ABB T6N800-TM800-40000-8000-F-F-3P - Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien

Leistungsschalter/

ABB T6N800-TM800-40000-8000-F-F-3P

This is an ABB SACE Tmax T6N 800A MCCB equipped with a TMA800/4000-8000 adjustable thermomagnetic release, 3-Pole, fixed mount, front connection, with N-type breaking capacity (36kA@400V). It is used as a main switch in industrial main circuits, heavy-duty motor protection, and power distribution systems. Full Model Code Breakdown Section Marking Description Technical Note 1 T6 ...

  • Produktdetails

This is an ABB SACE Tmax T6N 800A MCCB equipped with a TMA800/4000-8000 adjustable thermomagnetic release, 3-Pole, fixed mount, front connection, with N-type breaking capacity (36kA@400V). It is used as a main switch in industrial main circuits, heavy-duty motor protection, and power distribution systems.

  1. Full Model Code Breakdown
SectionMarkingBeschreibungTechnical Note
1T6RahmengrößeTmax T series MCCB, max frame current 800A, compact design (depth 103.5mm)
2NSchaltleistungsklasseN‑type standard breaking capacity: 36kA@400V/415V, 25kA@500V, 20kA@600V
3800Frame rated currentMaximum rated current of the Leistungsschalter frame: 800A
4TM/TMARelease typeThermomagnetic Adjustable release – both overload (thermal) and short‑circuit (magnetic) protection are adjustable
5800Nennstrom (In)Continuous operating current: 800A
640000‑8000Instantaneous trip rangeI3 = 4000–8000A, adjustable short‑circuit instantaneous protection
7FMounting typeBehoben (non‑withdrawable)
8FConnection typeFrontanschluss
93PPolen3‑pole circuit breaker for three‑phase systems
  1. Wichtige technische Parameter
ArtikelWertBemerkungen
Product typeSACE Tmax T6N 800A MCCBFactory code: 1SDA060214R1
Bemessungsisolationsspannung (Ui)1000VMaximum continuous voltage for insulation parts
Rated impulse withstand voltage (Uimp)8kVCapability to withstand transient high voltage
Nennbetriebsspannung (Ue)690V undMax operating voltage
Frequenz50/60HzFor standard mains systems
Trip characteristicAdjustable thermomagneticÜberlast (Umkehrzeit), short‑circuit (augenblicklich)
Ultimate breaking capacity (Icu)36kA@400VN class
25kA@500V
20kA@600V
Service breaking capacity (ICs)100% IcuReusable after tripping
Nennstrom (In)800AMaximum continuous current
Instantaneous trip range4000–8000AI3 = 5–10In, einstellbar
Abmessungen (mm)H×W×D: 268×210×103.5Uniform depth for panel layout
Gewichtca. 9kgStandard
Protection degreeIP30IEC 60529
  1. Typische Anwendungen
  2. Industrielle Stromverteilung

Main or sub-switch for 3-phase 800A circuits in factories, Werkstätten, Rechenzentren.

  1. Large motor protection

Three-phase induction motors up to approx. 400kW (380V)

Critical motor circuits requiring adjustable overload and short-circuit protection

  1. Building electrical

Main switchboards in commercial and high-rise buildings

Power circuits for HVAC, Pumps, and large equipment

  1. Renewable energy

Main switches in combiner boxes for PV and wind power systems

DC-side protection for energy storage (DC version required)

  1. Other heavy industries

Mining, ports, railways, and applications requiring high reliability and adjustable protection.

  1. Replacement Models

4.1 ABB Upgrades / Replacements

ErsatzmodellMain DifferenceAnwendung
T6S800 TMA800/4000‑8000 FF 3PBreaking capacity upgraded to S class (50kA@400V)Systems with higher short‑circuit current near transformers
T6L800 TMA800/4000‑8000 FF 3PBreaking capacity upgraded to L class (70kA@400V)Heavy industrial grids and large plants
T6N800 PR221DS‑LSI 800 FF 3PElectronic LSI release (Long / Short / Sofort)Complex systems requiring precise grading and selectivity
XT6N800 TMA800/4000‑8000 FF 3PNew‑generation Tmax XT, same dimensions, verbesserte LeistungSystem upgrades and new installations

4.2 Cross-Brand Equivalents

MarkeModellKey Matching ParametersNotizen
SchneiderNSX630N TM800D 3PIn=800A, Icu=36kA, thermomagneticNSX max frame 630A; 800A is special rating
Siemens3VA6880‑6EL32‑0AA0In=800A, Icu=36kA, 3P, thermomagnetic3VA series, similar performance
MitsubishiNF800‑CW 3PIn=800A, Icu=35kA, thermomagneticJapanese standard, suitable for Japanese equipment
DeltaPM800H‑3PIn=800A, Icu=36kA, thermomagneticCost‑effective industrial MCCB
  1. Auswahl & Application Notes
  2. Breaking capacity matching

Ensure short-circuit current ≤ 36kA@400V; otherwise use T6S/T6L.

Icu is only 20kA at 600V – use with caution.

  1. Release settings

Überlast (thermal): set to 1.0–1.1 × load rated current

Sofort (magnetic): set to 5–10 × In to avoid nuisance tripping while maintaining selectivity.

  1. Montage & Verdrahtung

Behoben, front connection; allow depth ≥ 103.5mm.

Use copper busbar/cable rated for 800A; ≥240mm² copper recommended.

  1. Wartung & replacement

Regularly verify release settings.

Inspect contacts after short-circuit tripping; replace if needed.

For upgrades, prefer T6S/T6L or XT6N to keep dimensions compatible.

  1. Abschluss

ABB T6N800-TM800-40000-8000-F-F-3P is a high-performance 800A MCCB with compact size, adjustable thermomagnetic protection, and standard breaking capacity. It is ideal for high-current three-phase circuits in industrial automation. Selection should consider system short-circuit current, protection requirements, and installation space. For better accuracy and selectivity, use higher-breaking versions or electronic releases.

Schneider Replacement for ABB T6N800-TM800-40000-8000-F-F-3P

Key Summary: The ABB T6N800 is an MCCB; Schneider’s NSX series is the best match. If you require an MT air circuit breaker (ACB), suitable models are also available. Full solutions and technical comparisons below.

  1. Product Type Comparison
TypABBSchneider Corresponding SeriesMain Difference
MCCBT6N800NSX SeriesCompact, 36–150kA, for sub‑circuits
ACBNo equivalent in Tmax T6MT SeriesLarger, 50–200kA, for main incomers
  1. Schneider MT ACB Replacement

2.1 Recmmended Model: MT08N1 3P F MIC2.0+LR 800A

Model explanation:

MT08: Frame size 800A

N1: Breaking capacity 50kA@400V (higher than T6N 36kA)

3P: 3-Pole

F: Fixed mount

MIC2.0+LR: Thermomagnetic protection (Long + Sofort)

800A: Nennstrom

Parameter matching:

ArtikelABB T6N800Schneider MT08N1Match Level
Nennstrom (In)800A800APerfect
MontageBehobenBehobenPerfect
Polen3P3PPerfect
Bruchkapazität (Icu)36kA@400V50kA@400VHigher
Release typeThermomagnetisch (TMA)Thermomagnetisch (LR)Functional match
Instantaneous range4000–8000A (5–10 Zoll)5–10In adjustablePerfect

Bestell-Nr: 63006 (MT08N1 3P F MIC2.0 800A)

2.2 Alternatives (Higher Breaking)

MT08N2 3P F MIC2.0+LR 800A: 50kA@400V, wider current range

MT08H1 3P F MIC2.0+LR 800A: 65kA@400V for heavy short-circuit systems

  1. Better Schneider NSX MCCB Replacement

3.1 Recommended Model: NSX800F TMD 800 3P3D F

Model explanation:

NSX800: Frame 800A

F: 36kA@400V (identical to T6N)

TMD: Thermomagnetic release (distribution type)

800: Nennstrom 800A

3P3D: 3-Pole

F: Behoben, front connection

Parameter matching:

ArtikelABB T6N800Schneider NSX800FMatch Level
TypMCCBMCCBPerfect
In800A800APerfect
Icu36kA@400V36kA@400VPerfect
MontageBehobenBehobenPerfect
VerbindungFrontFrontPerfect
Polen3P3PPerfect
ReleaseTMATMDPerfect
Sofort5–10 Zoll5–10 ZollPerfect

Bestell-Nr: C80F3TM800

3.2 Higher-Breaking Alternatives

NSX800N TMD 800 3P3D F: 50kA@400V, order No C80N3TM800

NSX800H TMD 800 3P3D F: 70kA@400V for heavy industry

  1. Replacement Selection Notes
  2. Product type choice

For direct replacement of an MCCB, choose NSX for identical form factor.

For upgrading to a main incomer, use MT ACB (note larger dimensions).

  1. Release settings

Long-delay (Und): 1.0–1.1 × rated current

Sofort (Ii): 5–10 × In (4000–8000A) to match original ABB behavior.

  1. Bruchkapazität

MT08N1, NSX800N/H exceed 36kA for improved safety.

NSX800F is sufficient if Isc ≤ 36kA.

  1. Mounting space

MT ACB depth ~300mm (much larger than T6N 103.5mm)

NSX matches T6 dimensions for easy retrofit.

  1. Zusammenfassung

Top Recommendation: Schneider NSX800F TMD 800 3P3D F (order No C80F3TM800).

Perfectly matches the ABB T6N800 in type, aktuell, mounting, Ausschaltvermögen, and characteristics, with near-identical dimensions for easy replacement.

Alternative: If ACB is required, use MT08N1 3P F MIC2.0+LR 800A (order No 63006), which provides higher breaking capacity but requires more space.

Let me know if you want a simplified 1-page English datasheet version for customers or bidding.