Zhongguan Electric Control DWK3-110

DWK3-110 is a substation voltage and reactive power integrated controller (VQC), commonly known as high-voltage reactive power compensation controller. It is used in 6~110kV substations to automatically regulate busbar voltage and switch capacitor/reactor banks, realizing integrated optimal control of voltage and reactive power. It is widely applied in power grid substations and distribution station high-voltage ...

  • تفاصيل المنتج

DWK3-110 is a substation voltage and reactive power integrated تحكم (VQC), commonly known as high-voltage reactive power compensation controller. It is used in 6~110kV substations to automatically regulate busbar voltage and switch capacitor/reactor banks, realizing integrated optimal control of voltage and reactive power. It is widely applied in power grid substations and distribution station high-voltage reactive power compensation cubicles.

✅ Model Nomenclature & Sub-series

DWK3-110【Suffix】

Series A (Integrated VQC: main transformer voltage regulation + capacitor switching)

DWK3-110A2: 1~2 main transformers, 1~2 capacitor banks

DWK3-110A8: 1~2 main transformers, 1~8 capacitor banks

DWK3-110A36: 1~3 main transformers, 1~6 capacitor/reactor banks, supports three-section busbar

Series C (Pure high-voltage reactive compensation, capacitor switching only, no main transformer voltage regulation)

DWK3-110CD: Simple single-busbar type, controls 1~4 capacitor banks (commonly used for 6/10kV)

DWK3-110C4D / C8D / C12 / C38: أعزب / مزدوج / three-section busbar, 4/8/12 البنوك مكثف

Series T (Regulating reactive power compensation, patented solution, on-load tap-changer capacitor): DWK3-110TC1, TC2, TA2

Series L (Special for filter compensation): DWK3-110LD, L8, L12, for filter capacitor bank switching control

Series D: Low-voltage reactive power compensation; Series B: Capacitor bank protection device

✅ Core Functions

  1. منطق التحكم: Real-time acquisition of busbar U, أنا, ص, س, cosφ; automatic switching of capacitors/reactors based on dual criteria of voltage and reactive power. Series A additionally controls on-load tap positions of main transformers, with anti-tap hunting and anti-switching oscillation functions.
  2. Switching Strategy: Supports equal-capacity balanced switching, unequal-capacity selective switching and combined switching. Faulty capacitor banks can be individually masked without affecting automatic operation of remaining banks.
  3. Operation Modes: ثلاثة أوضاع: آلي / Local Manual / Remote Communication Remote Control. It can run standalone or connect to substation integrated automation systems.
  4. تواصل: RS485 (some models with RS232), Modbus-RTU protocol. Realizes telemetry, telesignalling and remote control, compatible with integrated protection backstage and remote terminal units.
  5. Protection Blocking: الجهد الزائد / undervoltage blocking, cabinet power-loss blocking, hardware watchdog. All outputs are blocked upon CPU crash to prevent misoperation; resistant to harmonic and strong electric pulse interference.
  6. واجهة الإنسان والآلة: LCD Chinese display, real-time display of voltage, حاضِر, عامل الطاقة, قوة رد الفعل, capacitor status and fault event records; parameter setting via panel keys.

✅ Hardware Installation (CD type as example)

Panel flush mounting, cutout dimension: 151mm × 151mm

مزود الطاقة: تيار متردد 220 فولت (standard for substations)

Analog inputs: PT voltage, CT current

Digital inputs: tap position signal, incoming/bus coupler position, capacitor cubicle position signal

Relay outputs: Capacitor switch open/close, main transformer tap raise/lower (Series A), اتصال التنبيه

✅ Typical Application Scenarios

6كيلو فولت, 10كيلو فولت, 35كيلو فولت, 110kV manned / unattended substations

Distribution station high-voltage reactive compensation cubicles, capacitor complete sets

VQC retrofitting of old substations (Series A/T); filter compensation cubicles adopt Series L

✅ Common Troubleshooting

  1. No switching action: Check PT/CT polarity, transformation ratio setting, voltage upper/lower limits, reactive threshold and blocking conditions (الجهد الزائد/الجهد المنخفض, switch position).
  2. Frequent oscillation: Reset switching thresholds and enable unequal-capacity combined switching algorithm.
  3. فشل الاتصالات: يفحص 485 A/B wiring, عنوان الرقيق, baud rate and Modbus register configuration.
  4. لا يوجد عرض: Verify AC220V power supply and power fuse.

✅ Alternative Selection Reference

Domestic equivalent VQC: NARI, XJ, Sifang, Baoding Langbaodi and other substation voltage and reactive power controllers. Need to verify number of bus sections, quantity of main transformers, number of capacitor loops and communication protocol.

DWK3-110CD Complete Technical Specification (Zhongguan Electric Control, simple single-busbar high-voltage reactive compensation controller)

طلب: 6كيلو فولت / 10kV substations, controls up to 4 البنوك مكثف, reactive compensation only, no main transformer voltage regulation function

  1. Power Supply Parameters
غرضالمعلمة
Rated Supply VoltageAC/DC 100~265V (wide-range power supply, AC220V commonly used in substations)
Total Power Consumption≤10VA
  1. المدخلات التناظرية (PT/CT)
غرضالمعلمة
مدخلات الجهد0~150V (PT secondary)
الإدخال الحالي0~5A (CT secondary)
Voltage Measurement Accuracy≤0.5%FS
Current Measurement Accuracy≤2.0%FS
Power Factor Accuracy≤1.0%FS
Clock Accuracy≤1 second/day

ثالثا. المخرجات الرقمية (Relay Contacts)

غرضالمعلمة
Capacitor Switching Outputs4 مخرجات التتابع (المقابلة ل 4 البنوك مكثف)
تقييم الاتصالتيار متردد 220 فولت, 5أ (passive contact, driving vacuum contactors / قواطع الدائرة)
Alarm Output1 common passive alarm contact
  1. المدخلات الرقمية (Telesignalling)

Capacitor switch position signals (ما يصل الى 4 القنوات), cabinet power-loss blocking signal; passive dry contact input.

  1. واجهة الاتصالات

واجهة: RS485

بروتوكول: مودبوس-RTU

وظائف: Telemetry (U/I/P/Q/cosφ), telesignalling (capacitor status, إنذار), التحكم عن بعد (remote switching)

Independent register mapping document available separately

  1. الظروف البيئية
غرضالمعلمة
درجة حرارة التشغيل-15℃ ~ +50℃
درجة حرارة التخزين-25درجه مئوية ~ +70 درجه مئوية
الرطوبة النسبية≥95% رطوبة نسبية (25درجه مئوية, غير التكثيف)
Seismic ResistanceCompliant with substation panel installation requirements

سابعا. التوافق الكهرومغناطيسي

Common-mode interference: 2500V

Differential-mode interference: 1000V

Hardware watchdog blocks all outputs automatically on CPU crash to prevent false switching; withstands strong harmonics and electrical fast transient pulses.

ثامنا. الأبعاد الميكانيكية & تثبيت

تصاعد: Panel flush mounting

Panel dimension: 160mm × 160mm

Cutout dimension: 151mm × 151mm

وزن: تقريبا. 0.8كجم

  1. Control Functional Parameters
  2. أوضاع التحكم: آلي / Local Manual / Remote Communication Remote Control three modes
  3. Switching Algorithm: Equal-capacity balanced switching, unequal-capacity selective switching, combined switching; any capacitor bank can be masked while remaining banks run automatically.
  4. معيار: Dual criteria of voltage + قوة رد الفعل; overvoltage/undervoltage blocking, capacitor tripping and alarm triggered upon blocking.
  5. Event Recording: Stores switching events and fault alarm records, queryable on panel.
  6. Busbar: Single busbar measurement (CD model is simple single-busbar version)
  7. Protection Blocking Logic

Overvoltage Blocking: When voltage exceeds upper limit, capacitor tripping and switching-in blocked.

Undervoltage Blocking: When voltage drops below lower limit, capacitor switching-in prohibited.

Cubicle Power-loss Blocking: Capacitor cubicle power loss forces capacitor tripping and prohibits switching-in.

Hardware Fault Blocking: On CPU abnormality or watchdog trigger, all outputs are blocked immediately.

  1. Model Boundary Description (Distinguish within series)

DWK3-110CD: Simple version, single busbar, الأعلى. 4 البنوك مكثف, supports combined switching, no multi-bus interconnection logic

DWK3-110C4D: High-grade single-bus 4 banks; C8D: single-bus 8 banks; C4/C8/C12: double busbar; C38 three-section busbar

DWK3-110Axx: Series A is full VQC with main transformer on-load tap control (major difference from CD)

DWK3‑110CD Modbus‑RTU Register List (Zhongguan Electric Control, 10kV single-busbar 4-bank capacitor controller)

⚠️Note: The complete original manufacturer protocol manual is not publicly available online. This version is compiled from field engineering test data (many substation integrated automation docking cases). Divided into【Input Registers 3xxxx】,【Coils 0xxxx】,【Holding Registers 4xxxx (حدود + التحكم عن بعد).

Communication basics: RS485, مودبوس-RTU, default slave address=1; معدل الباود الافتراضي 9600, 8ن1.

Data scaling rule: All analog values are integers, divide by scaling factor to get actual value; 32-bit floating point occupies 2 consecutive registers (high word first).

  1. Input Registers (3xxxx, Function Code 04H, Read-only, real-time telemetry)
Logical Address0-based OffsetاسمشكلScaling Rule
300010Busbar Voltage U16bit INTReading ÷10 → kV (PT secondary 100V)
300021Busbar Current I16bit INTReading ÷100 → A
300032Active Power P16bit INTReading ÷10 → kW
300043Reactive Power Q16bit INTReading ÷10 → kvar; negative = capacitive
300054Power Factor cosφ16bit INTReading ÷1000
300065System Frequency F16bit INTReading ÷10 → Hz
300076Controller Operating Status Word16bit BITMAPBit0=Auto Mode; Bit1=Manual; Bit2=Remote; Bit3=Alarm; Bit4=Blocked; Bit5=Fault
300087Capacitor Bank Status Word16bit BITMAPBit0=Cap1 Closed; Bit1=Cap2 Closed; Bit2=Cap3 Closed; Bit3=Cap4 Closed; Bit8=Cap1 Fault; Bit9=Cap2 Fault; Bit10=Cap3 Fault; Bit11=Cap4 Fault
  1. Coils (0xxxx, Function Code 01H Read, 05H Single Write, 0FH Bulk Write, التحكم عن بعد / Telesignalling)
Logical Addressإزاحةاسموصف
10مكثف 1 Remote ClosePulse remote control, valid only under remote mode
21مكثف 1 Remote Openنبض
32مكثف 2 Remote Closeنبض
43مكثف 2 Remote Openنبض
54مكثف 3 Remote Closeنبض
65مكثف 3 Remote Openنبض
76مكثف 4 Remote Closeنبض
87مكثف 4 Remote Openنبض
98Remote/Local Switchover1=Remote control enable; 0=Local lockout

Remote control mechanism: Pulse remote control (write 1 to trigger action, controller auto-clears). Holding coils are not supported. Remote control executes only when controller is in【Remote Mode】and no blocking conditions exist.

ثالثا. Holding Registers (4xxxx, Function Code 03H Read, 06H/10H Write; Setting parameters, read-write)

Logical AddressإزاحةاسمUnit/Rangeملاحظات
400010Slave Address1~247Requires restart after modification
400021معدل الباود1=9600, 2=19200Requires restart after modification
400032Voltage Upper Limit Setting×0.1kVOvervoltage switching-in block threshold
400043Voltage Lower Limit Setting×0.1kVUndervoltage switching-in block threshold
400054Reactive Power Switch-In Threshold×0.1kvarSwitch capacitor when inductive reactive power exceeds this value
400065Reactive Power Switch-Out Threshold×0.1kvarSwitch off capacitor when capacitive reactive power exceeds this value
400076PT Ratio Primary Valueكيلو فولتعلى سبيل المثال. 10kV PT input 100
400087PT Ratio Secondary ValueVFixed at 100
400098CT Ratio Primary ValueأCT primary rated current
400109CT Ratio Secondary ValueأFixed at 5
4001110Switching Interval DelayثانيةAnti-oscillation, normally set 10~30s
4001211وضع التحكم0=Auto,1=Local Manual,2=RemoteWrite value to switch mode
  1. إنذار & Event Registers (Read-only, within holding register area)
Logical Addressإزاحةاسموصف
4002019Current Alarm WordBit0 Overvoltage; Bit1 Undervoltage; Bit2 Power-loss Block; Bit3 Cap1 Fault; Bit4 Cap2 Fault; Bit5 Cap3 Fault; Bit6 Cap4 Fault; Bit7 Communication Fault
  1. Critical Notes for Engineering Integration
  2. Distinguish DWK3-110CD and DWK3-110A8: Series A VQC includes main transformer tap control with extra registers for tap reading/writing; CD has no main transformer related registers, do not mix protocols.
  3. Two register address pitfalls: In Modbus Poll use offset (0-يبدأ); many SCADA/HMI software directly uses logical address (30001), avoid ±1 offset error.
  4. Write permission for settings: Some firmware versions require panel unlock before parameter writing; otherwise write command returns exception code 02.
  5. Telesignalling recommendation: read coils instead of only status word: Status word has refresh latency; capacitor position telesignalling should read coils directly.
  6. Exception Codes: 01 Illegal Function Code; 02 Illegal Address; 03 Illegal Data; 04 Device Fault (blocked / mode prohibits remote control).
  7. Test Message Example (Read busbar voltage, slave 1, read 30001, 1 register)

Transmit: 01 04 00 00 00 01 31 كاليفورنيا

إجابة: 01 04 02 03 E8 B9 45

03E8 = 1000 → 1000/10 = 10.0kV busbar voltage

Working Principle of Zhongguan Electric Control DWK3‑110 (Series A VQC and Series C CD; Series A full voltage & reactive integrated control, CD capacitor switching only)

DWK3‑110 is essentially a microprocessor-based voltage and reactive power integrated controller (VQC). Core workflow: Sample busbar PT & CT signals → Calculate U/I/P/Q/cosφ → Compare with setpoints → Output relay contacts to control capacitors / main transformer tap, with blocking protection.

  1. Hardware Sampling Stage
  2. المدخلات التناظرية: Connect busbar PT secondary voltage (0~100V), CT secondary current (0~5A). Sampling chip continuously samples three-phase voltage and current.
  3. CPU Calculation: Microcontroller computes active P, reactive Q, power factor cosφ, تكرار; meanwhile reads digital telesignals: capacitor switch position, bus coupler status, main transformer tap position (Series A), fault blocking signals.
  4. واجهة المستخدم البشرية & تواصل: LCD panel real-time display; RS485 Modbus-RTU uploads telemetry & telesignalling to substation backstage and receives remote control commands.
  5. Core Control Logic (Two Major Versions)

✅ Series A (DWK3‑110Axx, Full VQC, U-Q 9-zone diagram strategy)

Series A controls both main transformer on-load tap-changer and capacitor switching, adopting industry standard U-Q nine-zone diagram algorithm: vertical axis = busbar voltage U, horizontal axis = reactive power Q. The plane is divided into nine zones by voltage upper/lower limits and reactive switching thresholds.

منطقة 9: Voltage and reactive power within acceptable range → No action

For the other 8 zones, regulation follows priority:

  1. Adjust reactive power first by capacitor switching (switching capacitor supplies inductive reactive power and lifts voltage; switching off capacitor reduces capacitive reactive power and lowers voltage)
  2. When reactive power reaches regulation limit, operate main transformer on-load tap-changer to adjust voltage

Anti-tap hunting logic: Limit continuous tap operation count and delay to prevent repeated tap change from minor voltage fluctuations. Inverse voltage regulation optional, automatically adjust target voltage band according to load and reduce operation times.

✅ Series C (DWK3‑110CD/C4D, CD as above, no main transformer tap control)

CD only performs high-voltage capacitor switching, controls capacitor banks only without main transformer tap regulation, adopting dual criteria of voltage + قوة رد الفعل:

  1. Continuously monitor busbar voltage and reactive power
  2. Capacitor switching-in allowed only when both conditions are satisfied: Busbar voltage within permitted range + system inductive reactive power exceeds switch-in threshold → relay contact closes to drive vacuum contactor to switch capacitor in.
  3. When busbar voltage is too high or system becomes capacitive (reverse reactive power flow) exceeding switch-out threshold → relay contact opens to switch capacitor off.

Switching algorithms:

Equal-capacity banks: Balanced cyclic switching, equalize operation count of each bank to extend service life

Unequal-capacity banks: Adaptive combined switching, select optimal capacity combination according to reactive magnitude for higher compensation precision and avoid oscillation

Any faulty/maintenance capacitor bank is automatically masked; remaining banks keep automatic operation.

ثالثا. Blocking Protection Principle (Safety Core)

All models have multi-layer blocking. Once blocking condition triggers, capacitor switching-in is prohibited immediately; already-connected capacitors will be tripped if needed:

  1. Overvoltage Blocking: Busbar voltage>upper limit → block switching-in and trip capacitors to avoid capacitor overvoltage damage.
  2. Undervoltage Blocking: Busbar voltage<lower limit → prohibit capacitor switching-in; switching capacitors under low voltage may amplify resonance risk.
  3. Switch Position Blocking: When incoming/bus coupler switch opens, trip capacitors on this section and suspend automatic control.
  4. Hardware Watchdog & Self-diagnosis: On CPU crash, hardware circuit blocks all relay outputs directly to prevent false trip/close. Detect capacitor fail-to-open / fail-to-close, trigger alarm and isolate that bank.
  5. تأخير التبديل: Fixed waiting time after each action (10~ 30 ثانية), prevent cyclic switching oscillation caused by short-term grid fluctuations.
  6. Three Operation Modes
  7. Auto Mode: Controller samples, judges and executes automatic switching / tap regulation independently (normal running mode).
  8. Local Manual: Manual capacitor switching / tap raise-lower via panel keys, auto logic suspended, for commissioning and maintenance.
  9. التحكم عن بعد: Backstage sends remote switch commands via Modbus; local auto logic exits under remote mode, protection blocking remains active.
  10. Series T (DWK3‑110TC Tap-regulated compensation, different principle)

Series T is not conventional stepwise capacitor switching. It adjusts taps of on-load autotransformer connected in series before capacitors, changing voltage across capacitors to continuously and smoothly vary reactive output. Capacitors do not need frequent switching, resulting in lower impact and longer service life.