Schneider 3CT-H1-100-C Stromwandler

Vollständige Spezifikation des Stromwandlers Schneider 3CT-H1-100-C (Speziell für EOCR) Model Code Interpretation Code Segment Meaning Description 3CT Product Series Three-phase combined current transformer, customized for Schneider EOCR motor protector, manufactured by SAMWHA Korea H1 Specification Code Primary current rating 100A, circular aperture, applicable for cable outer diameter ≤25mm 100 Rated Primary Current 100A (numerator ...

  • Produktdetails

Full Specification of Schneider 3CT-H1-100-C Stromwandler (Speziell für EOCR)

  1. Interpretation des Modellcodes
CodesegmentBedeutungBeschreibung
3CTProduktserieThree-phase combined current transformer, customized for Schneider EOCR motor protector, manufactured by SAMWHA Korea
H1SpezifikationscodePrimary current rating 100A, circular aperture, applicable for cable outer diameter ≤25mm
100Bewerteter Primärstrom100A (numerator of transformation ratio)
CMounting/Terminal TypeTerminal block type; Z stands for direct lead wire type

Quick Identification: 3CT-H1-100-C = Three-phase 100/5A circular-aperture current transformer with terminal block, exclusive for EOCR

  1. Technische Kernparameter
ParameterkategorieSpezifikationBemerkung
Transformation Ratio100A/5AStandard secondary current 5A, compatible with full EOCR series
GenauigkeitsklasseKlasse 1Measuring tolerance ±1%, meets protection and metering requirements
Rated Burden10VAMax permissible secondary loop impedance 200mΩ
Frequenzbereich50/60HzGeneral industrial frequency
BemessungsisolationsspannungWechselstrom 600 VMaximum continuous operating voltage
Spannungsbeständig2kV (50Hz, 1min)Insulation test standard between windings and earth
Isolationswiderstand≥100 MΩ (DC 500V)Measured by megohmmeter
Aperture SizeCircular φ25mmStandard bore of H1 series
GesamtdimensionW150×H71×D55mmKompakte Struktur, space-saving installation
MontageartPanelmontageCompatible with standard 35mm DIN rail
MaterialFlame-retardant engineering plasticCompliant with UL94 V0 standard
GewichtCa. 0.58kgSingle unit weight
ZertifizierungCE, ULConforms to international safety standards
Bestellnummer3CT-H1-100-CExclusive official Schneider order code
  1. Full Model List (EOCR 3CT Series)
ModellVerhältnisAperture ShapeBore SizeNennstromMontageart
3CT-HS-75-C/Z75/5ACircularφ22mm75AC=Terminal block, Z=Lead wire
3CT-H1-100-C/Z100/5ACircularφ25mm100AC=Terminal block, Z=Lead wire
3CT-HH-150-C/Z150/5AQuadrat30×30mm150AC=Terminal block, Z=Lead wire
3CT-H2-200-C/Z200/5AQuadrat35×35mm200AC=Terminal block, Z=Lead wire
3CT-H3-300-C/Z300/5AQuadrat45×45mm300AC=Terminal block, Z=Lead wire
3CT-H4-400-C/Z400/5AQuadrat55×55mm400AC=Terminal block, Z=Lead wire
  1. Cross-brand Alternative Comparison
MarkeModellVerhältnisGenauigkeitBurdenApertureKompatibilität
Schneider

(SAMWHA)

3CT-H1-100-C100/5AKlasse 110VAφ25mmPerfect match for EOCR
Siemens5SD7410-7100/5AKlasse 110VAφ25mmUniverseller Typ, adaptation test required
ABBCT-AR/100100/5AKlasse 115VAφ25mmHigher burden capacity, EOCR compatible
ChintBH-0.66/100100/5AKlasse 110VAφ25mmCost-effective domestic alternative
LeckerLMZ1-0.66/100100/5AKlasse 110VAφ25mmInländischer Ersatz, minor dimension difference

Ersatzhinweise

  1. Ensure secondary burden capacity ≥10VA for non-Schneider products to guarantee protection precision
  2. Aperture shall match cable outer diameter; H1 series fits cables below 25mm
  3. Calibrate transformation ratio and phase for alternative models
  4. Fehlerbehebung & Wartung
FehlerphänomenMögliche UrsachenInspektionsschritteLösungen
No secondary outputFalsche Verkabelung, winding open circuit, loose terminalsCheck S1/S2 polarity; test secondary resistance; fasten terminalsCorrect wiring polarity; replace faulty CT; reinforce terminals
Large measuring deviationOverloaded circuit, mismatched ratio, core saturationCalculate loop impedance; verify ratio; check overload currentReduce circuit burden; replace matched model; upgrade CT specification
EOCR false trippingPhase shift, harmonic interference, CT saturationTest three-phase phase difference; check frequency converter interference; monitor surge currentRecalibrate phase; install harmonic filter; adopt high-saturation CT
IsolationsfehlerDampness, Alterung der Isolierung, mechanical damageMeasure insulation resistance; inspect shell cracks; test winding insulationDry or replace unit; renew CT; repair damaged parts

Safety Rules

  1. Never test open secondary circuit; short-circuit S1/S2 beforehand to avoid high voltage hazard
  2. Check load and wiring preferentially when deviation exceeds ±2%
  3. Replace CT immediately if insulation resistance below 10MΩ
  4. Anwendung & Cases

Anwendbare Szenarien

EOCR motor protection system: Überstrom, undercurrent and phase loss protection

Niederspannungs-Stromverteilung: Current monitoring and protection for circuits below AC 600V

Motor control center: Compact layout saves cabinet space

Industrielle Produktionslinien: Heavy-duty equipment protection in steel, cement and automobile industry

UPS feeder in data center: Precise current monitoring

Inadmissible Scenarios

Long-term operating current over 120A causing core saturation

High frequency (>400Hz) or DC circuits with poor measuring accuracy

Outdoor installation without waterproof enclosure

Secondary circuit burden exceeding 10VA

Typische Fälle

Fall 1: Motor Protection in Automobile Workshop

3 sets of 55kW three-phase asynchronous motors equipped with EOCR-3E protector. Model 3CT-H1-100-C is selected. It realizes overcurrent trip and rapid phase loss protection, cutting down failure rate by 40%.

Fall 2: Crane Control Cabinet Renovation

Replace old split CT with combined 3CT-H1-100-C, sparen 50% Installationsraum, simplifying wiring and improving operational reliability.

  1. Auswahl & Installationsrichtlinien

Three-step Selection Method

  1. Calculate current: Multiply rated motor current by 1.1 overload factor
  2. Select aperture: Choose circular or square bore according to cable size
  3. Confirm terminal type: Terminal block for cabinet wiring, lead wire for field wiring

Vorsichtsmaßnahmen bei der Installation

Keep correct S1(Ich+) and S2(ICH-) connection to prevent false operation

Strictly prohibit open secondary circuit during installation and maintenance

Total secondary loop impedance shall not exceed 200mΩ

Insulation resistance shall be no less than 100MΩ before commissioning

Wartungsplan

ArtikelZyklusStandard
SichtprüfungMonatlichNo crack, looseness or overheating mark
Terminal tighteningVierteljährlichTorque range 2-3N·m
IsolationstestYearlyResistance ≥100MΩ
Ratio calibrationBienniallyTolerance ≤±1%

Schneider 3CT-H1-100-C is a dedicated three-phase 100/5A combined current transformer for EOCR motor protectors. Featuring Class 1 Genauigkeit, 10VA rated burden and compact design, it is widely applied in low-voltage motor protection and power monitoring. Match current, aperture and terminal type properly, and comply with polarity and open-circuit prohibition rules to ensure stable system operation.