Technische Spezifikationen & Application Guide This is a 2‑pole, Typ C, 25A miniature circuit breaker (MCB) aus der Acti9-Serie von Schneider Electric, with order code A9F18225 and rated breaking capacity 6kA. It provides overload and short‑circuit protection for lighting, socket, and small motor circuits in AC distribution systems. Features include 3‑stage current limiting, quick make mechanism, ...

  • Produktdetails

Technische Spezifikationen & Application Guide

This is a 2‑pole, Typ C, 25A Miniatur-Leistungsschalter (MCB) aus der Acti9-Serie von Schneider Electric, with order code A9F18225 and rated breaking capacity 6kA.

It provides overload and short‑circuit protection for lighting, socket, and small motor circuits in AC distribution systems.

Features include 3‑stage current limiting, quick make mechanism, and protection degree IP40 (front) / IP20 (Terminals).

It is compatible with iC65 series accessories for functional expansion.

  1. Model Breakdown
CodeBedeutungBeschreibung
SCHNEIDERMarkeSchneider Electric (France), global electrical equipment manufacturer
iC65NSerieActi9 iC65 MCB, N‑type breaking capacity (6Die)
2PNumber of poles2‑pole, breaks phase and neutral simultaneously, for 230V/400V systems
CAuslösekurveTyp C, instantaneous tripping at 5~10×In (5In~10In)
25ANennstrom25 amperes continuous at 30°C ambient
A9F18225Full order codeOfficial unique identifier
  1. Core Specifications
ArtikelSpezifikationNotizen
Basic
TypMiniatur-Leistungsschalter (MCB)Entspricht IEC 60898-1 / GB 10963.1
Tripping typeThermal‑magneticÜberlast (thermal) + short‑circuit (magnetic) Schutz
Bruchkapazität6DieMax breaking current at rated voltage
Rated operational voltageWechselstrom 230 V/400 VFor 2‑pole version
Bemessungsisolationsspannung500VMax withstand voltage of insulation
Rated impulse withstand voltage6kVSurge voltage immunity
Rated frequency50/60HzGlobal grid compatible
Auslöseeigenschaften
Überlastschutz1.13In (no trip in 1h), 1.45In (trip within 1h)Meets IEC requirements
Short‑circuit protectionInstantaneous at 5In~10InTyp C, zur Beleuchtung geeignet, resistive loads, small motors
Physical & environmental
Abmessungen (B×H×T)18mm×86mm×62mmStandard modular, 2P = 2 Module (18mm/pole)
Protection degreeIP40 (front), IP20 (Terminals)Solid object and moisture protection
Betriebstemperatur-35°C ~ +70°CSuitable for harsh industrial environments
Montage35mm DIN railStandard panel mounting
CertificationsCCC, CE, RoHSMeets Chinese and international safety & environmental standards
  1. Merkmale
  2. Protection performance

3‑stage current limiting: Quickly limits peak current during short circuit, reduces thermal stress, protects equipment and cables.

Selective protection: Coordinates with upstream breakers for selective tripping, limits fault area.

Fault indication: Red window shows tripped status for quick diagnosis.

  1. Structural advantages

Dual‑lock clip: Secures firmly on DIN rail, prevents vibration loosening.

Quick make mechanism: Improves closing speed, reduces arcing, extends life.

Modular design: Accepts auxiliary contacts, alarm contacts, shunt trip, undervoltage trip, usw.

  1. Safety design

Isolationsfunktion: Safe isolation distance in OFF position, meets electrical safety rules.

Anti‑misoperation: Handle design prevents accidental closing.

Flame‑retardant housing: V0 grade material improves cabinet safety.

  1. Installation & Wartung

Installationsregeln

  1. Mount vertically (±15°) for proper tripping.
  2. Verdrahtung: Copper 1.5~35mm², Aluminium 2.5~35mm², torque 1.2~4N·m (depends on cross‑section).
  3. Environment: Avoid damp, dusty, corrosive or high‑vibration locations.
  4. Spacing: Maintain clearance for heat dissipation; follow installation manual.

Maintenance Guide

ArtikelIntervalCriterionLösung
Visual inspectionMonatlichNo damage, no overheating, tight connectionsClean, tighten loose terminals
Function testVierteljährlichManual ON/OFF smooth, no stickingOperate 3–5 times, check mechanism
ReisetestJährlichÜberlast & short‑circuit protection functionalTest with dedicated equipment or simulate overload
Accessory checkJährlichAuxiliary & alarm contacts workingCheck contact condition, replace damaged parts

Fehlerbehebung

  1. Häufiges Stolpern: Check overload → short circuit → high ambient temperature → aging.
  2. Kann nicht geschlossen werden: Check short circuit → handle position → trip reset → loose wiring.
  3. Overheating: Check terminal torque → overload → ventilation.
  4. Upgrade & Ersatz

5.1 Same‑series Upgrades

iC65H-2P-C25A (A9F28225): H‑type, 10Die, for higher short‑circuit current.

iC65L-2P-C25A (A9F38225): L‑type, 15Die, for heavy industrial use.

iC65N-2P-C25A‑Vigi (A9V58225): With residual current protection (FI-Schutzschalter), prevents electric shock.

5.2 Functional Accessories

ZubehörTypisches ModellFunktion
HilfskontaktA9A269241NO+1NC, remote status indication
RangierfahrtA9X16224Fernauslösung, z.B., fire alarm
Undervoltage tripA9X16624Auto‑trip on low voltage
AlarmkontaktA9A27924Signal when breaker trips

5.3 Cross‑series Alternatives

SerieErsatzKompatibilität
Easy9EA9AN 2P C25ASame dimensions, 6Die, economical
Acti9 CVSCVS100B 2P C25AMCCB, höhere Bruchkapazität (10Die), main circuit use
Merlin GerinC65N 2P C25AFully compatible with iC65
  1. Anwendungen
  2. Gewerbebauten: Offices, Geschäfte, hotels – lighting & socket circuits.
  3. Industrial automation: Control panels, small motors (≤5.5kW), VFD input protection.
  4. Residential: Home distribution – air conditioners, Küchengeräte.
  5. Public facilities: Schools, hospitals, stadiums – electrical safety.
  6. Auswahl & Purchasing Tips
  7. Load matching: Type C for lighting, Steckdosen, small motors (≤5.5kW). Use Type B for pure resistive, Type D for large motors.
  8. Bruchkapazität: Choose N (6Die), H (10Die), L (15Die) based on system short‑circuit current.
  9. Polen: 2P for 230V single‑phase where phase + neutral must be disconnected.
  10. Zubehör: Add aux, shunt, undervoltage for smart systems.
  11. Authenticity: Buy from authorized Schneider distributors.
  12. Quick Fault Guide
SymptomMögliche UrsacheLösung
Trips immediately after closingKurzschluss / ÜberlastLocate short, reduce load or upsize breaker
Trips after running a whileÜberlast / hohe TemperaturReduce load, improve ventilation, check cable size
Handle cannot be pushed to ONNot reset / wiring faultPull to OFF first, then ON; check circuit
Terminal overheatingLoose connectionRetorque after power off, check terminals
No operationThermal‑magnetic unit failedReplace MCB, check coordination

SCHNEIDER iC65N-2P-C25A

Cross‑Brand Replacement Guide

Core Summary: The iC65N-2P-C25A (A9F18225) can be directly replaced by equivalent MCBs from major international and domestic brands.

Key matching requirements:

2P, Typ C, 25A, 6Die, 35mm DIN rail mounting.

  1. International Brand Direct Replacements

ABB

ErsatzOrder CodeBreakingKompatibilität
S202-C252CDS252001R02546DieBest match, same dimensions, direct swap
S202M-C252CDS262001R025410DieHigher breaking capacity
S202L-C252CDS242701R02544.5DieEconomy option

Siemens

ErsatzSerieBreakingKompatibilität
5SL6225-75SL6DieDirekter Ersatz, IEC 60898-1
5SY6225-75SY6DieEconomy range
5SN6225-7CN5SN6DieClassic, reliable

Eaton

ErsatzSerieBreakingKompatibilität
FAZ6-C25/2FAZ6DieSame dimensions & mounting
PL9-C25/2PL96DieHigh performance, fast limiting

Moeller

ErsatzSerieBreakingKompatibilität
FAZ6-C25/2FAZ6DieSame dimensions & mounting
PL9-C25/2PL96DieHigh performance, fast limiting
  1. Chinese Domestic Brands
MarkeErsatzBreakingKompatibilität
CHINTNXB-63-2P C256DieCost‑effective, direct fit
DELIXICDM3-63C25/2P6DieSame dimensions
LiangxinNDM1-63C25/2P6DieHigh quality domestic
TENGENTGM1-63C25/2P6DieGrundschutz, economical
  1. Critical Parameter Matching
ArtikelOriginal (iC65N-2P-C25A)Muss übereinstimmenEinstellbarNotizen
Polen2P2PDisconnect phase + neutral
CurveTyp C (5~10In)Typ CFor lighting & small motors
Aktuell25A25AContinuous rating
Breaking6Die≥6kACan be higher (10Die)Ensure safe short‑circuit interruption
Montage35mm DIN rail35mm DIN railStandard panel mount
Breite18mm18mmH/D may varyFits standard spacing
StromspannungWechselstrom 230 V/400 VWechselstrom 230 V/400 VUniversal AC system
  1. Ersatzhinweise & Best Practice

Before Replacement

System short‑circuit current ≤ breaking capacity of replacement.

35mm DIN rail, space, terminal size compatible.

Protection coordination with upstream/downstream devices.

Accessory mounting interface compatible.

Replacement has valid certifications (CCC, CE).

Verfahren

  1. Power off and verify voltage absence.
  2. Remove wiring and old breaker.
  3. Clip replacement onto DIN rail.
  4. Torque terminals correctly.
  5. Test ON/OFF and tripping.
  6. Update labeling and drawings.

When NOT to replace

Original uses dedicated Schneider accessories (z.B., Vigi modules).

System short‑circuit current exceeds replacement rating.

Load inrush >10In (unsuitable for Type C).

Extreme environment outside replacement specs.

  1. Recommended Replacement Levels
EbeneEmpfohlene ModelleAnwendungVorteil
1stABB S202-C25Industrie, commerceFull performance, global support
Siemens 5SL6225-7
2ndEaton FAZ6-C25/2Control panelsGood value, easy install
Moeller DIL M9-25 C/2
3rdCHINT NXB-63-2P C25Residential, economyLow cost, fast local supply
DELIXI CDM3-63C25/2P
  1. Common Issues & Lösungen
IssueUrsacheLösung
Frequent tripping after replacementWrong curve / ÜberlastConfirm Type C, check load, upsize if needed
Will not fitWrong rail / BreiteUse 35mm DIN rail, 18mm width model
Wiring difficultIncompatible terminalsUse suitable lugs or select compatible model
Insufficient breaking capacityErsatz < system short鈥慶ircuit currentUse higher version (z.B., ABB S202M-C25, 10Die)

Cross‑brand replacement for SCHNEIDER iC65N-2P-C25A depends on parameter matching + mechanical compatibility + protection coordination.

Top international brands (ABB, Siemens) give identical performance.

Domestic brands (CHINT, DELIXI) offer cost savings.

Always verify specifications and follow electrical safety standards.

Vorher:

Hinterlassen Sie eine Antwort

Eine Nachricht hinterlassen