EOCRSSD-30DF7 Schneider Digitaler Motorschutz

EOCRSSD-30DF7 is a digital motor protector manufactured by Schneider Electric (formerly Samwha, Südkorea) with current range 3-30A and 110VAC control power supply. It provides triple protection against overload, phase loss and locked rotor. It is applicable for precise protection of three-phase low-power motors, capable of replacing traditional thermal relays to improve protection accuracy and fault diagnosis efficiency.

  1. Model Code Definition
CodesegmentBeschreibung
EOCRElectronic Over Current Relay, core product positioning
SSDSolid State Digital, adopting solid-state electronic components and digital control technology
30Current protection range: 3~30A (direkte Verbindung, no external CT required)
DDigitalanzeige, equipped with digital tube to display real-time 3-phase average current and fault status
F7Control power specification: 110VAC±15% (50/60Hz); other options: M7(220VAC), B(24VAC/DC)
  1. Main Technical Specifications
KategorieParameterBemerkungen
Grundlegende Informationen
MarkeSchneider Electric (Former Samwha Korea)Produced in Iksan, Korea; Authorized agent in China: Shanghai Hanshi Electric
ProdukttypDigital Overcurrent Relay / Motor ProtectorHöhere Präzision (±5 %) than traditional thermal relay
Elektrische Parameter
Nennbetriebsspannung600V und (UL) / 690V und (CSA, IEC 60947-4-1)Suitable for low-voltage motor circuits
Bewertete Stoßspannungsfestigkeit6kVKonform mit IEC 60947-4-1
Kontrollmacht110VAC±15%, 50/60HzMatched with F7 code
Stromverbrauch≤3WLow power consumption for long-term operation
Schutzparameter
Einstellbarer Strombereich3~30A continuously adjustableAdjustment ratio: 10:1
Schutzfunktionen1. Überstrom (O-Time: 0.5~10s adjustable)Independent adjustable start delay D-Time
2. Phase loss (fast protection within 3s)
3. Locked rotor (combined D-Time+O-Time protection)
Reset-ModusHandbuch / Elektrisch (optional)Reset required after fault for restart
Ausgabe & Anzeige
Ausgangskontakt1 NC + 1 NEIN (2-SPST)Kontaktbewertung: 3A/250VAC
Display ModeDigital tube displayReal-time 3-phase average current, flashing fault code indication
Körperlich & Umweltfreundlich
Dimension45×75×110mm, standard DIN rail mountingCompact size saves cabinet space
SchutzgradIP20 (Frontplatte)Suitable for installation inside control cabinets
Betriebstemperatur-20℃ ~ +60℃Adaptable to industrial temperature variation
Lagertemperatur-40℃ ~ +85℃Meet transportation and storage requirements
Zertifizierung
Internationale ZertifizierungenCE, UL, CSAComply with IEC 60947-4-1, global applicable
Luftfracht-ComplianceKeine eingebaute Lithiumbatterie, conform to UN38.3Shippable as general cargo without special packaging
  1. Markenübergreifender Vergleich
ModellAktueller BereichKontrollmachtAnzeigeSchutzPreisklasseAnwendung
Schneider EOCRSSD-30DF73~30A110VACDigitale AnzeigeÜberlast / Phase loss / Locked rotor350~450CNY3-phase low-power motors with fault diagnosis demand
ABB CM-MSS.31P3~30A24~240VAC/DCKontrollleuchteÜberlast / Phase loss / Locked rotor400~500CNYAllgemeine Industriemotoren, unified brand matching
Siemens 3RB2026-1SB02.5~32A24~240VAC/DCKontrollleuchteÜberlast / Phase loss300~400CNYSupporting Siemens PLC, Grundschutz
Omron K8DS-PH13~30A100~240VACDigitale AnzeigeÜberlast / Phase loss / Locked rotor380~480CNYAutomatisierte Produktionslinien, high-precision protection
Chint NR2-322.5~32ANo control powerKeine AnzeigeÜberlast / Phase loss50~80CNYEconomy application, low precision requirement

Wichtige Auswahlpunkte

  1. Display function: EOCRSSD-30DF7 supports real-time current monitoring and fault diagnosis, superior to indicator-light-only models
  2. Protection accuracy: Electronic protector (±5 %) far exceeds thermal relay (±15 %), extending motor service life
  3. Control power: 110VAC F7 version fits specific regional power grids, confirm on-site power supply first
  4. Vollständige Modellliste der Serie

EOCR-SSD Series Classification

Aktueller BereichBasismodellPower OptionsVollständige Modellbeispiele
0.5~6AEOCRSSD-05SS:24~240VAC/DCEOCRSSD-05DF7, EOCRSSD-05DM7, EOCRSSD-05DB
F7:110VAC
M7:220VAC
W:380~440VAC
3~30AEOCRSSD-30SDas Gleiche wie obenEOCRSSD-30DF7, EOCRSSD-30DM7, EOCRSSD-30DW
5~60AEOCRSSD-60SDas Gleiche wie obenEOCRSSD-60DF7, EOCRSSD-60DM7, EOCRSSD-60DS

Bestellcode & Zubehör

Standardbestellnummer: EOCRSSD-30DF7

Mounting bracket: EOCR-MNT-01 (DIN rail type)

Extension cable: EOCR-CAB-05 (5M) / EOCR-CAB-10 (10M)

Test kit: EOCR-TEST-KIT (including analog load & calibrator)

  1. Häufige Fehler & Maintenance Solutions
FehlerphänomenMögliche UrsachenSchritte zur FehlerbehebungLösungenVorbeugende Maßnahmen
Keine digitale Anzeige1. Control power disconnected1. Klemmenspannung messen1. Connect 110VAC correctlyCheck power spec before installation
2. Wrong wiring polarity2. Verkabelung prüfen2. Adjust connection (AC non-polar)
3. Internal fuse blown3. Inspect internal fuse3. Replace 0.5A fuse
Fehlauslösung1. Low current setting1. Confirm motor rated current1. Set current to 1.1 times rated valueSet parameters per motor nameplate
2. Short start delay2. Extend D-Time2. D-Time = motor start time +1s
3. Power harmonic interference3. Test power THD3. Install power filter
Failure to trip1. Excessively high current setting1. Check current setting1. Set current to 0.9 times rated valueRegular contact inspection, Überlastung vermeiden
2. Beschädigte Ausgangskontakte2. Test contact continuity2. Replace contact module
3. Internal circuit failure3. Inspect internal components3. Contact after-sales service
Garbled display1. Spannungsschwankung1. Test power stability1. Install voltage stabilizerKeep away from inverters, ensure good grounding
2. Elektromagnetische Störungen2. Check grounding2. Optimize grounding
3. Program error3. Power cycle restart3. Restore factory settings

Wartungszyklus

  1. Daily inspection: Check display status and alarm indicator
  2. Monthly maintenance: Dust cleaning, tighten wiring terminals
  3. Quarterly calibration: Verify protection parameter accuracy
  4. Annual overhaul: Inspect internal components, replace aging parts
  5. Anwendungsszenarien & Cases

Anwendbare Szenarien

Industrielle Automatisierung: CNC-Werkzeugmaschinen, Förderer, Druckgeräte

Water treatment: Wasserpumpen, fans with frequent startup and variable load

HVAC: Air compressors, cooling tower fans

Building materials industry: Mixer, heavy-duty conveyors

Power system: Standby generators, small transformer protection

Non-recommended Scenarios

High voltage motors (>690V): Adopt dedicated high-voltage protectors

Explosion-proof environment: Extra explosion-proof housing required with higher cost

Ultra-low current (<0.5A): Choose EOCRSSD-05S or match external CT

Typische Fälle

Fall 1: Water Pump Motor Protection in Steel Plant

Problem: Frequent false tripping of old thermal relays causing unplanned shutdowns without fault identification

Lösung: Install EOCRSSD-30DF7, set current 15A (motor rated 13.5A), start delay 5s

Wirkung: False shutdown rate reduced by 62%, fault diagnosis time shortened from 2h to 5min, annual maintenance cost saved about 80,000 CNY

Fall 2: Mixer System in Pharmaceutical Factory

Problem: Motor burnout caused by mixer locked rotor leading to heavy losses

Lösung: Adopt EOCRSSD-30DF7, set locked rotor protection (D-Time=3s, O-Time=1s)

Wirkung: Power cut within 3s once locked rotor occurs, 100% motor intact rate, avoid production stop losses

  1. Auswahlregeln

Schnellauswahlregeln

  1. Aktuelle Übereinstimmung: Set protection current within 0.9~1.1 times motor rated current
  2. Delay setting: Start delay (D-Time) = actual motor startup time + 1 zweite
  3. Stromversorgung: Prioritize matching on-site control power to avoid extra transformer cost
  4. Display demand: Choose D-type for fault diagnosis, non-D-type for basic protection only
  5. Luftfracht-Compliance & Zertifizierungen
  6. Air Freight Regulation

No built-in lithium batteries or supercapacitors, fully compliant with UN38.3 air transport standards

Can be delivered as general goods, no MSDS or special shipping documents needed

Packaging suggestion: Anti-static bag + hard carton to prevent vibration damage

  1. Qualification Certificates

CE: Comply with EU LVD & EMV-Richtlinien

UL: Meet US safety standards for North America market

CSA: Certified for Canadian market

IEC: Conform to international electrical standards for global use

Vorher:

Nächste:

Hinterlassen Sie eine Antwort

Eine Nachricht hinterlassen