RS485 PROFIBUS 9-pin Sub-D bus plug, 90° vertical outlet, with PG programming port, built-in disconnectable terminating resistor. Suitable for DP/MPI stations such as S7-300/400 and ET200M, العاكسون.
✅ Key Specifications
Communication rate: ما يصل الى 12 ميغابت/ثانية
منفذ الكابل: 90° (vertical downward)
إعدادات: with PG programming socket (programming cable can be plugged in online without disconnecting the bus)
Terminating resistor: built-in with toggle switch (ON/OFF, معزول)
أبعاد: 15.8 × 64 × 35.6 مم (العرض × الارتفاع × العمق)
Bus standard: بروفيبوس موانئ دبي / MPI (MPI network compatible)
حالة المنتج: PM300 active product, صنع في ألمانيا, متوافق مع RoHS
سمات: pure hardware connector, no configuration required in TIA Portal / STEP7, التوصيل والتشغيل
📌 Model Comparison for Selection
| رقم الطلب. | Outlet Angle | PG Port |
| 6ES7972-0BB12-0XA0 | 90° عمودي | ✅ With PG port (هذا النموذج) |
| 6ES7972-0BA12-0XA0 | 90° عمودي | ❌ Without PG port |
| 6ES7972-0BB42-0XA0 | 35° angled outlet | ✅ With PG port |
| 6ES7972-0BA42-0XA0 | 35° angled outlet | ❌ Without PG port |
لاحقة 12 = updated optimized version; older 11 series is gradually phased out
🛠️ Typical Application
- MPI/DP interface of S7-300 CPU, IM153 interface module, ET200M slave stations
- Inverters (MM440, G120 old DP board), DP instruments, الإدخال/الإخراج عن بعد
- Field commissioning: reserved PG port for PLC online monitoring, program upload and download without interrupting the bus network
- Start and end nodes of the bus: switch to ON to enable terminating resistor; switch to OFF for intermediate stations
⚠️ التثبيت & Troubleshooting Notes
- الأسلاك: A/B lines must be connected correspondingly, A to A, ب إلى ب. Communication fails directly if reversed. سيمنز DP bus cable 6XV1830-0EH10 is recommended.
- Terminating resistor rule: Only the first and last connectors on the entire DP bus shall activate terminating resistors; all intermediate stations must turn them off, otherwise packet loss and intermittent communication failure occur.
- Clarification: It is only a physical connector, not a protocol converter. MPI cannot be directly converted to Modbus RTU.
- البدائل المحلية: Compatible DP plugs (90° with PG) are available on the market. ل 12 Mbit/s high-speed and heavy interference environments, original parts are preferred.
🌡️ Special Wide-temperature Version
SIPLUS anti-corrosion wide-temperature model: 6AG1972-0BB12-2XA0, -25~+70℃ with anti-corrosion coating, suitable for outdoor and corrosive environments.
Application Scenarios of 6ES7972-0BB12-0XA0 (90° Outlet DP Bus Connector with PG Programming Port)
الميزة الأساسية: Built-in PG debug port, programming adapter can be connected for online monitoring and downloading without removing the bus cable. Preferred for stations requiring frequent commissioning. Supports PROFIBUS DP / MPI up to 12 ميغابت في الثانية, 90° vertical outlet saves cabinet space for compact wiring.
- Compatible Hardware Stations
- S7-300 PLC (CPU315-2DP, 313-2DP etc., onboard DP/MPI port) – most widely used
- S7-400 PLC, CP443-5 DP communication module
- S7-200 (with DP expansion EM277)
- ET200 series remote I/O: ET200M, ET200S, ET200B, ET200L (IM153-1/2/4 interface module)
- Siemens DP inverters: MM440, MM420, legacy G120 DP option board, 6SE70 DC drives
- Third-party PROFIBUS DP slaves: DP instruments, weighing modules, جزر الصمام, encoders, أجهزة التحكم في درجة الحرارة, DP servo drives of other brands
- Network Function Scenarios
- DP bus master station (highly recommended for this model)
Located at the PLC master station, used for frequent commissioning, upload/download and online diagnosis. USB-MPI/DP adapter can be plugged into the PG port without breaking the bus, this is its mainstream application.
- Start and end terminating nodes of DP bus
Terminating resistor toggled ON for connectors at both ends of the bus. If the master station sits at the end, the PG-equipped version is preferred.
- MPI network communication
MPI communication between S7-300 and legacy HMI such as MP277 / TP170. This connector can be fitted on CPU or HMI side to reserve a debug port.
- Compact wiring inside control cabinet
90° downward cable routing along cabinet base plate. Compared with 35° angled outlet, it fits densely arranged backplanes with limited cabinet space.
For intermediate stations with rare maintenance, select 6ES7972-0BA12-0XA0 without PG port to reduce cost.
ثالثا. تطبيقات الصناعة
أدوات الآلة: مخارط CNC, مراكز التصنيع, gantry machines (legacy 840D/810D PROFIBUS networks)
التعبئة والتغليف, textile and printing production lines
معالجة المياه, التدفئة والتهوية وتكييف الهواء, air handling units, محطات الضخ
ممحاة & plastic extruders, آلات صب الحقن
الرافعات, أنظمة النقل, المستودعات الآلية
Power plant, علم المعادن, petrochemical retrofitting & maintenance of legacy DP systems
- Not Suitable Scenarios (Pitfall Reminder)
- Not a protocol converter, DP/MPI cannot be directly converted to Modbus RTU
- Not applicable for PROFINET (PN Ethernet)
- في الهواء الطلق, corrosive and ultra-wide temperature (below -25℃) environments: use SIPLUS version 6AG1972-0BB12-2XA0
- FastConnect stripping cable: this model does not support FC quick terminals; dedicated FC models are required
PROFIBUS DP Wiring Specification + Terminating Resistor Setting + Communication Troubleshooting Checklist
For 6ES7972-0BB12-0XA0 / 6ES7972-0BA12-0XA0 standard Sub-D DP connectors
Recommended cable: 6XV1830-0EH10 standard purple DP cable (shielded twisted pair with copper conductor)
- مواصفات الأسلاك
- Bus Topology Rule (DP only permits bus topology; star and tree topology forbidden)
✅ Valid: All stations connected in series on one main cable with two terminators at both ends
❌ Prohibited: Short branches, T-taps, star junction boxes (causes unstable communication)
If branches are mandatory, DP repeater (6ES7972-0AA01-0XA0) must be used
- معدل الباود & Max Cable Length (single segment without repeater)
| معدل الباود | Max Cable Length |
| 9.6 kbit/s | 1200 م |
| 19.2 kbit/s | 1000 م |
| 187.5 kbit/s | 500 م |
| 500 kbit/s | 200 م |
| 1.5 ميغابت/ثانية | 100 م |
| 3 ميغابت/ثانية / 6 ميغابت/ثانية / 12 ميغابت/ثانية | 100 م |
Repeater: Each repeater extends one segment and isolates signals; الحد الأقصى 9 repeaters cascaded
- التدريع & Earthing (root cause of most faults)
- The outer metal shield of DP cable shall be crimped to the metal shell of the connector. Do not strip a separate wire from shield for PE connection.
- Metal shell of all DP connectors connected to cabinet PE protective earth (equipotential bonding)
- Power cables (العاكس, motor power lines) and DP signal cables shall be routed separately, minimum spacing ≥20 cm. Cross at 90° if unavoidable.
- Line reactors and filters shall be installed for variable frequency motors and high-power contactor circuits to suppress interference.
- Avoid multi-point earthing of shield and cross-cabinet wiring with large potential difference, which creates ground loop and intermittent communication dropouts.
- تعريف الدبوس (9-pin Sub-D, DP standard)
دبوس 3: B line (أخضر)
دبوس 8: A line (أحمر)
✅ Mnemonic: Red=A, Green=B. A to A, ب إلى ب, consistent across the whole bus. A/B crossover causes communication failure.
A and B are differential signals inside the connector. Reversed wiring leads to no slave station found without short-circuit alarm.
- مَنفَذ & تثبيت
90° models (0BB12/0BA12): suitable for horizontally arranged backplanes inside cabinet, cable routed downward
35° angled outlet (0BB42/0BA42): suitable for cables entering from cabinet side
Avoid sharp bending of DP cable; نصف قطر الانحناء ≥ 8 × cable diameter
Do not bundle DP cables together with servo power cables in the same trunking
- Terminating Resistor Setting (شديد الأهمية)
Side toggle switch on connector: ON = terminating resistor activated; OFF = deactivated
✅ Standard rule:
Only the very first and last stations on one DP bus shall toggle ON; all intermediate stations must stay OFF!
Master station at bus end: master connector ON, last slave connector ON, others OFF
Master station located in the middle of bus: master connector OFF, connectors at two remote ends ON
Common mistakes:
① No terminator activated at both ends → signal reflection, packet loss, intermittent failure, worse at high speed
② Multiple nodes with terminator ON → excessive bus load, unstable communication and slave failure alarms
③ Only one end terminator ON → signal reflection, sporadic faults
ملحوظة: The PG port on 6ES7972-0BB12-0XA0 does not carry built-in terminator. The PG adapter itself has no terminating resistor, it is only for commissioning.
ثالثا. DP Communication Troubleshooting Checklist (follow sequence for high efficiency)
خطوة 1: Visual Hardware Inspection (أولوية)
- Check A/B wiring for reverse connection, loose contact, stray copper wire short circuit
- Verify terminating resistor switches, confirm only two ends are ON
- Check DP cable for damage, compression, heat exposure from power equipment
- Confirm shield is reliably crimped and connector shell is well earthed
- Check Sub-D connector is fully locked and not loose
خطوة 2: PLC Diagnosis (STEP7 / TIA Portal)
- Online check CPU diagnostic buffer:
عيب: Station failure: usually cable issue, terminator setting, interference or slave power loss
عيب: Frame error, checksum error, synchronization error: mostly loose A/B contact, interference or baud rate mismatch
- تكوين الأجهزة: baud rate of master and all slaves must be identical, cannot mix 1.5M and 500K
- No duplicate DP addresses. DP address range: 0~126. Master is usually address 2; duplicate addresses are forbidden.
خطوة 3: Segmentation Isolation Method (for hard-to-locate intermittent faults)
- Split the bus into two segments and test separately to locate faulty section
- Remove slaves one by one starting from the last station to find the faulty node
- Suspected interference: replace with short DP cable temporarily and keep away from inverters and contactors
- Suspected connector failure: replace DP plug directly (many faults come from aged spring contacts inside)
خطوة 4: Frequent Pit Summary
- Ordinary 2-core shielded cable substituted for Siemens dedicated DP cable → impedance mismatch, unstable communication at high speed
- Large ground potential difference, ground loop formed by shield earthing → slow intermittent dropout
- Excessive bus length with baud rate set too high, exceeding length limit
- Unstable 24V supply and large voltage drop for old EM277, IM153 modules
- Ungrounded inverters and servos inject high-frequency interference into DP bus
- Pulling PG adapter during commissioning loosens bus connector and causes poor contact
خطوة 5: الأدوات المساعدة
DP bus tester: measure terminal impedance. When both ends are enabled, bus impedance is approximately 110 أوه. Readings other than 110 Ω at intermediate nodes are normal.
Online diagnosis table: observe cyclic loss and recovery of slaves. Periodic dropout is mostly interference or terminator problem.
- Quick Commissioning Tips (for 0BB12 with PG port)
- USB-DP adapter plugged into PG port during commissioning, no removal of original DP bus required, no impact on the whole network
- Prefer 0BB12 if master station is at the end for convenient maintenance later
- Select 0BA12 (without PG) for intermediate stations with minimal maintenance to save cost
- Fault Quick Reference Table
| أعراض | السبب المحتمل |
| All slaves cannot be detected | A/B reversed on master connector, terminators disabled at both ends, master DP port damaged |
| One slave drops randomly, others normal | Loose connector of this station, unstable power supply of this slave, faulty slave module |
| Communication drops after running, recovers after cooling | Inverter interference, heat-affected cable, thermal contact degradation of connector |
| Works at 9.6K baud rate, frequent dropout at 1.5M | Overlength cable, عدم تطابق المعاوقة, wrong terminator setting, heavy interference |
- 6ES7972 Full Series PROFIBUS Bus Connectors (DP/MPI Plugs)
قاعدة ترميز النموذج
بادئة: 6ES7972 (standard DP connector); 6AG1972 (SIPLUS wide-temperature anti-corrosion version)
5الحرف ال: B = with PG programming port; A = without PG programming port
6th~7th digits: outlet angle & نوع الأسلاك
12: 90° vertical outlet, محطة المسمار (النوع القياسي)
42: 35° angled outlet, محطة المسمار
52: 90° vertical outlet, FastConnect quick stripping type
60/61: 35° angled outlet, FastConnect quick plug
لاحقة: 0XA0 (standard industrial grade)
- Standard Industrial Versions (6ES7972, IP20, 0~+60 درجة مئوية)
1) 90° Vertical Outlet (downward routing in cabinet, flagship model)
Screw Wiring (not compatible with FC cable)
- 6ES7972-0BB12-0XA0|90°, with PG port (هذا النموذج, preferred for master station)
- 6ES7972-0BA12-0XA0|90°, without PG port (cost-effective for intermediate slaves)
FastConnect Quick Plug (no stripping required for FC purple cable)
- 6ES7972-0BB52-0XA0|90°, with PG port, FC quick plug
- 6ES7972-0BA52-0XA0|90°, without PG port, FC quick plug
2) 35° Angled Outlet (cable entering from cabinet side)
Screw Wiring
- 6ES7972-0BB42-0XA0|35°, with PG port
- 6ES7972-0BA42-0XA0|35°, without PG port
FastConnect Quick Plug
- 6ES7972-0BB60-0XA0|35°, with PG port, FC quick plug
- 6ES7972-0BA60-0XA0|35°, without PG port, FC quick plug
3) 180° Straight Outlet (axial outlet, for OLM fiber module)
- 6ES7972-0BB00-0XA0|straight outlet, with PG
- 6ES7972-0BA00-0XA0|straight outlet, without PG
4) Matching Active Terminating Resistor (for bus end)
- 6ES7972-0DA00-0AA0|active terminator, improves signal for high-speed long-distance communication
ثالثا. SIPLUS Wide-temperature Anti-corrosion Series (6AG1972, harsh & outdoor environments)
نطاق درجة الحرارة: -40درجه مئوية ~ +70 درجه مئوية, طلاء مضاد للتآكل, for HVAC, metallurgy and outdoor equipment
- 6AG1972-0BB70-7XA0 (90° with PG, equivalent to 0BB12)
- 6AG1972-0BA70-7XA0 (90° without PG, equivalent to 0BA12)
- Selection Reference Table
| Routing Type | نوع الأسلاك | With PG Port (Master Station) | Without PG Port (Intermediate Slave) |
| 90° downward (common cabinet layout) | محطة المسمار | 6ES7972-0BB12-0XA0 | 6ES7972-0BA12-0XA0 |
| 90° downward | FC quick plug | 6ES7972-0BB52-0XA0 | 6ES7972-0BA52-0XA0 |
| 35° side entry | محطة المسمار | 6ES7972-0BB42-0XA0 | 6ES7972-0BA42-0XA0 |
| 35° side entry | FC quick plug | 6ES7972-0BB60-0XA0 | 6ES7972-0BA60-0XA0 |
- Related Accessories
- PROFIBUS standard cable: 6XV1830-0EH10 (purple DP cable)
- DP repeater: 6ES7972-0AA01-0XA0 (extend segment, isolate interference)
- OLM fiber link module: convert electrical DP to optical fiber for long-distance and heavy interference applications
Master station & frequent commissioning → BB (with PG); intermediate stations with rare maintenance → BA (without PG)
Ordinary wiring & standard DP cable → 12/42 (نوع المسمار); FC fast cable used → 52/60 (FC quick plug)
Backplane downward routing in cabinet → 90° (12/52); side cable entry → 35° (42/60)