Schneider MT08N1 3P 800A is a fixed 3-pole intelligent Luftleistungsschalter (ACB) belonging to the Masterpact MT series. It has a frame current and rated current of 800A, with an N1-class breaking capacity (50kA@400V). Suitable for incoming line/bus tie protection and power distribution in power distribution systems, it is commonly used in primary/secondary power distribution of industrial plants, large buildings and data centers. Below are the complete specifications and core details:
Technische Kernparameter
| Artikel | Parameter | Bemerkungen |
| Modell | MT08N1 3P 800A (Bestellcode: MT08N1) | MT series; 08=800A frame; N1=50kA breaking capacity |
| Serie | Masterpact MT (Offener Leistungsschalter) | Intelligent type, zero arcing, compatible with Micrologic control units |
| Polzahl | 3P | Three-phase power distribution, no neutral protection (4P optional) |
| Nennstrom (In) | 800A (at 40℃) | Long-term continuous current-carrying capacity |
| Rahmenstrom (Iu) | 800A | Maximum current adaptable to the breaker body |
| Nennbetriebsspannung (Ue) | 690V AC 50/60Hz | Isolationsspannung (Ui) = 1000V |
| Kurzschlussausschaltvermögen (Icu) | 50Die (400V und) | N1 class, konform mit IEC 60947-2 |
| Short-time Withstand Current (Icw) | 42kA/1s (400V) | Ability to withstand short-circuit impact |
| Making Capacity (Icm) | 105Die (440V und) | Ability to close short-circuit current |
| Impulse Withstand Voltage (Ump) | 12kV | Strong surge resistance |
| Control Unit | Compatible with Micrologic 2.0/5.0/6.0, usw. | Long-time delay/short-time delay/instantaneous/earth fault protection |
| Montagemethode | Behoben (F) / Drawout (D) | Standard dimensions for fixed 3P model: 301×276×196mm |
| Verkabelungsmethode | Front/back panel screw clamping terminals | Suitable for top/bottom cable entry |
| Operationsmethode | Elektrisch + manual (for maintenance) | Equipped with closing/opening buttons and status indicators |
| Mechanical/Electrical Service Life | 10,000 mechanical operations; 2,000 electrical operations (AC-3) | High durability |
| Zertifizierungen | CCC, IEC, UL, CSA, EAC | Green Premium compliant |
Kernfunktionen & Protection Features
- Full Intelligent Protection: Realizes long-time delay (Überlast), kurze Zeitverzögerung (Kurzschluss), augenblicklich (heavy short circuit) and earth fault protection via the Micrologic control unit. Parameters can be precisely set to adapt to cascade coordination in multi-level power distribution systems.
- Measurement & Monitoring: Displays real-time electrical parameters such as current, voltage and power, with fault memory and alarm output functions. Supports Modbus and other communication protocols, and can be integrated into SCADA systems.
- Design ohne Lichtbogenbildung: Optimized arc extinguishing chamber with zero arcing distance, improving cabinet safety and space utilization.
- Isolationsfunktion: Compliant with IEC 60947-2, can be used as an isolating switch (without controller).
Anwendungsszenarien & Wichtige Auswahlpunkte
– Typische Szenarien: Primary/secondary power distribution links such as incoming line cabinets of industrial plants, power distribution of large buildings, UPS output of data centers, photovoltaic/energy storage combiner boxes, usw. It is used for power distribution and short-circuit, Überlast, earth fault protection of lines/equipment.
– Key Selection Tips:
– Control Unit: 2.0 for basic protection; 5.0/6.0 with added measurement and communication functions, select according to requirements.
– Mounting Type: Fixed type is cost-effective; drawout type facilitates maintenance and allows breaker replacement without power outage.
– Bruchkapazität: N1 (50Die) meets general power distribution needs; upgrade to N2/H1/H2 class if short-circuit current is high.
Procurement & Replacement Recommendations
- Complete Order Specification: Must specify MT08N1 + control unit model + mounting method + Polzahl, z.B., MT08N1 F MIC 2.0 3P.
- Ersatzkompatibilität: Can directly replace MT08N2/H1 and other models with the same frame size. Dimensions differ from the NW series; verify cabinet installation space before replacement.
- Preisreferenz (December 2025): Domestic fixed type with MIC 2.0 control unit is approximately RMB 14,500-16,000 pro Einheit; drawout type is priced higher.
Breaking Capacity Comparison Table of Schneider Masterpact MT08 Series (800A)
| Artikel | MT08N1 3P 800A | MT08N2 3P 800A | MT08H1 3P 800A | MT08H2 3P 800A | Bemerkungen |
| Schaltleistungsklasse | N1 | N2 | H1 | H2 | N=Standard type; H=High breaking type |
| Rated Ultimate Short-circuit Breaking Capacity (Icu) @400V AC | 50Die | 70Die | 100Die | 150Die | Compliant with IEC 60947-2 |
| Rated Service Short-circuit Breaking Capacity (ICs) @400V AC | 50Die (100% Icu) | 70Die (100% Icu) | 100Die (100% Icu) | 150Die (100% Icu) | Can carry rated current continuously after breaking |
| Short-time Withstand Current (Icw) @400V AC/1s | 42Die | 50Die | 85Die | 120Die | Ability to withstand short-circuit impact |
| Making Capacity (Icm) @440V AC | 105Die | 147Die | 210Die | 315Die | Ability to close short-circuit current |
| Nennbetriebsspannung (Ue) | 690V und | 690V und | 690V und | 690V und | Isolationsspannung (Ui) = 1000V |
| Nennstrom (In) | 800A (at 40℃) | 800A (at 40℃) | 800A (at 40℃) | 800A (at 40℃) | Rahmenstrom (Iu) = 800A |
| Optional Pole Number | 3P/4P | 3P/4P | 3P/4P | 3P/4P | 4P with neutral protection |
| Montagemethode | Fixed/Drawout | Fixed/Drawout | Fixed/Drawout | Fixed/Drawout | Drawout type requires additional chassis |
| Compatible Control Units | Micrologic 2.0/5.0/6.0/7.0 | Micrologic 2.0/5.0/6.0/7.0 | Micrologic 2.0/5.0/6.0/7.0 | Micrologic 2.0/5.0/6.0/7.0 | 7.0 is a high-end measurement and control unit, supporting power quality analysis |
| Abmessungen (Fixed 3P, B×H×T) | 301×276×196mm | 301×276×196mm | 301×276×210mm | 301×276×225mm | High breaking types have slightly increased depth due to optimized arc extinguishing chambers |
| Mechanische Lebensdauer | 10,000 Operationen | 10,000 Operationen | 10,000 Operationen | 10,000 Operationen | Electrical service life: 2,000 Operationen (AC-3) |
| Preisreferenz (December 2025, Fester Typ + Micrologic 2.0) | RMB 14,500-16,000/unit | RMB 17,000-19,000/unit | RMB 22,000-25,000/unit | RMB 28,000-32,000/unit | Drawout type: 30%-40% price increase; imported model: um 50% price increase |
| Typische Anwendungsszenarien | General industrial plants, incoming line/bus tie of building power distribution | Medium-voltage distribution outgoing terminals, industrial scenarios with high short-circuit current | Heavy industrial plants, Rechenzentren, photovoltaic/energy storage combiner systems | Power grids with high short-circuit current, supporting large generator sets | Select according to grid short-circuit current level |
Complete Order Code Examples & Stocking Recommendations
- Complete Order Code Specification (4 Core Elements Required)
Ordering Schneider MT series requires specifying frame size + breaking capacity class + mounting method + control unit + Polzahl. Examples are as follows:
– MT08N1 F MIC 2.0 3P: 800A N1 class, fester Typ, Micrologic 2.0 control unit, 3-Pole
– MT08H1 D MIC 5.0 4P: 800A H1 class, Ausziehtyp, Micrologic 5.0 control unit, 4-Pole
- Stocking & Auswahlempfehlungen
- Select by Short-circuit Current
– First calculate the expected short-circuit current at the distribution point: choose N1 class (highest cost-performance) if ≤50kA; N2 class if 50-70kA; H1/H2 class if >70Die.
– For industrial plants close to substations with high short-circuit current, prioritize H1 class.
- Select by Operation & Maintenance Requirements
– Choose fixed type for general power distribution scenarios, featuring low cost and small space occupation;
– Choose drawout type for scenarios where power outage for maintenance is not allowed (z.B., Rechenzentren, hospitals), enabling live replacement of the breaker body.
- Select by Functional Requirements
| Control Unit Model | Kernfunktionen | Anwendbare Szenarien |
| Micrologic 2.0 | Grundschutz (long-time delay/short-time delay/instantaneous) | General power distribution without measurement and control requirements |
| Micrologic 5.0 | Schutz + electrical parameter measurement (current/voltage/power) | Buildings and factories requiring energy consumption monitoring |
| Micrologic 6.0 | Schutz + Messung + Kommunikation (Modbus/Profibus) | Intelligent power distribution systems requiring SCADA integration |
| Micrologic 7.0 | Volle Funktionen + power quality analysis (harmonics/unbalance) | Rechenzentren, precision manufacturing workshops |
- Stocking Recommendations
– For regular trade stocking, prioritize MT08N1 F MIC 2.0 3P, which adapts to 80% of general power distribution scenarios and ensures fast inventory turnover;
– For heavy industry customers, stock a small quantity of MT08H1 F MIC 5.0 3P to meet high short-circuit current requirements;
– Customize drawout models on demand; large-scale stocking is not recommended (high capital occupation and strong model specificity).
Core Parameter Comparison Table: Schneider MT08 Series vs. Chint NA8G-800 Series
(Both are 800A frame, 3-Pole, fester Typ, basic protection type, suitable for general power distribution scenarios)
| Vergleichsartikel | Schneider MT08N1 3P 800A (Micrologic 2.0) | Chint NA8G-800-3P-800A (Basic Trip Unit) | Core Difference Summary |
| Product Series Positioning | Masterpact MT series intelligent air circuit breaker | NA8G series air circuit breaker | Schneider focuses on intelligent measurement & Kontrolle + high reliability; Chint focuses on high cost-performance + localized adaptation |
| Rated Ultimate Short-circuit Breaking Capacity (Icu) @400V | 50Die | 40Die | Schneider’s breaking capacity is 25% higher, suitable for scenarios with high short-circuit current |
| Rated Service Short-circuit Breaking Capacity (ICs) @400V | 50Die (100% Icu) | 40Die (100% Icu) | Both support continuous operation after breaking; Schneider has higher redundancy |
| Short-time Withstand Current (Icw) @400V/1s | 42Die | 31.5Die | Schneider has stronger short-circuit impact resistance, suitable for heavy-duty industrial scenarios |
| Schutzfunktionen | Long-time delay/short-time delay/instantaneous three-stage protection; expandable earth fault protection | Long-time delay/short-time delay/instantaneous three-stage protection; earth fault protection requires customization | Basic protection is consistent; Schneider offers more flexible expansion functions |
| Measurement & Control Capability | Supports electrical parameter display (current/voltage); can be equipped with communication modules for SCADA integration | Basic protection only, no measurement and control functions; measurement supported only by upgraded models (NA8G-800M) | Schneider has higher intelligence level, suitable for intelligent power distribution needs |
| Montagemethode | Fixed/drawout optional; drawout type with standard mechanical interlock | Fixed/drawout optional; drawout interlock is optional | Similar structural design; Schneider’s standard interlock offers higher safety |
| Abmessungen (Fixed 3P, W脳H脳D) | 301脳276脳196mm | 320脳285脳210mm | Schneider is more compact, saving cabinet space |
| Mechanical/Electrical Service Life | 10,000 mechanical operations; 2,000 electrical operations (AC-3) | 8,000 mechanical operations; 1,500 electrical operations (AC-3) | Schneider has better durability, suitable for high-frequency operation scenarios |
| Zertifizierungsstandards | CCC, IEC, UL, CSA, EAC | CCC, IEC | Schneider has broader certification coverage, suitable for export projects |
| Preisreferenz (December 2025, Fester Typ) | RMB 14,500-16,000/unit | RMB 6,500-7,500/unit | Chint’s price is about 45%-50% of Schneider’s, with outstanding cost-performance |
| Typische Anwendungsszenarien | Industrial plant incoming lines, Rechenzentren, high-end buildings, export projects | Civil building power distribution, small and medium-sized factories, localized power distribution renovation projects | Select according to project budget and reliability requirements |
| Kundendienst | Nationwide warranty, extensive overseas network; spare parts supply cycle: um 7 Tage | Nationwide warranty, fast localized service response; spare parts supply cycle: um 3 Tage | Chint’s after-sales service is more suitable for domestic small and medium-sized customers |
Selection Decision Recommendations
- Scenarios for Prioritizing Schneider MT08 Series
– Export projects (z.B., overseas markets such as Algeria), power distribution projects requiring international certifications;
– Scenarios with high requirements for short-circuit breaking capacity and reliability, such as data centers and heavy industrial plants;
– Intelligent power distribution systems requiring energy consumption monitoring and remote control.
- Scenarios for Prioritizing Chint NA8G-800 Series
– Domestic civil buildings, small and medium-sized factories and other general power distribution scenarios with limited budgets;
– Localized renovation projects requiring fast delivery and after-sales response;
– Power distribution circuits with only basic short-circuit and overload protection needs, no intelligence requirements.
- Replacement Compatibility Notes
– The two series have slightly different mounting dimensions; verify cabinet installation space before replacement;
– Chint NA8G series can upgrade measurement and control functions by installing intelligent trip units (z.B., NA8G-M), with the cost still lower than that of similarly configured Schneider models.
Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien