and data centers

Public Utilities: Power protection for pumping stations and water treatment projects

حالات التطبيق النموذجية

  1. Substation Feeder Protection in Chemical Park

Objective: Protect 10kV feeders against equipment damage and power outage caused by overcurrent & earth faults

المزايا: Wide voltage adaptability; 8 programmable outputs for complex trip logic; dual-port communication for remote monitoring

System Configuration: P127BA0V6D3FE0 + 10kV Vacuum Circuit Breaker + SCADA System

Effect: Fault response <30آنسة; power outage duration reduced by 40%; power supply reliability improved

  1. Motor Protection Scheme for Automotive Factory

Objective: Protect large stamping line motors against overload and earth faults

المزايا: Directional protection for fault location discrimination; auto-reclosing reduces transient fault impact; event recording facilitates fault analysis

System Configuration: P127BA0V6D3FE0 + مركز عملائي + Industrial Ethernet

Effect: Motor failure rate reduced by 25%; production line efficiency increased by 18%

Not Recommended Scenarios

High voltage system (>35كيلو فولت): Use MiCOM P40 or higher series

UHVDC system: Not applicable; dedicated DC protection relay required

Strong electromagnetic interference environment: Additional electromagnetic shielding required to avoid measurement deviation

Underwater / Humid outdoor environment: IP50 only suitable for indoor dry locations; outdoor installation requires protective enclosure

  1. تثبيت & Wiring Guidelines

متطلبات التثبيت

  1. نوع التركيب: Flush mounting; panel cutout 138×138mm, front panel 144×144mm
  2. موقف التثبيت: Install inside control cabinet, avoid direct sunlight and high heat source; reserve ≥50mm clearance for heat dissipation
  3. Wiring Standard: Current loop ≥2.5mm² copper cable; voltage loop ≥1.5mm² copper cable; separate routing ≥100mm between current and voltage wires
  4. Earthing: Device earth terminal must be reliably connected; earth resistance ≤1Ω linked to station earthing grid
  5. Communication Wiring: RS485 uses shielded twisted pair; single-end shielding grounding; max communication distance 1200m

Core Terminal Definition

رقم المحطة.وظيفةيكتبملاحظات
L1/L2/L3Phase Current Input5A/1AConnect CT secondary, pay attention to polarity
INEarth Current Input1أ (النوع ب)Connect residual CT secondary
UA/UB/UC/UNVoltage Input57-130VConnect PT secondary; phase/line voltage optional
DC+/DC-مزود الطاقة24-250في العاصمة / 48-240الخامس وWide voltage with reverse polarity protection
RL1-RL8تتابع الإخراجلا/NC اختياريRL1 master trip linked with trip indicator
COM1/COM2Communication PortRS232/RS485COM1 front port; COM2 rear port

Commissioning Key Points

  1. Parameter Configuration: Use MiCOM S1 Studio via RS232 to set CT/PT ratio, protection settings and communication parameters
  2. Setting Group Selection: 8 setting groups switchable for different operation modes; Group 1 as default
  3. Protection Function Test: Simulate phase overcurrent & earth overcurrent to verify action accuracy and response time
  4. Communication Test: Verify Modbus / IEC60870-5-103 / DNP3.0 data transmission
  5. Event Record Check: Confirm complete event & fault waveform records after fault triggering
  6. Selection Rules & مرجع سريع

Selection Mnemonic

Schneider P127 relay, full 3-phase earth protection,

Type B 1A earth input, V6 voltage 57-130V option,

D3 dual-port communication, FE0 with 8 relay operation,

24-250V wide power range, IP50 high protection graduation,

Order by P127BA0V6D3FE0, ideal for feeder station application.

Quick Selection Rules

  1. Current Input: A=5A standard CT; B=1A high precision; C=0.1A high-sensitivity earthing
  2. Voltage Module: V6=57-130V for PT secondary; Z1=24-60V for low voltage supply
  3. تواصل: D3=dual-port local+remote; D1=single-port cost saving
  4. الإخراج: FE0=8 relays standard; GE0=12 relays extended control
  5. وظيفة خاصة: لاحقة “1” supports IRIG-B time synchronization
  6. طلب: Feeder=standard; Motor=with directional; Transformer=with cold load pickup
  7. Air Freight Compliance & الشهادات

Air Freight Compliance: No lithium battery / supercapacitor. Built-in electromagnetic components, compliant with IATA DGR Class 9 non-restricted goods, shippable as general cargo.

الشهادات:

م: اللجنة الانتخابية المستقلة 60255, في 61010

أول: أول 1053 Power Protection Standard

وكالة الفضاء الكندية: Canadian electrical safety approval

اللجنة الانتخابية المستقلة 60255 Functional Safety certified by TÜV Rheinland

RoHS: EU RoHS compliant, free of hazardous heavy metals

Environmental Compliance: REACH regulation compliant

  1. شراء & Logistics Info
غرضتفاصيل
MOQ1 وحدة
Lead Timeمعيار 8-10 أسابيع; Express 3-5 أسابيع
التعبئة والتغليفIndividual carton with manual, software CD and communication cable
ضمان12 months after commissioning acceptance
Recommended SparesSame model relay, relay output module, وحدة الاتصالات
Matching AccessoriesMiCOM S1 Studio, CT/PT, قاطع الدائرة, communication switch

Schneider MiCOM Protection Relay Full Series List (Structured Version)

Schneider MiCOM protection relays consist of 8 platform series: Px10 / Px20 / Px30 / Px40 / Px60 / Px70 / Px80 / Px90. Covers feeder / محرك / محول / generator / busbar / line distance / differential protection. يدعم مودبوس / IEC60870-5-103 / DNP3.0. Applicable from medium-low voltage up to EHV power systems. Part number rule: PXXX[Function Code][Module Code].

  1. Naming Rule Definition
شريحةمعنىمثال
صProtection Relay identifierص
XXXكود السلسلة:P127 (Feeder), P241 (محرك)
P1xx: Feeder Protection
P2xx: محرك & Rotating Machine
P3xx: Generator
P4xx: Line Distance
P6xx: Differential (Transformer/Motor/Busbar)
P7xx: Busbar Protection
P8xx: Circuit Breaker Failure
P9xx: Voltage/Frequency Control
Function CodeSpecial function:B=1A Earth; A1=IRIG-B
A/B/C: Earth current 5A/1A/0.1A
A0/A1: معيار / with IRIG-B
Module CodeFunctional module:V6, D3, FE0
V6/Z1: 57-130V / 24-60V
D1/D3/D5: Single/Dual-port/Ethernet
FE0/GE0/HE0: 8/12/16 المرحلات
Full Part No.Global unique codeP127BA0V6D3FE0
  1. Series Classification by Application

2.1 Feeder Protection (P1xx)

مسلسلنموذجالوظيفة الأساسيةCurrent InputVoltage ModuleComm.الإخراجTypical Part No.
Px10 BasicP111/P115/P116التيار الزائد + Earth Fault, تعمل بالطاقة الذاتية5A/1ANone/OptionalNone/D14-6رP111A00V0D0FE0
Px20 StandardP121/P122/P1273-stage O/C + 2-stage Earth + Direction + Auto-reclose5A/1A/0.1AV6/Z1D1/D3FE0/GE0P127BA0V6D3FE0
Px30 AdvancedP132/P139/P138Feeder Management + ATS + Remote I/O5A/1AV6/Z1D3/D5GE0/HE0P132AA0V6D5GE0
Px40 High-EndP141/P142/P143Full feeder protection + قياس الطاقة + Fault Recorder5A/1AV6/Z1D3/D5HE0P141CA0V6D5HE0

2.2 محرك & Rotating Machine (P2xx)

مسلسلنموذجالوظيفة الأساسيةMotor Typeوظيفة خاصةرقم الجزء. مثال
Px20P211Motor Monitoring + الزائد + Locked Rotor + خسارة المرحلةLV Motorمراقبة درجة الحرارةP211A00V0D0FE0
Px40P241/P242/P243Integrated Motor Protection + Start Control + تشخيص الخطأMV/HV MotorPositive/Negative Sequence + Thermal ModelP242AA0V6D3GE0
خاصP244Synchronous Motor Protection + Excitation ControlSynchronous MotorOut-of-step + Excitation MonitoringP244BA0V6D3GE0

2.3 Transformer Protection (P6xx)

مسلسلنموذجالوظيفة الأساسيةTransformer TypeDifferential Typeرقم الجزء. مثال
Px30P631/P632/P633Transformer Differential + O/C + Earth + درجة حرارة2-لف / 3-لفRatio DifferentialP632AA0V6D3GE0
Px40P635/P636/P637Advanced Transformer Protection + Winding Temp + BuchholzPower TransformerHarmonic Restraint Ratio DifferentialP635BA0V6D5HE0
RailwayP638Railway OHL Differential ProtectionTraction TransformerFast Differential + DirectionalP638CA0V6D3GE0

2.4 Generator Protection (P3xx)

2.5 Line Distance Protection (P4xx)

2.6 Busbar Protection (P7xx)

2.7 Special Function Series