Siemens VVF53.25 Flanged Globe Valve

Siemens ACVATIX™ long-stroke 2-way flanged globe valve, DN25 nominal diameter, PN25 pressure rating. Suitable for media temperature range -20~220°C. Matched with SAX/SKD/SKB/SKC series actuators. Applied to fluid control such as steam, hot water and thermal oil. Typical model: VVF53.25-10 (Kvs=10m³/h). Order numbers start with S55208. Model Segment Definition Model Segment Description VVF Product type: كهربائي ...

  • تفاصيل المنتج

Siemens ACVATIX™ long-stroke 2-way flanged globe valve, DN25 nominal diameter, PN25 pressure rating. Suitable for media temperature range -20~220°C. Matched with SAX/SKD/SKB/SKC series actuators. Applied to fluid control such as steam, hot water and thermal oil. Typical model: VVF53.25-10 (Kvs=10m³/h). Order numbers start with S55208.

  1. تعريف الجزء النموذجي
الجزء النموذجيوصف
VVFProduct type: Electric 2-way Flanged Globe Valve
53رمز السلسلة: ACVATIX™ long-stroke series, suitable for medium and high pressure working conditions
25Nominal diameter: DN25 (25مم)
-XFlow coefficient: Kvs value; على سبيل المثال. -6.3/-8/-10 stands for Kvs=6.3/8/10m³/h
High differential pressure version: Reinforced valve body for higher differential pressure conditions
-JCSpecial material version: Stainless steel internal parts for corrosive media
S55208-VxxxSiemens official order number, globally unique identifier
  1. Full Version Core Specification Table
فئة المعلمةSpecific Parameterملاحظات
المعلومات الأساسية2-way flanged globe valve, ACVATIX™ long-stroke series, PN25 pressure ratingCompliant with ISO 7005 flange standard
Typical ModelsVVF53.25-6.3 / VVF53.25-8 / VVF53.25-10Corresponding Kvs=6.3/8/10m³/h
رقم الطلب. أمثلةS55208-V118 (6.3) / S55208-V119 (8) / S55208-V120 (10)Different Kvs correspond to different order numbers
أبعادDN25, flanged connection, stroke 20mmValve body length 160mm, الوزن تقريبا. 5كجم
Rated PressurePN25 (25حاجِز)الأعلى. working pressure 2500kPa
Media Temperature-20°C ~ +220°CValve stem seal replacement required for low temperature below -5°C
Valve Body MaterialDuctile Iron EN-GJS-400-18-LTCorrosion resistant, قوة عالية, مثالية للبيئات الصناعية
Internal Parts MaterialSeat / Plug: الفولاذ المقاوم للصدأ (1.4408/1.4571)Wear and high temperature resistant, عمر خدمة ممتد
Flow CharacteristicEqual percentageHigh regulating accuracy, suitable for wide flow range control
Leakage ClassClass IV (ANSI B16.104)Leakage ≤0.01%×Kvs, excellent sealing performance
نوع الاتصالFlanged (ايزو 7005-2)Standard DN25 flange size, تركيب سهل
Compatible ActuatorsSAX61.03 (كهربائي), SKD60/SKB62/SKC62 (Electro-hydraulic)Adapt to different torque and control requirements
شهادات السلامةم, أول, وكالة الفضاء الكندية, اتيكسMeets safety and explosion-proof requirements of global major markets
خدمة الحياةMechanical life ≥10⁵ cyclesLong-term stable operation under regular maintenance
  1. Full Series Model List (VVF53 2-Way Flanged Globe Valve)
Nominal Diameter (DN)نموذجKvs Value m³/hسكتة دماغية (مم)Special Versionرقم الطلب. بادئة
25VVF53.25-5520معيارS55208-V117
25VVF53.25-6.36.320معيارS55208-V118
25VVF53.25-8820معيارS55208-V119
25VVF53.25-101020معيارS55208-V120
25VVF53.25-10K1020High Differential PressureS55208-V120-K
25VVF53.25-6.3JC6.320Stainless Steel Internal PartsS55208-V183-A110
15VVF53.15-0.16~40.16~416معيارS55208-Vxxx
20VVF53.20-6.36.316معيارS55208-Vxxx
32VVF53.32-161620معيارS55208-Vxxx
40VVF53.40-252520معيارS55208-Vxxx
50VVF53.50-404025معيار / High Differential PressureS55208-Vxxx
65VVF53.65-636325معيار / High Differential PressureS55208-Vxxx
80VVF53.80-10010030معيار / High Differential PressureS55208-Vxxx
100VVF53.100-16016030معيار / High Differential PressureS55208-Vxxx
  1. منافس / Obsolete Model Replacement List

4.1 Same Brand Alternative Models (Directly Compatible)

النموذج الأصلينموذج الاستبدالReplacement Descriptionسيناريو التطبيق
VVF53.25-10VVF53.25-10KUpgraded high differential pressure version with reinforced valve bodyWorking conditions with differential pressure>10bar
VVF53.25-10VVF53.25-10JCUpgraded stainless steel internal parts with improved corrosion resistanceCorrosive media such as salt water and weak acid
VVF53.25-10VXF53.25-103-way version for diverting / mixing flow controlSystems requiring fluid mixing or splitting
VVF53.25-10VVF43.25-10Short-stroke series with more compact structureLimited installation space scenarios

4.2 Cross-Brand Equivalent Models

Siemens ModelHoneywell ModelDanfoss ModelJohnson Controls Modelالاختلافات الرئيسية
VVF53.25-10V5011P2010VFG25.100VG1205APSiemens ACVATIX™long-stroke design provides higher regulating accuracy
Honeywell lower price; Danfoss faster response
Siemens supports more actuator types and easier maintenance
Johnson Controls higher integration, ideal for BMS
  1. بيئة التطبيق & Industry Cases

Recommended Application Scenarios (★★★★★)

HVAC System: Temperature control for central air conditioning water systems in commercial buildings, hotels and hospitals

Industrial Steam System: Steam heating and humidification control in textile, food and pharmaceutical industries

District Heating: Secondary side temperature regulation for urban heating pipe networks

Refrigeration System: Flow control for chillers and cooling towers

Industrial Fluid Control: Regulation of process fluids (hot water, thermal oil, condensate) in chemical and power industries

الطاقة المتجددة: Heat exchange control for solar energy and ground source heat pump systems

حالات التطبيق النموذجية

  1. Steam Sterilization System in Food Processing Plant

Application Target: Precisely control steam flow to keep sterilization temperature stable at 121°C

Core Advantage: Equal percentage flow characteristic adapts to wide range flow regulation; PN25 rating withstands steam pressure fluctuation

System Configuration: VVF53.25-10 + SKD62 electro-hydraulic actuator + S7-1200 PLC control

Operation Effect: Temperature control accuracy ±0.5°C, sterilization efficiency +20%, energy consumption -15%

  1. Central Air Conditioning System of Commercial Complex

Application Target: Regulate chilled water flow to realize independent temperature control in different zones

Core Advantage: Compatible with SAX61.03 electric actuator with fast response; flanged design for easy installation and maintenance

System Configuration: VVF53.25-8 + SAX61.03 actuator + room thermostat + building management system

Operation Effect: Room temperature accuracy ±1°C, improved comfort, system energy consumption -18%

Not Recommended Scenarios (★☆☆☆☆)

High differential pressure>16bar: Adopt VVF53K high differential pressure version

Strongly corrosive media such as strong acid and alkali: Select special alloy valves

Temperature over 220°C or below -20°C: Beyond nominal range, sealing performance declines

Media containing solid particles: Easy seat wear and increased leakage

Vacuum system: Not applicable; dedicated vacuum valve required

  1. تثبيت & Wiring Guidelines (Engineering Essential)

Installation Regulations

  1. Mounting Direction: Vertical installation with actuator upward; horizontal installation must keep actuator shaft horizontal
  2. Flow Direction: Install strictly according to valve body arrow; reverse installation not allowed
  3. Pipeline Preparation: Flush pipelines thoroughly before installation; 100μm filter is recommended
  4. Flange Connection: Use ISO 7005 standard flanges; fasten bolts evenly to avoid valve body deformation
  5. العزل: Insulate valve body for high temperature media to reduce heat loss and prevent scalding
  6. Maintenance Space: Reserve ≥200mm clearance around valve for actuator disassembly and servicing

Actuator Wiring Diagram (SAX61.03 Example)

1 2 3 4 5 6 7 8

┌─────────────────────┐

│ │

│ SAX61.03 Actuator │

│ │

└─────────────────────┘

رقم المحطة.وظيفةWiring Description
1-2مزود الطاقة24الخامس التيار المتناوب/تيار مستمر, 1=Positive, 2=Negative
3-4إشارة التحكم0-10V DC or 4-20mA, 3=Signal+, 4=Signal-
5-6Feedback Signal0-10في العاصمة, 5=Feedback+, 6=Feedback-
7-8تبديل الحدNO/NC optional for status indication

Commissioning Key Points

  1. Stroke Calibration: Perform automatic stroke calibration after power-on to ensure full open / full closed position accuracy
  2. Flow Test: Verify linear relationship between control signal and flow via PLC output
  3. Leakage Inspection: Check closed valve leakage complies with Class IV standard
  4. وقت الاستجابة: Test full travel response time to meet system control requirements
  5. Alarm Configuration: Set actuator fault alarms (over torque, power failure) for system monitoring
  6. Selection Mnemonic & Quick Rules

Selection Mnemonic

Siemens 2-way VVF53,

DN25 size PN25 rated,

Long-stroke high precision guaranteed,

Equal percentage flow graded,

Fit steam and hot water shaded,

-20 to 220°C ranged,

Kvs 6.3/8/10 selected,

SAX/SKD actuators matched,

K version for high pressure dated,

JC for corrosion related,

Order by S55208 validated,

Flanged mounting firmly stated.

Quick Selection Rules

  1. Diameter Matching: Choose DN15~DN250 by pipe size; DN25 corresponds to VVF53.25
  2. Kvs Calculation: Calculate required Kvs via formula \(Kvs=Q\times\sqrt{\Delta P/\rho}\) according to system flow and differential pressure
  3. Pressure Rating: Standard for regular conditions, -K version for high differential pressure
  4. Media Temperature: Standard range -20~220°C; customized for over-limit temperature
  5. Actuator Selection: SAX electric for small torque; SKD/SKB/SKC electro-hydraulic for large torque
  6. Special Conditions: Select -JC stainless steel internal parts for corrosive media
  7. Air Freight Compliance & Certification Info (International Trade)

Air Freight Compliance: No lithium battery / super capacitor. Valve body metal construction, كهربائي / electro-hydraulic actuator. Compliant with IATA DGR Class 9 non-restricted goods, shippable as general cargo.

الشهادات:

م: Compliant with EN 12516-1, في 60730

أول: Compliant with UL 1995 industrial control standard

وكالة الفضاء الكندية: Canadian electrical safety approval

اتيكس: Suitable for potentially explosive atmosphere (actuator certified separately)

ايزو 9001: Quality management system certification

Environmental Certification: متوافق مع RoHS, free of lead, الزئبق, الكادميوم; meets REACH regulations.

  1. شراء & Inventory Information
Purchasing Itemتفاصيل
MOQ1 piece
Lead Timeمعيار 7-14 أيام العمل; Express 3-5 أيام العمل
التعبئة والتغليفIndividual carton with installation manual and flange gasket
ضمان2 years from commissioning acceptance
Recommended SparesSame model valve, seat seal kit, actuator control module
Matching ProductsSAX61.03/SKD62 actuator, flange gasket, strainer, check valve