ABB MS116-4.0 MPCB - Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-Mail: kent@bestcontactor.com

Um Kontakt |

ABB MS116-4.0 MPCB - Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien

Leistungsschalter/

ABB MS116-4.0 MPCB

ABB MS116-4.0 Technical Datasheet (Manual Motor Starter / Motor Protection Circuit Breaker) Key Overview: 3-Pole, rated current 4.0A (adjustable 2.5~4.0A), Class 10A tripping, 50kA/400V breaking capacity, suitable for 1.5kW/400V AC-3 motors, 45mm DIN-rail mounting, Schutzart IP20, global order number 1SAM250000R1008. Model Explanation Model Part Description MS116 ABB MS116 series compact 3-pole manual motor starter, integrated ...

  • Produktdetails

ABB MS116-4.0 Technical Datasheet (Manual Motor Starter / Motor Protection Circuit Breaker)

Key Overview: 3-Pole, rated current 4.0A (adjustable 2.5~4.0A), Class 10A tripping, 50kA/400V breaking capacity, suitable for 1.5kW/400V AC-3 motors, 45mm DIN-rail mounting, Schutzart IP20, global order number 1SAM250000R1008.

  1. Modellerklärung
ModellteilBeschreibung
MS116ABB MS116 series compact 3-pole manual motor starter, integrated thermal-magnetic protection (Überlast + Kurzschluss + Phasenausfall), fuse-free design
4Rated operational current Ie = 4.0A, adjustable range 2.5~4.0A
1SAM250000R1008Global order code
Abmessungen / MontageWidth 45mm, standard 35mm DIN rail mounting, IP20 degree of protection
  1. Core Electrical & Mechanical Data

2.1 Basic & Protection Parameters

ParameterWertBeschreibung
Number of poles3-PoleFor three-phase motor protection
Rated current Ie4.0AAdjustable range 2.5~4.0A
Tripping classKlasse 10ATypical motor tripping characteristic; trips in approx. 10 s at 10 overload current
Kurzschlussschutz50A (fixed)Instantaneous magnetic trip, no extra fuse required
Breaking capacity Ics50Die (400V und)Rated service short-circuit breaking capacity
Nennspannung690V und, 50/60HzSuitable for various voltage systems
Applicable power (AC-3)1.5kW (400V) / 2 hp (480V)For standard motor duty
Protection functionsTemperature compensation, fuse-free protection, free tripping mechanism, isolation function, phase failure protectionComprehensive motor protection, IEC compliant

2.2 Mechanisch & Mounting Data

  1. ParameterWert
    Breite45mm
    Höhe90mm
    Tiefe85.6mm
    Gewicht0.225kg
    MontageStandard 35mm DIN rail (TH35-15/TH35-7.5)
    VerbindungSchraubklemmen, main circuit torque 0.8~1.2Nm
    BetriebDrehgriff (clear ON/OFF indication), free tripping mechanism
    Degree of protectionIP20 (front)
    Stromverbrauch5.4W
    Umgebungstemperatur-25C≈+55C

    Auswahlhilfe

3.1 Typische Anwendungen

Direct starting and protection of small three-phase motors (1.5kW/400V)

Control of pumps, Fans, compressors and industrial automation equipment

Replacement of traditional “fuse + contactor” combinations to save space and cost

Applications requiring manual control and reliable motor protection

3.2 Selection Steps

  1. Verify motor rated current: within 2.5~4.0A adjustable range
  2. Check motor power: ≤ 1.5kW (400V AC-3)
  3. Confirm system voltage: ≤ 690V AC, 50/60Hz
  4. Evaluate short-circuit current: system short-circuit current ≤ 50kA (400V)
  5. Installation space: reserve 45mm DIN rail width
  6. Umgebungsbedingungen: temperature -25°C ~ +55°C, no excessive vibration or corrosive gas

3.3 Einstellung & Operation Notes

Überlastschutz: set to 1.0~1.1 × motor rated current (within 2.5~4.0A)

Ensure reliable phase failure protection for all three-phase motor applications

Use isolation function: safe electrical isolation after shutdown for maintenance

Can be used with contactors for remote control and automatic protection

  1. Cross-Brand Replacement Models
MarkeModellHauptparameterDifferences
SchneiderGV2ME083-Pole, 2.5~4.0A, Klasse 10, 50kA/400VSame width (45mm), functionally compatible, Direkter Ersatz
Siemens3RV2011-0JA103-Pole, 2.5~4.0A, Klasse 10, 50kA/400VMatching mounting dimensions, compatible protection characteristics
EatonPKZM0-43-Pole, 2.5~4.0A, Klasse 10, 50kA/400VFunctionally and dimensionally compatible, kostengünstig
ABB UpgradeMS132-4.03-Pole, 2.5~4.0A, Klasse 10, 100kA/400VHigher breaking capacity, backward compatible mounting
  1. Application Notes
  2. Thermal-magnetic characteristics: Class 10A is intended for standard squirrel-cage motors; not recommended for special loads (z.B., Transformatoren, Kondensatoren)
  3. Phasenausfallschutz: Trips within 2~5 seconds if any phase is lost, effectively preventing motor burnout
  4. Fuse-free design: Eliminates external fuses, reduces cost and maintenance; ensure line short-circuit current ≤ 50kA
  5. Free tripping mechanism: Forces tripping under overload/short-circuit even in ON position, Gewährleistung der Sicherheit
  6. Temperature compensation: Protection characteristics stable over ambient temperature range -25°C ~ +55°C