Schneider Easy9 series 4‑pole 63A C‑curve Miniatur-Leistungsschalter, used for overload and short‑circuit protection in three‑phase four‑wire distribution systems. DIN‑rail mountable, suitable for final distribution in residential, commercial and light industrial applications.
1 Model Explanation
| Teil | Bedeutung |
| EA9AN | Easy9 series standard MCB |
| 4 | 4 Stangen (3 phases + N), all poles with protection function |
| C | C tripping curve (5–10In instantaneous trip), suitable for lighting and resistive/slightly inductive mixed loads |
| 63 | Rated current 63A (at 30°C ambient) |
2 Wichtige technische Parameter
| Parameter | Wert | Beschreibung |
| Rated operational voltage | 230/400V und | Suitable for single‑/three‑phase systems |
| Rated insulation voltage | 400V und | – |
| Rated frequency | 50/60Hz | Universal frequency |
| Rated breaking capacity | 6Die (400V) | Standard breaking capacity for general distribution |
| Tripping type | Thermal‑magnetic | Thermal overload protection + magnetic short‑circuit protection |
| Tripping curve | C‑curve | Instantaneous trip range: 5–10 Zoll, moderate inrush current withstand |
| Number of poles | 4P | 4 protected poles, neutral on the left |
| Montage | 35mm DIN rail | Standard electrical cabinet mounting |
| Electrical endurance | 10,000 Operationen | Rated operating cycles |
| Mechanical endurance | 20,000 Operationen | Mechanical operating cycles |
| Abmessungen | Approx. 85mm×78.5mm×18mm (4‑pole width) | Standard 4‑pole MCB size |
| Standards | GB16917/IEC60898 | National and international standards |
3 Kernfunktionen & Merkmale
- Überlastschutz: Thermal trip unit acts with current‑time accumulation to prevent overheating and burnout.
- Short‑circuit protection: Magnetic trip unit operates instantaneously (<0.1S) to clear short‑circuit current and protect equipment and wiring.
- Isolation function: Complies with EN/IEC 60947‑2, can be used as an isolating device.
- Quick make: Internal mechanism ensures fast circuit closing.
- Operation indication: Clear ON/OFF status indication for easy maintenance.
- Safety design: Anti‑misoperation structure, high insulation performance, safe and reliable.
4 Typische Anwendungen
Residential distribution: Main incoming breaker for three‑phase four‑wire homes, protecting the entire electrical system.
Commercial buildings: Floor or zone main breaker in offices, shopping malls, Hotels, usw.
Light industry: Branch circuit protection for workshops and production lines, suitable for mixed motor, lighting and socket loads.
Final distribution: Dedicated protection for three‑phase equipment (Klimaanlagen, Pumps, small machine tools).
5 Cross‑Brand Replacement Reference
| Brand | Ersatzmodell | Notizen |
| ABB | S204‑C63 | Same 4P C63A, 6kA-Ausschaltvermögen |
| Siemens | 5SY6463‑7CC | 4P C63A, standard breaking capacity |
| CHINT | NXB‑63 4P C63 | Domestic alternative, cost‑effective |
| Lecker | CDM30s‑63 4P C63 | Similar performance, compatible with domestic panels |
| Schneider upgrade | A9F94463 (Acti9-Serie) | Breaking capacity up to 15kA, verbesserte Leistung |
6 Installation & Auswahlnotizen
- Installation precautions
Must be mounted on 35mm standard DIN rail, installation depth ≥78.5mm
Terminal suitable for copper conductors: 1.5–35mm²
Neutral must be connected to the designated left terminal – do not reverse.
- Selection recommendations
Total three‑phase load current ≤63A, suitable for C‑curve loads (not heavy motor starting).
For distribution systems with short‑circuit current >6Die, upgrade to higher breaking capacity models (z.B., Acti9-Serie).
Derate at ambient temperature >30°C: current reduced by 1% per °C rise.
Schneider EA9AN4C63 vs Acti9 A9F94463 Full Comparison & Upgrade Recommendation
At a glance: A9F94463 (iC60L series) is superior to EA9AN4C63 in breaking capacity, compactness, accessory expandability, and electrical/mechanical endurance, suitable for higher short‑circuit risk and higher reliability/expandability requirements.
EA9AN4C63 is more economical and meets basic protection for standard residential and light commercial use.
1 Core Parameter Comparison
| Parameter | EA9AN4C63 (Easy9) | A9F94463 (Acti9 iC60L) | Key Difference |
| Series positioning | Economic standard | High‑performance standard | A9 higher‑end, richer functions |
| Poles/Current/Curve | 4P / 63A / C‑curve | 4P / 63A / C‑curve | Basic specs identical |
| Rated breaking capacity | 6Die (400V) | 15Die (400V) | A9 ×2.5 higher, stronger short‑circuit withstand |
| Rated insulation voltage | 400V und | 400V und | Same |
| Rated operational voltage | 230/400V und | 230/400V und | Same |
| Tripping type | Thermal‑magnetic | Thermal‑magnetic | Same |
| Montage | 35mm DIN rail | 35mm DIN rail | Same |
| Abmessungen | 85mm×78.5mm×18mm (4P) | 85mm×44.5mm×18mm (4P) | A9 depth –43%, saves panel space |
| Wiring capacity | 1.5–35mm² (copper) | 1.5–35mm² (copper), dual tunnel terminals | A9 more secure, same conductor range |
| Electrical endurance | 10,000 | 15,000 | A9 +50% |
| Mechanical endurance | 20,000 | 25,000 | A9 +25% |
| Protection degree | IP20 | IP20 (terminal IP20B) | A9 better terminal protection |
| Accessory compatibility | Basic accessories (aux./shunt) | Full Acti9 range (aux., shunt, UVP, remote, usw.) | A9 more expandable, supports Ti24 |
| Standards | GB16917/IEC60898 | GB16917/IEC60898/IEC60947‑2 | A9 covers more standards |
| Price range | Approx. ¥150–200 | Approx. ¥350–500 | A9 ~2–2.5× EA9 price |
2 Detailed Performance Differences
2.1 Bruchkapazität: Core Safety Gap
EA9AN4C63: 6Die, suitable for general systems with short‑circuit current ≤6kA.
A9F94463: 15kA high breaking capacity, reliably clears higher short‑circuit currents, reduces arc risk.
Suitable for:
Industrial plants, large commercial buildings
Distribution circuits near transformers
Systems where short‑circuit current may exceed 6kA
2.2 Kompaktes Design: Better Space Utilization
A9F94463 depth only 44.5mm, greatly reduced from EA9AN4C63 78.5mm.
Benefits:
Fits slimmer distribution boards/cabinets
Spart Installationsraum, eases maintenance
Ideal for retrofit projects with limited space
2.3 Endurance & Zuverlässigkeit: Longer‑Term Stability
Electrical endurance from 10k → 15k operations; mechanical 20k → 25k.
A9 series uses higher‑grade materials and precision manufacturing for better long‑term stability.
Better vibration and impact resistance for harsh environments.
2.4 Accessory Expandability: Flexible Function Upgrades
EA9AN: Supports only basic auxiliary contacts and shunt trips.
A9F94463: Supports full Acti9 accessory range:
Multi‑function auxiliary / alarm contacts
Remote‑control shunt trips
Over/undervoltage protection modules
Auto‑reclose accessories
Ti24 interface for PLC/BMS integration
3 Upgrade Decision Guide
Recommended to upgrade to A9F94463 if:
- Calculated short‑circuit current >6Die
- Critical facilities: industrial, large commercial, hospital, data center
- Future expansion needed (Fernbedienung, voltage monitoring, usw.)
- Limited panel space requires compact solution
- Higher reliability and longer service life required to reduce maintenance cost
Recommended to keep EA9AN4C63 if:
- Standard residential / small shop loads, short‑circuit ≤6kA
- Budget‑sensitive, Kostenpriorität
- Basic protection only, no complex accessories
- Already installed EA9 panel with matching system parameters
4 Replacement Notes
- Direct interchangeability: Both 4P C63A, DIN‑rail mount – direct replacement.
- Wiring check: A9F94463 neutral position matches EA9AN (left) – no need to reorder wiring.
- Derating: Both derate at >30°C (–1% per °C).
- Accessory compatibility: Existing EA9 accessories must be replaced with Acti9‑specific versions.