Core Difference Analysis between P3U30-5AAA2BBAA and P3U30-5AAA2BBAC - Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-Mail: kent@bestcontactor.com

Um Kontakt |

 Core Difference Analysis between P3U30-5AAA2BBAA and P3U30-5AAA2BBAC - Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien

NachrichtHandelsnachrichten

Core Difference Analysis between P3U30-5AAA2BBAA and P3U30-5AAA2BBAC

Core Difference Analysis between P3U30-5AAA2BBAA and P3U30-5AAA2BBAC Both models belong to the Schneider PowerLogic/Easergy P3U30 Series Universal Protection Relay. The core difference lies only in the last two characters (AA vs AC).

Both models belong to the Schneider PowerLogic/Easergy P3U30 Series Universelles Schutzrelais. The core difference lies only in the last two characters (AA vs AC). The complete structure analysis is as follows:

ModellsegmentBedeutungP3U30-5AAA2BBAAP3U30-5AAA2BBAC
P3U30ProduktserieUniverselles Schutzrelais (P3U30)Universelles Schutzrelais (P3U30)
5Power Supply Type48-230V AC/DC48-230V AC/DC
AAAMeasurement Input3CT (1/5A), 1Io (1/5A), 4VT (100V/110V)3CT (1/5A), 1Io (1/5A), 4VT (100V/110V)
2E/A-Konfiguration16DI/8DO (with watchdog)16DI/8DO (with watchdog)
BBCommunication ModuleBasic communication configurationBasic communication configuration
AA/ACDigital Input Voltage + KommunikationsschnittstelleAA: DI=220V AC/DC, RS485 serial port onlyWechselstrom: DI=110-230V AC/DC, Dual RJ45 Ethernet ports + RS485
  1. Key Specification Comparison Table
ParameterkategorieP3U30-5AAA2BBAAP3U30-5AAA2BBACImpact of Difference
Standard REL CodeREL52002REL52008Official material code distinction
Digitaler Eingang (AUS)16 Kanäle, 220V AC/DC16 Kanäle, 110-230V AC/DCAC version has wider voltage range for more application scenarios
Kommunikationsschnittstelle1×RS485 Serial Port (Modbus RTU / IEC 60870-5-101/103)2×RJ45 Ethernet Ports (IEC 61850 / Modbus TCP) + 1×RS485 Serial PortAC version supports Ethernet communication for system network integration
KommunikationsprotokollSerial protocols only (kein Ethernet)All serial protocols + Ethernet protocols (IEC 61850 Ed.1/Ed.2, DNP3, Ethernet/IP)AC version complies with modern industrial Ethernet standards
VerbindungstypSchraubklemmenSchraubklemmen + Dual RJ45 portsAC version facilitates network wiring and remote monitoring
Other Core ParametersIdentisch: 3CT phase current input (1/5A), 1Io residual current input (1/5A), 4VT voltage input (100V/110V), 8TUN (with watchdog), 48-230V AC/DC power supplyIdentischBasic protection functions are fully consistent
  1. Detailed Description of Differences

3.1 Digital Input Voltage Difference

P3U30-5AAA2BBAA (REL52002): Fixed digital input of 220V AC/DC, suitable for standard industrial control voltage environments.

P3U30-5AAA2BBAC (REL52008): Wide-range digital input of 110-230V AC/DC, compatible with more international standard voltages with higher flexibility.

3.2 Communication Capability Difference (Core Distinction)

P3U30-5AAA2BBAA: Equipped with only RS485 serial communication, suitable for simple point-to-point communication; does not support network integration or remote monitoring.

P3U30-5AAA2BBAC: Equipped with dual RJ45 Ethernet ports + RS485 serial port, unterstützend:

Redundant Ethernet communication (RSTP/PRP protocol)

IEC 61850 substation communication standard (Ed.1/Ed.2)

Modern industrial protocols such as Modbus TCP, DNP3, Ethernet/IP

Remote-Konfiguration, monitoring and firmware upgrade

3.3 Anpassung des Anwendungsszenarios

AnwendungsszenarioEmpfohlenes ModellGrund
Traditional Substation (No network requirement)P3U30-5AAA2BBAANiedrigere Kosten, meets basic communication needs
Smart Substation / Industrial IoTP3U30-5AAA2BBACUnterstützt IEC 61850 for easy system integration
International Projects / Multi-voltage EnvironmentP3U30-5AAA2BBACWide-range DI voltage adapts to different national standards
Remote Monitoring & Diagnostics RequirementP3U30-5AAA2BBACEthernet enables remote access
Cost-Sensitive ProjectsP3U30-5AAA2BBAAEtwa 10-15% lower price than AC version
  1. Auswahlempfehlungen
  2. Communication Requirement Judgment

Local communication or simple SCADA connection only: Choose AA version (REL52002)

IEC 61850, remote monitoring or network redundancy required: Must choose AC version (REL52008)

  1. Digital Input Voltage Adaptation

System unified with 220V control voltage: AA version fully compatible

Mixed 110V/220V control voltage or uncertain future demands: Choose AC version with wide-range input

  1. Future Expandability

The dual Ethernet port design of AC version reserves space for future system upgrades and supports advanced smart grid applications.

  1. Supplementary Information

Hardware Compatibility: Both models have identical physical dimensions and mounting methods, enabling direct interchangeable installation.

Schutzfunktionen: Both provide more than 40 protection functions including overcurrent, Erdschluss, Unterspannung, phase sequence reversal, usw., meeting feeder and motor protection requirements.

Zertifizierungen: Both comply with international standards such as IEC 60255 und EN 61850 for global market application.

Communication Interface Difference: P3U30-5AAA2BBAA vs P3U30-5AAA2BBAC

P3U30-5AAA2BBAA has only an RS485 serial port without Ethernet; P3U30-5AAA2BBAC retains RS485 and adds dual RJ45 Ethernet ports to support network communication.

  1. Detailed Communication Interface Comparison
ArtikelP3U30-5AAA2BBAAP3U30-5AAA2BBAC
Physical Network PortNo RJ45 Ethernet port2-channel RJ45 Ethernet ports
Serial Interface1-channel RS485 terminal1-channel RS485 terminal (retained same as AA version)
Communication HardwareSerial communication hardware onlyDual hardware: Serial + Ethernet
Unterstützte ProtokolleSerial protocols only:All serial protocols + Ethernet protocols:
Modbus RTU, IEC 60870-5-101/103Modbus TCP, IEC 61850, DNP3, usw.
Networking CapabilityOnly RS485 bus networkingSupports Ethernet star/ring/redundant networking and dual-port cascading
Remote / Smart SubstationNo Ethernet remote access, no IEC61850 supportSupports remote network access and IEC61850 smart substation standard
  1. Key Difference Summary
  2. AA Version: Pure serial port type

Only RS485 interface, limited to traditional RS485 bus networking; cannot connect to switches, access Ethernet, or support IEC61850.

  1. AC Version: Hybrid type with serial port + zwei Ethernet-Ports

Retains the original RS485 interface and adds 2 RJ45 ports, which can be directly connected to industrial switches, form ring networks, and support IEC61850 & Modbus TCP network communication.

  1. Simple Selection Rule

Only RS485 communication for traditional cabinet internal connection → Choose P3U30-5AAA2BBAA

Require Ethernet, remote networking, smart substation or IEC61850 → Must choose P3U30-5AAA2BBAC

Schneider PowerLogic P3U30 Series Universal Protection Relay Model List

  1. Modellkodierungsregel (Full Interpretation)

The P3U30 series adopts the format P3U30-XXXXXXXX with 14 characters. The definition of each segment is as follows:

ModellsegmentPositionBedeutungOptional Code & Beschreibung
P3U301-5ProduktserieP3U30 = Universal Protection Relay for feeder and motor protection
56. des Monats6Power Supply Type5 = 48-230V AC/DC
6 = 24-48V AC/DC
AAA/ABA7-9Measurement Input ConfigurationAAA = 3CT(1/5A), 1Io(1/5A), 4VT(100V/110V)
ABA = 4L (3CT+1Io) ring-type terminal, 4VT(100V/110V)
1月2日10E/A-Konfiguration1 = 16DI/4DO (without watchdog)
2 = 16DI/8DO (with watchdog)
BB/BD/BC11-12Basic Communication ConfigurationBB = Basic communication
BD = Extended communication
BC = Advanced communication
AA/AC/BA/CA13-14Digital Input Voltage + KommunikationsschnittstelleAA = DI=220V AC/DC, Nur RS485
AC = DI=110-230V AC/DC, Dual RJ45 + RS485
BA = DI=24-48V AC/DC, Nur RS485
CA = DI=24-230V AC/DC, Dual RJ45 + RS485
  1. Vollständige Modellliste (Classified by Communication Interface)

2.1 RS485 Serial Communication Only (Without Ethernet)

ModellREL CodeStromversorgungMeasurement InputE/A-KonfigurationDI-SpannungKommunikationsschnittstelleAnwendungsszenario
P3U30-5AAA2BBAAREL5200248-230V AC/DC3CT+1Io+4VT16DI/8DO (with watchdog)220V AC/DC1×RS485Traditional substation, local communication
P3U30-5AAA2BBBAREL5200348-230V AC/DC3CT+1Io+4VT16DI/8DO (with watchdog)24-48V AC/DC1×RS485Low-voltage control system, PLC interlocking
P3U30-6AAA2BBAAREL5200424-48V AC/DC3CT+1Io+4VT16DI/8DO (with watchdog)220V AC/DC1×RS485DC system, battery-powered
P3U30-6AAA2BBBAREL5200524-48V AC/DC3CT+1Io+4VT16DI/8DO (with watchdog)24-48V AC/DC1×RS485Kleine Ausrüstung, low-power application
P3U30-5ABA1BBAAREL5200648-230V AC/DC4L ring type + 4VT16DI/4DO (without watchdog)220V AC/DC1×RS485Feeder protection, vereinfachte Konfiguration
P3U30-6ABA1BBAAREL5200724-48V AC/DC4L ring type + 4VT16DI/4DO (without watchdog)220V AC/DC1×RS485Distributed system, remote terminal unit

2.2 Dual RJ45 Ethernet + RS485 Communication (Smart Type)

ModellREL CodeStromversorgungMeasurement InputE/A-KonfigurationDI-SpannungKommunikationsschnittstelleAnwendungsszenario
P3U30-5AAA2BBACREL5200848-230V AC/DC3CT+1Io+4VT16DI/8DO (with watchdog)110-230V AC/DC2×RJ45+1×RS485Smart substation, IEC 61850
P3U30-5AAA2BBCCREL5200948-230V AC/DC3CT+1Io+4VT16DI/8DO (with watchdog)24-230V AC/DC2×RJ45+1×RS485International projects, multi-voltage compatibility
P3U30-6AAA2BBACREL5201024-48V AC/DC3CT+1Io+4VT16DI/8DO (with watchdog)110-230V AC/DC2×RJ45+1×RS485DC smart system, Fernüberwachung
P3U30-6AAA2BBCCREL5201124-48V AC/DC3CT+1Io+4VT16DI/8DO (with watchdog)24-230V AC/DC2×RJ45+1×RS485IoT integration, multi-protocol support
P3U30-5ABA1BDACREL5201248-230V AC/DC4L ring type + 4VT16DI/4DO (without watchdog)110-230V AC/DC2×RJ45+1×RS485Feeder automation, network redundancy
P3U30-6ABA1BDACREL5201324-48V AC/DC4L ring type + 4VT16DI/4DO (without watchdog)110-230V AC/DC2×RJ45+1×RS485Distributed feeder protection, IEC 61850

2.3 Special Configuration Models (Wide Temperature / Extended Functions)

ModellREL CodeBesondere MerkmaleKommunikationsschnittstelleBemerkungen
P3U30-5AAA2BBAA-WREL52045Wide temperature (-25°C~+70°C)1×RS485Outdoor application, raue Umgebung
P3U30-5AAA2BBAC-WREL52046Wide temperature (-25°C~+70°C)2×RJ45+1×RS485Smart outdoor equipment, remote diagnosis
P3U30-5ABA2BDAAREL520474L ring terminal, erweiterte E/A1×RS485High-current measurement, industrial monitoring
P3U30-5ABA2BDACREL520484L ring terminal, erweiterte E/A2×RJ45+1×RS485Smart grid, feeder automation
  1. Key Parameter Overview Comparison
ParameterkategorieRS485 Only ModelsEthernet + RS485 ModelsGemeinsame Merkmale
KommunikationsprotokolleModbus RTU, IEC 60870-5-101/103Serial protocols + IEC 61850, Modbus TCP, DNP3, Ethernet/IPAll support basic serial protocols
Networking CapabilityRS485 bus only, point-to-point / bus topologyEthernet star/ring/redundancy (RSTP/PRP), dual-port cascadingSupport standard industrial networking modes
Digitaler EingangTwo fixed voltages: 220V / 24-48VWide-range voltage: 110-230V / 24-230V16 channels with optical isolation
Digitaler Ausgang4TUN / 8TUN (watchdog optional)4TUN / 8TUN (watchdog optional)Relay output, contact rating 5A/250V AC
MessgenauigkeitKlasse 0.2 (Current/Voltage), Klasse 0.5 (Leistung)Klasse 0.2 (Current/Voltage), Klasse 0.5 (Leistung)Konform mit IEC 60255
Schutzfunktionen40+ protections (Überstrom, Erdschluss, Unterspannung, usw.)40+ protections (Überstrom, Erdschluss, Unterspannung, usw.)Suitable for feeder and motor protection
Power Supply Range24-48V or 48-230V AC/DC24-48V or 48-230V AC/DCWide voltage design for global power grid adaptation
  1. Quick Selection Chart (By Core Requirement)
Core RequirementEmpfohlenes ModellHauptvorteile
Traditional substation without network demandP3U30-5AAA2BBAALow cost, meets basic communication
Smart substation with IEC 61850P3U30-5AAA2BBACDual Ethernet ports, unterstützt IEC 61850 Ed.1/Ed.2
International project with multi-voltage environmentP3U30-5AAA2BBCC24-230V wide-range DI, globale Kompatibilität
DC system with battery power supplyP3U30-6AAA2BBAA24-48V power supply, geringer Stromverbrauch
Outdoor application & raue UmgebungP3U30-5AAA2BBAC-WWide temperature design, starke Anti-Interferenz
High-current measurement with ring terminalsP3U30-5ABA2BDAC4L ring terminals compatible with high-current CT
  1. Supplementary Information
  2. Hardware Compatibility: All P3U30 models share identical physical dimensions (96×96×75mm) and mounting methods (DIN-Schiene / panel mounting) for direct interchangeable installation.
  3. Schutzfunktionen: All models offer 40+ protection functions including overcurrent (ICH>>), Erdschluss (Ig), Unterspannung (U<), phase sequence reversal, Überlast, usw., konform mit IEC 60255 Standard.
  4. Zertifizierungen: Compliant with CE, UL, CSA, IEC 61850 and other international certifications for global market use.
  5. Firmware Upgrade: Ethernet models support remote firmware upgrade; RS485 models require local upgrade.
  6. Zubehörliste:

Front Connector: Standard 9-pin spring terminal

Communication Cable: RS485 shielded twisted pair (optional)

Ethernet Cable: CAT5e/CAT6 industrial Ethernet cable (Ethernet models only)

Vorher:

Nächste:

Hinterlassen Sie eine Antwort