Siemens MXG461.20-5.0 Solenoid Modulating Valve

This is a 3-way/2-way solenoid proportional modulating valve with DN20 (3/4″) threaded connection and a Kvs value of 5.0 م³/ساعة. It operates on 24V AC/DC power supply, with selectable control signals: 0-10الخامس / 2-10الخامس / 4-20أماه. It features a positioning time of less than 2 ثواني, a resolution of 1:1000 and an IP54 protection rating. ...

  • تفاصيل المنتج

This is a 3-way/2-way solenoid proportional modulating valve with DN20 (3/4″) threaded connection and a Kvs value of 5.0 م³/ساعة. It operates on 24V AC/DC power supply, with selectable control signals: 0-10الخامس / 2-10الخامس / 4-20أماه. It features a positioning time of less than 2 ثواني, a resolution of 1:1000 and an IP54 protection rating. It is designed for mixing and straight flow control of cold and hot water in closed HVAC systems.

  1. شرح كود النموذج
مقطع الكودوصف
MXGرمز سلسلة المنتج: MX stands for solenoid actuator; G stands for external thread connection, suitable for cold and hot water systems
461Model type code: ACVATIX™ series solenoid control valve, PN16 pressure rating
0.2Nominal diameter DN: 20مم (3/4 بوصة)
-5Kvs flow coefficient: 5.0 م³/ساعة (flow rate of cold water at 1 bar pressure differential)
(Suffix P)Optional version: For media containing mineral oil (SAE05SAE50)
(Suffix U)Optional version: Equipped with NPT thread fitting set
  1. Main Technical Specifications
فئةتحديدملاحظات
المعلمات الأساسية
Valve TypeSwitchable 3-way mixing valve / 2-way straight valveNot applicable for diverting service
نوع الاتصالExternal thread G1¼B (ايزو 228-1)DN20 corresponds to 3/4 بوصة
Nominal PressurePN16 (1.6MPa)الأعلى. working pressure: 1000kPa
Flow CoefficientKvs=5.0 m³/h, Cv=5.9Cold water at 5-30℃, 1 bar pressure differential
Actuator Parameters
مزود الطاقةAC/DC 24V ±20% (SELV/PELV)تكرار: 45-65هرتز
إشارة التحكمDC 0/2-10V or DC 4-20mA (DIP switch selectable)Input impedance: ≥100kΩ (voltage signal), 100أوه (current signal)
Position FeedbackDC 0-10V (Load resistance >500أوه)Non-wear inductive measurement
Positioning Time< 2 ثوانياستجابة سريعة
Stroke Resolution0.736111111High regulating accuracy
فئة الحمايةIP54Dustproof and splash-proof
Valve Body Parameters
Valve Body MaterialCast iron EN-GJL-250 (GG25)Plug: CrNi steel; Seat: النحاس
مادة الختمEPDM (معيار) / FPM (Type P)For different media
درجة حرارة متوسطة1-130درجه مئويةFor cold and hot water systems
Leakage RateA→AB: ≤0.02% Kvs; B→AB: ≤0.2% KvsAt Δp=0.1MPa
موقف التركيبVertical to horizontal installation availableNo special angle restrictions
Fail-Safe FunctionPort A→AB closes automatically upon power loss (spring return)Safety protection feature
المعلمات المادية
أبعاد (L1×L2×L3×H2)95×47.5×52.5×260mmUnder straight flow status
وزن4.2كجم
  1. قائمة نماذج السلسلة الكاملة
نموذجDNKvs (م³/ساعة)نوع الاتصالApplicable Mediumملاحظات
MXG461.15-0.6150.6خيط خارجيCold & hot waterالنموذج القياسي
MXG461.15-1.5151.5خيط خارجيCold & hot waterالنموذج القياسي
MXG461.15-3.0153خيط خارجيCold & hot waterالنموذج القياسي
MXG461.20-5.0205خيط خارجيCold & hot waterCurrent model
MXG461.25-8.0258خيط خارجيCold & hot waterالنموذج القياسي
MXG461.32-123212خيط خارجيCold & hot waterالنموذج القياسي
MXG461.40-204020خيط خارجيCold & hot waterالنموذج القياسي
MXG461.50-305030خيط خارجيCold & hot waterالنموذج القياسي
MXG461.XX-XXP15-500.6-30خيط خارجيMineral oilVersion for oil media
MXG461.XX-XXU15-500.6-30خيط خارجيCold & hot waterVersion with NPT fittings
MXF461.XX-XX15-650.6-50شفةCold & hot waterFlanged version
  1. Cross-Brand & Replacement Model Reference
فئةنموذجMatching Rateالاختلافات
Siemens Equivalent ModelsMXG461.20-5.0P100%Only seal material changed to FPM, suitable for mineral oil
MXG461.20-5.0U100%Supplied with NPT thread fittings for easier installation
MXF461.20-5.095%Flanged connection type, different mounting method
البدائل المحليةMuyi MVC20-5.090%Identical functions, تقريبا. 60% of Siemens price, response time 2-3s
Chuanyi ZDLP-20K85%Electric actuator, slightly lower accuracy, IP65 rating
Imported CompetitorsHoneywell V5011P201090%Similar structure and price, positioning time around 2s
Danfoss AVTA20-5085%Slightly different flow characteristics, operating temperature 2-120℃
  1. بيئة التطبيق & حالات الصناعة

5.1 السيناريوهات القابلة للتطبيق

HVAC Systems: Cold/hot water mixing control and fan coil unit temperature regulation for commercial buildings, hotels and hospitals

District Heating: Secondary hot water temperature control for residential communities and office parks

Industrial Temperature Control: Water flow regulation for chillers and heat pumps, cooling systems for data centers

Process Cooling: Temperature control loops for plastic molding machines and printing equipment

5.2 Not Recommended Scenarios

Media with solid particles (A pre-filter with filtration accuracy ≥100μm is required)

Vacuum systems or working conditions with high pressure differential (>300kPa)

Diverting flow applications (For mixing and straight flow only)

Corrosive media (Select MXG461S stainless steel version)

5.3 حالات التطبيق النموذجية

قضية 1: HVAC System of Commercial Complex

Project: HVAC water system renovation for a 30-floor shopping mall

طلب: Cold and hot water mixing control for air handling units on each floor, total 80 sets of MXG461.20-5.0

حصيلة: Temperature control accuracy improved to ±0.5℃, energy consumption reduced by 18%, response speed tripled

قضية 2: Industrial Water Chiller

معدات: 500RT screw chiller

طلب: Chilled water outlet temperature control (7درجه مئوية), 4 units operated in parallel

سمات: Matched with Siemens PLC for 0-10V proportional control, water temperature fluctuation stabilized below 0.3℃

  1. استكشاف الأخطاء وإصلاحها & دليل الصيانة
ظاهرة الخللالأسباب المحتملةخطوات استكشاف الأخطاء وإصلاحهاالحلول
Valve fails to operate1. No power supply1. Measure terminal voltage (24V±20%)1. Repair power circuit
2. Missing control signal2. Check 0-10V/4-20mA control signal2. Inspect controller output
3. Actuator failure3. Manual operation test (Turn handwheel clockwise)3. Replace ASE1 electronic module
Poor regulating accuracy1. Position offset1. Perform auto-calibration (Long press calibration button)1. Recalibrate the valve
2. Incorrect valve characteristic setting2. Check DIP switch (Linear / Equal percentage)2. Reset DIP switch
3. Impurities in medium3. Inspect filter cleanliness3. Clean the filter
Excessive leakage1. Aged seals1. Check seal condition1. Replace EPDM seals
2. Worn valve seat2. Measure leakage under closed status2. Replace valve seat assembly
3. Excessive pressure differential3. Confirm system pressure differential ≤300kPa3. Install bypass valve to reduce pressure difference
Abnormal feedback signal1. Faulty feedback wiring1. Measure feedback terminal voltage (0-10الخامس)1. Repair feedback wiring
2. Damaged electronic module2. Check module indicator lights2. Replace electronic module
3. Defective inductive sensor3. Inspect sensor connection3. Replace inductive sensor

Maintenance Schedule

عنصر الصيانةدورةOperation Content
التفتيش البصريشهرياCheck valve body and actuator for damage and loose connections
تنظيف الفلترربع سنويةClean inlet filter to prevent impurity ingress
Auto-CalibrationSemi-annuallyExecute auto-calibration to ensure positioning accuracy
Seal InspectionسنوياCheck seal aging and replace if necessary
Overhaulكل 3 سنينDismantle for internal inspection and replace wearing parts
  1. إرشادات الاختيار
  2. ثلاثة عوامل اختيار رئيسية: DN size (match pipeline) → Kvs flow rate (meet system demand) → Medium type (Standard type for cold/hot water, Type P for mineral oil)
  3. Signal Selection: DC 0-10V for general control; DC 4-20mA for long-distance transmission (قوية مضادة للتدخل)
  4. نصائح التثبيت: Follow the flow direction marked on the valve body; do not use as diverting valve; 4-wire connection for power and signal ensures higher stability
  5. Fault Judgment: Automatic shutdown after power loss (spring return) is a standard safety function; manual operation can quickly verify mechanical performance
  6. طلب المعلومات

النموذج القياسي: MXG461.20-5.0 (BPZ:MXG461.20-5.0)

الملحقات الموصى بها: ALG203 thread fitting set (3 union nuts + 3 gaskets + 3 plain washers), Z155/20 blind flange set

Replacement Module: ASE1 electronic module (Applicable for DN15-32)

Supplementary Application Description

MXG461.20-5.0 is a DN20 solenoid proportional modulating valve with Kvs=5.0. It is mainly used for continuous and precise temperature control in closed cold and hot water systems. Featuring fast positioning (<2ق) and high resolution (1:1000), it is only applicable for mixing and straight flow, not for diverting service.

  1. التدفئة والتهوية وتكييف الهواء & Refrigeration (Primary Application)

Air Handling Units / Fresh Air Units: Proportional regulation of cold/hot water coils to stabilize supply air temperature (±0.5℃)

Fan Coil Units (FCU): Terminal temperature control for high-rise and commercial buildings, available for 2-way on/off or 3-way mixing flow

Chilled Water Systems: Water temperature regulation and bypass mixing control for chillers

Cooling Tower Control: Stabilize cooling water temperature and save energy

Computer Room Precision Air Conditioning: High-precision water temperature control for data center and equipment room cooling

  1. District Heating & Boiler Systems

Heat Exchanger Stations: Secondary hot water temperature regulation and mixing loop control

Radiant Floor Heating: Limit supply water temperature (35–45℃) and prevent overheating via 3-way mixing

Boiler Load Control: Stabilize hot water outlet temperature and follow system load changes

Domestic Hot Water (DHW): Mix cold and hot water to provide constant-temperature water (على سبيل المثال. 45–55℃)

  1. Industrial Process & Special Media

Process Cooling: Precise cooling water temperature control for injection molding machines, printing machines and lasers

Mold Temperature Controllers: Proportional regulation for thermal oil and hot water circuits (Type P for mineral oil)

طعام & صناعة الأدوية (Sanitary Application): Closed-loop temperature control for pure water and hot water

Solar Water Heating Systems: Mix water from solar collectors and return water for constant water supply

  1. Typical Circuit Applications

3-way Mixing (Combining Flow): Mix high-temperature primary water and low-temperature secondary water to stabilize supply water temperature (most common application)

2-way Straight Flow: On/off or proportional regulation for coil/equipment inlet, automatic shutdown upon power loss for safety

Bypass / Differential Pressure Control: Stabilize system pressure difference and balance flow under partial load

  1. Disqualified Application Scenarios

❌ Media with solid particles (Pre-filter ≥100μm required)

❌ Diverting flow service (Mixing and straight flow only)

❌ Vacuum conditions, high pressure differential (>300kPa) or highly corrosive media

❌ Steam systems (Operating medium: cold/hot water and thermal oil, 1–130℃)

  1. Application Matching Based on Core Advantages

Fast Response (<2ق): Ideal for systems with fluctuating load requiring rapid temperature stabilization, such as HVAC terminals and process cooling

High Resolution (1:1000): Suitable for high-precision temperature control scenarios including precision air conditioning, pharmaceutical and electronic manufacturing

Power-off Safety (Port A→AB Closed): Safety loop for heating and hot water systems to avoid overheating and scalding risks