بلك/

شنايدر RM17TG00 تسلسل المرحلة & مرحل مراقبة فقدان المرحلة

RM17: Harmony RM17 series three-phase monitoring relay TG: Monitors phase sequence and phase loss only (no voltage unbalance, overvoltage or undervoltage functions) 00: 1 الاتصال التحول (1ج/س) إصدار; RM17TG20 in the same series is the 2C/O dual-contact model ✅ Core Functions Monitors three phases L1/L2/L3: خطأ في تسلسل المرحلة (reverse phase, motor reverse rotation protection) مرحلة ...

  • تفاصيل المنتج

RM17: Harmony RM17 series three-phase monitoring relay

TG: Monitors phase sequence and phase loss only (no voltage unbalance, overvoltage or undervoltage functions)

00: 1 الاتصال التحول (1ج/س) إصدار; RM17TG20 in the same series is the 2C/O dual-contact model

✅ Core Functions

Monitors three phases L1/L2/L3:

  1. خطأ في تسلسل المرحلة (reverse phase, motor reverse rotation protection)
  2. Phase loss fault (loss of two or more phases; single-phase weak voltage drop will NOT trigger)

تعمل بالطاقة الذاتية, energized directly from L1/L2/L3, no additional auxiliary مزود الطاقة مطلوب

📋 Key Technical Specifications

غرضالمعلمة
Monitoring Voltage Range208~480 VAC (operating limit 183~528VAC)
تكرار50/60Hz ±10%
اتصالات الإخراج1ج/س (1 مفتوح عادة + 1 مغلق عادة)
تصنيف الاتصال الحالي5A @250VAC, max.1250VA
Power-up Start Delay≤650ms
Fault Response Time≤130ms
استهلاك الطاقة≤22VA @400VAC 50Hz
تصاعد35مم DIN السكك الحديدية, width 17.5mm (1 وحدة)
مؤشرYellow LED: ON under normal condition, OFF in fault state
الشهاداتم, الجهد الزائد الفئة الثالثة, IEC60255

🔌 Terminal Wiring Definition

المحطات العليا: L1, L2, L3 → Connect to three-phase power supply

Lower contact terminals:

11: شائع

14: مفتوح عادة (لا) (closed in normal state, open under fault)

12: مغلق عادة (نورث كارولاينا) (مفتوحة في الحالة الطبيعية, closed under fault)

With correct three-phase supply and proper phase sequence: relay energizes, LED ON; خسارة المرحلة / reversed phase → relay de-energizes, LED OFF

🛠️ Typical Application Scenarios

Hoisting equipment, مصاعد, conveyor lines, water pump sets, preventing motor reverse rotation

ضواغط الهواء, chiller unit three-phase power protection

Portable equipment power access detection, emergency power switching judgment

⚠️ Troubleshooting Points

  1. إيقاف تشغيل الصمام: No power on three-phase incoming lines or loose wiring;
  2. LED fails to energize after power-up: Most likely reversed phase sequence, swap any two L phases;
  3. Single-phase voltage drop will not trigger RM17TG00. TG series only detects complete phase loss and does not monitor voltage unbalance. For unbalance/overvoltage & حماية الجهد المنخفض, select RM17TE series.

🧩 Same-series Comparison & مرجع الاستبدال

RM17TG00: 1ج/س, تسلسل المرحلة + خسارة المرحلة

RM17TG20: 2C/O dual changeover contacts, تسلسل المرحلة + خسارة المرحلة

RM17TE00: With voltage unbalance, الجهد الزائد, انخفاض الجهد, phase loss and phase sequence (full-featured model)

📌 Notes

No potentiometer for threshold adjustment, fixed logic without adjustment knobs;

For three-phase 3-wire system only;

Dry contact output for PLC DI or contactor coil interlock circuit.

شنايدر RM17TG20 Troubleshooting Document

ملائم: RM17TG00 / RM17TG20 three-phase phase sequence & phase loss relay

Safety Precaution: High-voltage work must follow power cut & voltage verification. Use qualified high-voltage multimeter and wear insulated protective gear for three-phase voltage measurement.

Product Principle Review: Only monitors phase sequence and complete loss of two or more phases; single-phase voltage drop and voltage unbalance will not trigger protection. Self-powered from L1/L2/L3. الحالة الطبيعية: yellow LED ON, both contact sets energized; Fault state: yellow LED OFF, both contact sets de-energized

  1. Pre-check Preparation
  2. أدوات: المتر الرقمي, cross screwdriver, القفازات العازلة
  3. تأكيد النموذج: RM17TG20, rated monitoring voltage 208~440VAC (limit 183~484VAC), long-term operation above 440VAC is not permitted
  4. System Confirmation: Three-phase 3-wire system, no neutral wire connected; this model cannot detect single-phase drop in 3P4W system
  5. Basic Status Description: ≤650ms initialization delay after power on; fault response ≤130ms; relay stays de-energized when fault exists, auto-recovers once fault cleared
  6. Troubleshooting by Fault Symptom

أعراض 1: Yellow LED completely off after power-up, relay contacts no action

وصف: No indicator light after energizing, اتصالات 11/14 و 21/24 fail to close

  1. خارج السلطة, inspect L1/L2/L3 terminals: Check for looseness, oxidation or poor crimping; clean dust and copper oxide on terminals
  2. تشغيل الطاقة, measure line-to-line voltage L1-L2, L2-L3, L1-L3 at relay upper terminals with multimeter

Any line voltage <183V: Undervoltage on power supply, relay cannot operate; check upstream circuit breaker, fuse and cable breakage

No voltage on two or more phases: Upstream phase loss fault, repair power supply circuit

  1. LED still OFF with all three-phase voltages normal:

Check miswiring of L1/L2/L3; confirm power cables are not connected to contact terminals

Inspect module appearance: Cracked housing, burn marks or carbonized terminals → internal damage, replace relay directly

Cross test: Remove relay and connect to known good three-phase supply; if LED remains off, relay is defective

أعراض 2: Three-phase supply normal, LED stays off, relay continuously reports fault (contacts not energized)

Most frequent on-site fault: Reversed phase sequence

  1. Measure three line voltages and confirm all values between 183~484VAC with balanced three-phase voltage
  2. خارج السلطة, swap any two incoming L phases (على سبيل المثال. L1 و L3)
  3. Re-energize and observe LED:

LED ON and contacts close: Fault resolved, root cause reversed phase sequence

LED still OFF after twice phase swap: proceed to next step

  1. Check for virtual connection with induced voltage: Multimeter shows normal voltage but voltage collapses under load. TG series cannot identify weak single-phase drop, but will trigger phase loss alarm if single-phase voltage falls below 100V
  2. Still invalid: Relay internal failure, replace for test

أعراض 3: LED is ON, but no signal on output contact circuit (no PLC feedback / contactor fails to act)

Power monitoring circuit healthy, fault lies in secondary dry contact circuit

RM17TG20 has two independent changeover contact sets: 11/12/14 و 21/22/24, both act synchronously

  1. Power off and verify contact wiring:

11, 21: Common terminals

14, 24: مفتوح عادة (لا) (closed when energized; open under fault)

12, 22: مغلق عادة (نورث كارولاينا) (open when energized; closed under fault)

  1. تشغيل الطاقة (relay normal state, LED ON), measure continuity with multimeter:

11 & 14, 21 & 24: should conduct; 11 & 12, 21 & 22: should be open

  1. Manually create fault (reverse phase sequence), LED OFF:

11 & 14, 21 & 24: يفتح; 11 & 12, 21 & 22: conduct

  1. Asynchronous action between two contact sets (one closed, one open): Internal contact damage, must replace relay
  2. Contact status correct but no signal on downstream circuit: Check PLC DI module, external interlock circuit, broken secondary wiring or blown fuse

أعراض 4: Random false tripping during motor operation (LED OFF, protection trip)

  1. Monitor three-phase voltage, focus on voltage dip during motor starting:

⚠️ Important Limitation: RM17TG only detects complete loss of two phases; single-phase voltage dip will not trigger protection. Random tripping is mostly caused by instantaneous two-phase power loss or poor connection

  1. Inspect main circuit contactor, thermal relay terminals and cable lugs for loose connections, overheating and poor contact under high current
  2. Check power cables: Cable damage, earth fault or risk of phase-to-phase short circuit
  3. EMI Troubleshooting: Relay routed in parallel with power cables; relocate RM17TG away from VFDs and contactors, use separate cable trunking or shielding
  4. Confirm supply voltage does not exceed RM17TG20 upper limit 440VAC; use RM17TG00 for 480VAC application
  5. Cross replacement test: If fault disappears after installing new relay, original relay is aged and damaged

أعراض 5: Relay does not alarm with single-phase cut-off (protection no action)

This is NOT a fault, it is inherent design limitation!

RM17TG series only detects loss of ≥2 phases. Single-phase disconnection and single-phase voltage drop cannot trigger protection

If single-phase loss, voltage unbalance, الجهد الزائد & undervoltage protection required: Replace with RM17TE00 multi-function monitoring relay

ثالثا. Quick Self-check Procedure (On-site Maintenance Checklist)

✅ Step1: خارج السلطة, inspect appearance and wiring (محطات, burn marks, رخاوة)

✅ Step2: Power on and measure L1-L2 / L2-L3 / L1-L3 line-to-line voltages

✅ Step3: Observe LED status to locate fault domain (مزود الطاقة / تسلسل المرحلة / relay itself)

✅ Step4: Power off and swap two L phases to verify reversed phase sequence

✅ Step5: Power off and test continuity of two contact sets to confirm switching logic

✅ Step6: Cross replace relay to confirm whether fault comes from relay or external wiring

  1. المفاهيم الخاطئة الشائعة
  2. ❌مفهوم خاطئ: Relay should protect on single-phase loss

✅ Note: TG series only detects loss of two or more phases; single-phase breakage is not detected.

  1. ❌مفهوم خاطئ: Front panel adjustment knobs are available for threshold setting

✅ Note: RM17TG has no potentiometer, threshold fixed.

  1. ❌مفهوم خاطئ: Two contact sets can act independently

✅ Note: Two contact sets operate synchronously; asynchronous action indicates relay damage.

  1. ❌مفهوم خاطئ: Can be used in 3P4W system (with neutral wire)

✅ Note: For three-phase 3-wire only, neutral wire must NOT be connected.

  1. Replacement Criteria (Replace relay if any condition met)
  2. L1/L2/L3 supply voltage normal, LED remains OFF after phase sequence swap
  3. Two contact sets act asynchronously, contacts burnt or fail to switch
  4. Housing or terminals show black burn marks, bulging or carbonization
  5. Fault eliminated after installing new relay under same power condition
  6. Maintenance Recommendation
  7. Periodic inspection: Tighten L1/L2/L3 input terminals and contact terminals quarterly to prevent vibration-induced looseness
  8. Ambient condition: Operating temperature -20~+60℃; avoid heavy dust, humid or corrosive gas environment
  9. تنظيف: Clean module surface dust with dry brush after power cut, liquid cleaner prohibited
  10. خدمة الحياة: Mechanical life of contacts >10 مليون دورة; electrical life approx.100,000 cycles at 5A@250VAC

Schneider RM17 Series Three-phase Monitoring Relay Full List (Harmony Zelio, 35مم DIN السكك الحديدية, 17.5mm 1-module width)

All models are self-powered from L1/L2/L3, no auxiliary supply required, 5A@250VAC dry contact output, for three-phase 3-wire system

  1. RM17TG (النموذج الأساسي: تسلسل المرحلة + phase loss only, no adjustment knobs, fixed threshold)
نموذجاتصالاتنطاق الجهدالوظائف الأساسيةتطبيق نموذجي
RM17TG001ج/س (1 changeover)208~480VACخطأ في تسلسل المرحلة, ≥2 phases loss protection; No unbalance / زيادة&انخفاض الجهدSingle interlock, water pump and general motor protection
RM17TG202ج/س (2 independent changeover)208~440VACخطأ في تسلسل المرحلة, ≥2 phases loss protection; No unbalance / زيادة&انخفاض الجهدHardware interlock + PLC alarm, hoisting, elevator

TG Series Features: No potentiometer, no adjustment window on housing, only yellow status LED; Single-phase voltage drop will not trigger alarm

  1. RM17TT / مواجهة / TU / TE (Multi-function adjustable type, transparent cover with adjustment knobs)
نموذجاتصالاتنطاق الجهدوظائف المراقبة
RM17TT001ج/س208~480VACخسارة المرحلة + تسلسل المرحلة; rated voltage selectable, delay adjustable; No voltage unbalance, أكثر من / انخفاض الجهدBasic adjustable phase sequence & خسارة المرحلة, suitable for multi-voltage site
RM17TA001ج/س208~480VACخسارة المرحلة + تسلسل المرحلة + three-phase voltage unbalance; unbalance threshold & delay adjustable; No over/undervoltageMotor winding protection, detect three-phase asymmetry
RM17TU001ج/س208~480VACخسارة المرحلة + تسلسل المرحلة + undervoltage monitoring; undervoltage threshold & delay adjustable; No overvoltage, no unbalancePower supply drop monitoring, generator set, incoming power supervision
RM17TE001ج/س208~480VACوظائف كاملة: phase loss+phase sequence+voltage unbalance+overvoltage+undervoltage, multiple potentiometers adjustable, true RMS measurementمبرد, ضاغط الهواء, UPS switching, full protection requirement

ثالثا. RM17 Series Single-phase / DC Voltage Monitoring (نفس السلسلة, non three-phase)

نموذجيكتبMonitoring Rangeاتصالات
RM17UAS14الجهد المستمر9~15VDC1ج/س
RM17UAS16التيار المتناوب/تيار مستمر عالمي20~80V AC/DC1ج/س
RM17UAS15التيار المتناوب/تيار مستمر عالمي65~260V AC/DC1ج/س
RM17UBE SeriesSingle-phase AC Over & انخفاض الجهد24~240VAC1ج/س
RM17UB310Single-phase Voltage Monitoring200~240VAC1ج/س
  1. Model Suffix Coding Definition (RM17Txx00)

TG: النوع الأساسي, fixed threshold, no adjustment knob, تسلسل المرحلة + خسارة المرحلة

تي تي: Adjustable basic model, تسلسل المرحلة + خسارة المرحلة, voltage range selectable

مواجهة: ت + Asymmetry voltage unbalance detection

TU: ت + Undervoltage monitoring

TE: Total full functions (تسلسل المرحلة, خسارة المرحلة, unbalance, الجهد الزائد, انخفاض الجهد)

00: 1C/O output

20: 2C/O dual independent changeover contacts (only available for TG series)

  1. جدول الاختيار السريع (Three-phase models)
متطلباتالنموذج الموصى به
Only phase sequence+phase loss, single contact output, 480V applicationRM17TG00
Phase sequence+phase loss, dual independent dry contacts for interlock + إنذارRM17TG20
Phase loss+phase sequence, multi-voltage option, delay requiredRM17TT00
Phase loss+phase sequence+three-phase unbalance (motor asymmetry protection)RM17TA00
Phase loss+phase sequence+undervoltage monitoringRM17TU00
الحماية الكاملة: phase loss+phase sequence+unbalance+overvoltage+undervoltageRM17TE00
  1. Common General Specifications
  2. تصاعد: 35مم DIN السكك الحديدية, 1 وحدة (17.5مم);
  3. Output Logic: Relay energized (power normal) → contacts closed; fault → contacts open (fail-safe type);
  4. مزود الطاقة: Self-powered directly from L1/L2/L3, no neutral wire, three-phase 3-wire system only;
  5. وقت الاستجابة: TG fixed ≤130ms; TT/TA/TU/TE fault delay manually adjustable;
  6. تقييم الاتصال: 5A 250VAC resistive load; for PLC DI and contactor interlock circuit, not for direct driving of high-power loads

سابعا. استبدال & Upgrade Reference

RM17TG00 ↔ RM17TG20: identical function, only contact quantity differs

RM17TT00 → RM17TA00: add voltage unbalance detection

RM17TA00 → RM17TE00: add overvoltage and undervoltage window monitoring

Legacy RM22TG series is substitute series (نفس الوظيفة, different form factor)