Basic Product Information
ماركة: SAMWHA EOCR (شنايدر Korea)
نوع المنتج: EOCR-SS Series Knob-type Electronic Motor Protector (Replaces traditional thermal overload relays)
- Model Code Breakdown of EOCRSS-60NW7PQ
| شريحة | شفرة | تعريف |
| EOCRSS | مسلسل | SS Economy Integrated Through-Core Motor Protector |
| 60 | التقييم الحالي | Built-in CT, adjustable rated current: 5.0~60A, compatible with 1.5~30kW three-phase motors |
| ن | وضع الحماية | Type N Fail-Safe: Contacts open and contactor trips upon protector power loss or fault; Type R does not trip when power fails |
| W7 | مزود الطاقة | W7 = Wide Voltage AC 180~480V (Suitable for 380/400/440V industrial three-phase power grids) |
| ص | تكوين الاتصال | P = Standard changeover contacts: 95(نورث كارولاينا)/97(لا) (1 مفتوح عادة + 1 مغلق عادة) |
| س | وظيفة إضافية | Q = Built-in Modbus-RTU RS485 communication; supports PLC/DCS remote monitoring, real-time current reading and fault code retrieval |
المواصفات الفنية الأساسية
3.1 حاضِر & Time Adjustment
النطاق الحالي: 5~60A (10:1 wide adjustment ratio)
D-Time (Start Stall Delay): 0.2~30s adjustable to avoid false tripping caused by high motor starting current
O-Time (Overload Trip Delay): 0.2~30s adjustable to match motor thermal characteristic curves
3.2 وظائف الحماية
- الزائد & حماية التيار الزائد (O-Time delayed trip)
- Three-Phase Phase Loss Protection (Instant trip)
- Stall Protection (D-Time + O-Time dual delay)
- Three-Phase Current Unbalance Protection
3.3 المواصفات الكهربائية
Operating Power Supply: AC 180~480V (W7 wide voltage)
Output Contacts: 5A/250VAC changeover contacts (95نورث كارولاينا, 96كوم, 97لا)
تواصل: RS485 Modbus RTU (Exclusive to Q suffix models)
Dielectric Withstand Voltage: 2kV for 1 دقيقة
استهلاك الطاقة: ≤250mA
3.4 بيئة & تثبيت
درجة حرارة التشغيل: -20℃~+60℃; درجة حرارة التخزين: -30℃~+80℃
رطوبة: 30%~85%RH, غير التكثيف
تصاعد: Standard 35mm DIN rail or screw fixing
الدائرة الرئيسية: Two through-core CTs (Pass L1 and L2 through protector windows)
- Front Panel Knobs & Indicators
- LOAD(أ): Motor rated current adjustment knob (5~60A)
- D-TIME: Start delay (Prevent false tripping during startup)
- O-TIME: Overload trip delay
- Green PWR LED: Power supply normal
- Red TRIP LED: Fault tripping (Number of flashes indicates fault type)
- إعادة ضبط: Manual reset button; امتحان: Unit self-test button
- Key Differences of PQ Suffix (vs Standard 60NW7)
- Built-in RS485 Modbus communication: Remotely read real-time operating current, fault logs and protector status; receive remote reset commands from upper computer
- PCB of Q model integrates communication terminals, supporting multi-protector bus networking
- Ideal for automated production lines, pump stations, central air conditioning and centralized monitoring control rooms
- سيناريوهات التطبيق النموذجية
380V three-phase fans, مضخات المياه, ضواغط الهواء, belt conveyors and mixing motors
Motors with rated current 5~60A, no external current transformer required
Control cabinets requiring PLC remote motor data collection and remote fault reset
- Wiring Guidelines
- الدائرة الرئيسية: Run motor phase wires L1 and L2 through the two CT windows of the protector; L3 does not need to pass through
- Power Terminals A1/A2: Connect to AC380V control power supply
- دائرة التحكم: 96COM كمحطة مشتركة; wire 95NC normally closed contact in series with contactor coil (Type N opens on power loss); connect 97NO normally open contact to fault alarm indicator light
- RS485 Communication: A/B differential bus, daisy-chain wiring for multiple devices
- Troubleshooting Matrix
| ظاهرة الخلل | السبب الجذري | الحلول |
| TRIP LED stays lit and cannot be reset | Continuous overload / motor stall | تقليل الحمل, increase set current, check mechanical jamming |
| TRIP LED flashes twice | Phase loss | Inspect main circuit fuses, contactor contacts and motor wiring |
| No response after power-on, PWR LED off | Abnormal power supply to A1/A2 | Measure 380V power supply, replace the protector |
| No Modbus communication data | A/B wires reversed / duplicate device addresses | Swap RS485 A/B polarity, set unique address for each device |
- Alternative Models in the Same Series
- Non-communication version: EOCRSS-60NW7P (No RS485, تكلفة أقل)
- 24–240V power supply version: EOCRSS-60NS7PQ (S7 = 24~240V AC/DC)
- Higher current rating: For motors over 60A, select EOCRSS-100 series with external CT