Full Model Name: CP SNT 48W 24V 2A
فئة: DIN Rail Single-Phase Switching Power Supply (ConnectPower INSTA Series)
- Core Electrical Specifications
مدخل
تكييف: 85~264 VAC, 50/60 هرتز
DC compatibility: 110~370 VDC
اتصال: محطات المسمار
Built-in 2.5A(ت) input fuse
الإخراج
تصنيف: 24 VDC / 2 أ, total power 48 دبليو
Adjustable output voltage range: 15~28 VDC
تموج & ضوضاء: ≤120 mV
Maximum parallel units: 3 (active current sharing)
Maximum capacitive load at output: 8000 ميكروف
- Isolation & حماية
Input-to-output isolation voltage: 4 كيلو فولت
وظائف الحماية: التيار الزائد, الزائد, ماس كهربائى, overvoltage automatic protection, auto-recovery after fault elimination
Status indicator: Green LED for power normal indication
- ميكانيكية & البيانات البيئية
تصاعد: معيار 35 مم DIN السكك الحديدية
الأبعاد الشاملة: W70 × H90.5 × D62.5 mm
وزن: تقريبا. 200 ز
درجة حرارة التشغيل: -10 ℃~+70 ℃ (derating required above 55℃)
Storage temperature: -40 ℃~+85 ℃
رطوبة: ≤95%RH, غير التكثيف
- الشهادات & امتثال
م, UL/cULus, توفالو, بنفايات, يصل
Applicable standard: ITE industrial control equipment
- التطبيقات النموذجية
Power supply for PLCs, أجهزة الاستشعار, صمامات الملف اللولبي, small control cabinets, أتمتة البناء, access control systems and fieldbus modules
- Alternative Selection Reference (نفس السلسلة / Compatible Solutions)
- Upgraded Weidmüller model with identical power rating: CP E SNT 48W 24V (new-generation economical version)
- Third-party equivalent models:
Siemens SITOP PSU100C 24V/2.5A
Phoenix Contact STEP-PS 24V/2A
Application Scenarios of Weidmüller 8739140000 (CP SNT 48W 24V 2A)
This power supply belongs to the INSTA installation-grade DIN rail switching power supply. Rated 48W/24VDC/2A with wide-range input and compact plastic housing. It is mainly deployed in small and medium-sized control cabinets, building equipment and light-duty automation sites, suitable for 24VDC loads with total power consumption ≤42W (derating margin recommended).
- الأتمتة الصناعية (Mainstream Application)
List of Powered Loads
Small PLCs, remote I/O modules, signal relay assemblies, proximity/photoelectric sensors, encoders, miniature solenoid valves, واجهة المستخدم البشرية (small touch panels), fieldbus terminal modules (Profinet/Modbus slaves).
Typical Equipment Scenarios
- Substation control cabinets on production lines, small conveyor control boxes
- Auxiliary control cabinets for packaging machinery, labellers and small test tooling
- Auxiliary machine tool control cabinets (cooling fans, sensor loops, signal circuits)
- Test equipment, automated test benches and laboratory industrial control cabinets
> ملحوظة: Not applicable for high-power servos or dense pneumatic valve clusters; minimum 15% power margin is recommended for all loads.
- أتمتة البناء / التدفئة والتهوية وتكييف الهواء
- Central air-conditioning DDC controllers, duct sensors, air damper actuators
- Fire linkage control modules, smoke/temperature sensor repeaters, fire shutter control boxes
- Intelligent lighting control modules, building gateways, energy consumption acquisition terminals
- Local small control boxes for water pumps and fans
- Access Control, Security & Intelligent Transportation
- Access controllers, card readers, electric locks and small barrier control boxes
- Security alarm hosts, perimeter infrared photoelectric beams and vibration detector power supply
- Auxiliary control units for parking barriers, parking space detection sensors
- Auxiliary signal collection boxes for traffic lights, miniature road detection terminals
- Intelligent Equipment & التعامل مع المواد
- AGV station call panels, photoelectric detection loops for sorting machines
- Miniature signal acquisition cabinets in automated warehouses
- Signal collection sub-stations for printing and textile machinery
- Small control cabinets for food machinery (dry and clean working conditions)
- Industrial LED Lighting & Signage
Equipment status indicators, cabinet internal lighting, equipment warning light strips
Small equipment display panels, workstation indicator light boxes (constant-voltage 24V light strips)
✅ Application Restrictions (السيناريوهات غير الموصى بها)
- Open-air outdoor environments: No ingress protection rating; only for indoor cabinet installation
- Cabinets with heavy dust, corrosive atmosphere or persistent condensation
- Battery float charging applications (not a dedicated charging power supply; cannot directly charge batteries)
- Continuous full-load operation close to 48W, or loads with frequent high impulse power
- Long-term full-load operation inside enclosed cabinets above 55℃ (power derating mandatory)
Load Selection Guidelines
Safe continuous total power consumption: ≤42W (≈1.75A). Short-time peak loads can reach 48W temporarily, while continuous full load accelerates service life degradation.
Supports up to 3 units in parallel for capacity expansion (fine-tune output voltage to maintain current sharing when paralleling).
Mounting Specification for Weidmüller 8739140000 (CP SNT 48W 24V 2A)
- Basic Mounting Method
Snap-on mounting onto standard 35 مم DIN السكك الحديدية (TH35-7.5)
- Hook the upper latch on the bottom of the power supply onto the DIN rail;
- Press down the housing until an audible click confirms the lower lock engages with the rail;
- Removal: Use a flathead screwdriver to pry down the bottom latch, then lift upwards to detach.
> ❗ Direct wall mounting via screws is not supported; a DIN rail mounting bracket is required for wall installation.
- Mounting Orientation (المتطلبات الإلزامية)
✅ Recommended: التركيب العمودي, terminals up or terminals down (terminals down preferred by manufacturer)
❌ Horizontal flat mounting (housing laid sideways) prohibited
سبب: Natural convection cooling channels are built inside; horizontal placement severely obstructs heat dissipation, causing heavy power derating, shortened service life or overtemperature protection.
- Cabinet Clearance for Heat Dissipation (Critical)
Minimum clearance ≥50 mm above the power supply
Minimum clearance ≥20 mm below the power supply
Minimum spacing ≥10 mm on left and right sides from heat-generating components (المقاولين, المرحلات)
For multiple units mounted side by side: maintain ≥10 mm mutual spacing; tight arrangement leads to heat accumulation.
- Terminal Wiring Specifications
- محطات الإدخال: ل / ن / بي (protective earth)
Cable size: 0.5~2.5 mm² solid or stranded copper wire
Screw torque: 0.6~0.8 N·m
- Output terminals: +24V / 0V
Cable size: 0.5~2.5 mm²
Screw torque: 0.6~0.8 N·m
> Avoid excessive exposed bare conductors to prevent short circuits; ferrules are recommended for stranded wires.
- Environmental Mounting Constraints
- Install only inside control cabinets; no enclosure protection, cannot be deployed outdoors or in damp exposed areas
- Avoid mounting adjacent to transformers, high-power contactors and other high heat sources
- Power derating is required if cabinet ambient temperature exceeds 55℃ without ventilation fans
- Route cables away from inverter and servo drive output cables to reduce electromagnetic interference
- Additional On-site Mounting Tips
- The DIN rail shall be reliably earthed; connect the PE terminal of the power supply to protective earth to improve EMC performance and safety
- For high-vibration sites (الناقلات, أدوات الآلة), install rail end stops to prevent sliding
- When multiple power supplies are paralleled, mount them on the same DIN rail and adopt equal-length wiring to minimise circulating current
- Common Improper Mounting Pitfalls
- Horizontal flat mounting → poor heat dissipation and overtemperature
- Insufficient vertical ventilation clearance → high-temperature derating and frequent faults
- Excessive screw torque causing terminal thread stripping; insufficient torque leading to poor contact and overheating
- Unconnected PE protective earth → degraded anti-interference performance and potential safety hazards
المقاولين,قاطع الدائرة,العاكس للطاقة الشمسية,عداد كهرباء,البطاريات الشمسية