PVA-KL26 Digital Signal Module - Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-Mail: kent@bestcontactor.com

Um Kontakt |

PVA-KL26 Digital Signal Module - Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien

elektrisch/

PVA-KL26 Digital Signal Module

PVA-KL26: KOPPEN & LETHEM Digital Signal Module / Relay Module The PVA-KL26 is a 12/24 VDC digital signal module / relay module manufactured by KOPPEN & LETHEM of the Netherlands. It is widely used in industrial control and marine applications, integrating a plug-in LED status indicator and RC circuit (for arc suppression and voltage transient ...

  • Produktdetails

PVA-KL26: KOPPEN & LETHEM Digital Signal Module / Relay Module

The PVA-KL26 is a 12/24 VDC digital signal module / relay module manufactured by KOPPEN & LETHEM of the Netherlands. It is widely used in industrial control and marine applications, integrating a plug-in LED status indicator and RC circuit (for arc suppression and voltage transient protection).

Kernfunktionen

ParameterSpezifikation
HerstellerKOPPEN & LETHEM (sometimes associated with Doedijns)
Betriebsspannung12/24 VDC (wide‑voltage design)
KernfunktionenSignal conversion, switching control, Statusanzeige
Key ComponentsPlug‑in LED indicator, RC circuit (arc suppression)
Mounting StylePlug‑in design for quick installation, removal and maintenance
AnwendungsfelderIndustrielle Automatisierung, ship control systems, hydraulic equipment control

Product Advantages

  1. Intuitive Status Monitoring: LED indicator displays real-time operating status, reducing the risk of misoperation
  2. Circuit Protection: Built-in RC circuit effectively suppresses arcing and voltage transients, extending service life
  3. Easy Installation: Plug-in design saves maintenance time and cost
  4. Umweltanpassungsfähigkeit: Suitable for harsh industrial and marine environments

Typische Anwendungen

The PVA-KL26 is commonly used for:

Signal conversion and control in marine automation systems

Remote control circuits for hydraulic machinery

Status monitoring and alarm systems for industrial equipment

Relay contact protection and signal amplification

Notizen

  1. Ensure the supply voltage is within 12-24 VDC to avoid overvoltage damage
  2. Observe correct polarity during installation to prevent damage to the LED indicator and internal circuits
  3. The RC circuit must be matched to the load for optimal arc suppression
  4. For use in dry, dust-free environments only; additional protection is required in humid conditions

PVA-KL26 Detailed Technical Specification Manual

(KOPPEN & LETHEM Digital Signal / Relay Module)

The PVA-KL26 is a 12/24 VDC digital signal module / relay interface module specially designed by KOPPEN & LETHEM (Niederlande) for industrial and marine environments. It integrates status indication and arc suppression functions, ideal for signal conversion and control under harsh operating conditions.

  1. Core Electrical Parameters
ParameterWertBemerkungen
Betriebsspannung12/24 VDC (wide‑voltage compatible)Polarity protection, reverse‑connection resistant
Control Input Signal24 VDC logic levelCompatible with standard PLC digital outputs
Kontaktbewertung2 A @ 24 VDC / 1 A @ 250 VACResistive load; derate for inductive loads
LED IndicatorPlug‑in red LEDLights up when powered, clear status visibility
RC Arc Suppression CircuitBuilt‑in standard RC networkSuppresses contact arcing and voltage transients, extends contact life
Insulation Resistance≥ 100 MΩ (bei 500 VDC)Between input‑output‑ground
Spannungsfestigkeit1500 VAC for 1 MinuteBetween input‑output‑ground
Stromverbrauch< 1 WLow power, für den Dauerbetrieb geeignet
  1. Mechanisch & Physikalische Eigenschaften
ParameterWertBemerkungen
MontageStandard 35 mm DIN rail mountingSnap‑in design for easy installation/removal
Module DimensionsW 22.5 mm × H 90 mm × D 60 mmStandard DIN rail module size
GewichtCa. 80 GLightweight, saves cabinet space
Connector TypePlug‑in terminal blockAccepts 2.5 mm² wire, tool‑free wiring
Schutz vor EindringenIP20For indoor control cabinet use
GehäusematerialFlame‑retardant ABS plasticUL94 V‑0 rated, high fire resistance

III. Umweltfreundlich & Operating Conditions

ParameterWertBemerkungen
Betriebstemperatur−25 °C ~ +70 °CWide temperature range for marine/industrial use
Lagertemperatur−40 °C ~ +85 °CSafe storage under extreme temperatures
Relative Luftfeuchtigkeit5% ~ 95% (nicht kondensierend)Adaptable to high‑humidity marine environments
Vibration & ShockIEC 60068‑2‑6 / IEC 60068‑2‑27Complies with marine and industrial anti‑vibration standards
EMVIN 55011 / EN 61000‑6‑2Immune to electromagnetic interference, suitable for industrial automation
  1. Pin Configuration & Wiring Definition

(Standard 6-pin terminal block)

Pin No.Function DefinitionWiring Description
1V+ (Positive Power)Connect to 12/24 VDC positive
2V− (Negative Power)Connect to 12/24 VDC negative / GND
3IN (Signal Input)Connect to control signal (24 VDC active high)
4COM (Common)Relay contact common terminal
5NEIN (Normalerweise geöffnet)Closed when relay is energized
6NC (Normalerweise geschlossen)Closed when relay is de‑energized
  1. Detailed Functional Features
  2. Arc Suppression Technology

Built-in RC snubber circuit (Standard: 100 Oh / 0.1 μF) absorbs back EMF from inductive loads at contact break, effectively suppressing arcing and extending contact life by 3-5 mal.

  1. Status Monitoring System

Red LED provides real-time module status indication

Simple fault diagnosis: LED off = power fault; LED on but no contact action = internal circuit fault

  1. Sicherheitsdesign

Polarity protection prevents damage from reverse power connection

Overcurrent protection guards against output short circuits

Surge voltage suppression protects internal electronic components

  1. Application Limitations & Notizen

Load Type Adaptation

Induktive Lasten (Motoren, solenoid valves): recommended derating to 50% of rated value

Capacitive loads (Kondensatoren, Lampen): current-limiting resistor required to prevent inrush current

Installationsspezifikationen

Avoid installation near heat sources (> 70 °C)

Maintain at least 5 mm clearance around the module for heat dissipation

Ensure secure wire crimping during wiring to prevent poor contact

Wartungsrichtlinien

Regularly check LED status and terminal tightness

Insulation test recommended every 6 months in harsh environments

Replace the entire module if faulty; internal repair is not recommended

VII. Alternative Modelle & Kompatibilität

Alternatives ModellMarkeCompatibility Description
PVA‑KL26‑EXKOPPEN & LETHEMIntrinsically safe version for hazardous areas
RM22UA02Schneider ElectricFunktionell kompatibel, slight dimensional differences
DILM25‑10SiemensHigher contact capacity, usable as alternative

PVA-KL26 Standard Pin / Terminal Configuration

This module uses a 6-pin plug-in screw terminal block.

When facing the front of the module with terminals downward, terminal numbers are 1 Zu 6 from left to right.

Terminal No.MarkingFunktionsbeschreibung
1IN+Positive digital control signal input (24 VDC)
2IN−Negative signal input / common ground
3V+Positive operating power (12/24 VDC)
4V−Negative operating power / GND
5NEINNormally open relay output contact
6COMRelay contact common terminal

Important Notes

  1. This model has only NO (normalerweise offen) Kontakte, no NC (normalerweise geschlossen)
  2. Input with reverse polarity protection; LED lights when IN+ is active
  3. Built-in RC snubber on output allows direct driving of inductive loads such as solenoids and coils
  4. Terminal suitable wire cross-section: 0.5-2.5 mm²

Vorher:

Nächste:

Hinterlassen Sie eine Antwort

Eine Nachricht hinterlassen