Schneider RM17TA00 3-Phase Multifunction Supply Monitoring Relay

(Phasenfolge / Phasenverlust / 3-Phase Voltage Unbalance) Serie: Zelio Control / Harmony RM17T Series, DIN rail mounted 3-phase monitoring relay, commonly known as phase sequence protector. ✅ Monitoring Functions Phase sequence detection (L1-L2-L3): Instant trip upon reverse phase sequence Phase loss detection: Instant trip if any phase is lost (including phase loss with ...

  • Produktdetails

(Phasenfolge / Phasenverlust / 3-Phase Voltage Unbalance)

Serie: Zelio Control / Harmony RM17T Series, DIN-Schienenmontage 3-phase monitoring relay, commonly known as phase sequence protector.

✅ Monitoring Functions

Phase sequence detection (L1-L2-L3): Instant trip upon reverse phase sequence

Phase loss detection: Instant trip if any phase is lost (including phase loss with regenerated voltage from motors)

3-phase voltage asymmetry (Ungleichgewicht): Adjustable threshold from 5% Zu 15% of Un, with time-delayed tripping

Logic rule: Phasenumkehr / phase loss → instantaneous trip; voltage unbalance → delayed trip.

📌 Key Electrical Specifications

Monitoring voltage range: AC 208~480V (operating limit: 183~528V AC)

Frequenz: 50/60 Hz (±10 %)

Output contact: 1 C/O (SPDT), 5A / 250VAC

Time delay adjustment: 0.1~10s (only for unbalance faults)

Reset delay: Ca. 1.5S

Stromverbrauch: ≤22VA @ 400V 50Hz

Montage: DIN-35-mm-Schiene; Breite 17,5 mm (1 module width)

Anzeige: Status LED; sealed transparent cover prevents accidental parameter changes

🧮 RM17T Series Selection Comparison (Key for Model Selection)

RM17TT00: Phasenfolge + Phasenverlust (NO unbalance monitoring)

RM17TA00 (Aktuelles Modell): Phasenfolge + Phasenverlust + 3-phase voltage asymmetry

RM17TU00: Phasenfolge + Phasenverlust + Unterspannung

RM17TE00: Phasenfolge + Phasenverlust + asymmetry + Überspannung + Unterspannung (full-function model)

🛠️ Typische Anwendungsszenarien

Aufzüge, Heben & Fördergeräte, Luftkompressoren, Wasserpumpen, refrigeration units, Verpackungsmaschinen; prevents motor reverse rotation, burnout from phase loss, and overheating caused by three-phase unbalance.

🔌 Wiring Guidelines

  1. Connect L1/L2/L3 directly to the monitored three-phase supply (selbstversorgt, no separate auxiliary supply required).
  2. Terminals 15/16/18 form one changeover contact: 15-16 = normally closed; 15-18 = normally open.
  3. Panel setting: First select rated voltage (208/220/380/400/415/480V), then set unbalance threshold and fault delay time.
  4. Fehlerbehebung: Automatic reset once power returns to normal; no manual reset button.

⚠️ Fehlerbehebung

Relay does not energize after power-up: Check phase sequence, Phasenverlust, and voltage range dip switch setting.

Frequent tripping during normal operation: Increase unbalance percentage threshold, extend time delay, and investigate single-phase load current imbalance.

No LED illumination: Three-phase input voltage exceeds the 183~528V operating range.

📎 Replacement Options

Direct upgraded replacement within the same product line: RM22TA33 (RM22 series, same functions with 2 C/O contacts).

Inländische Alternativen: Chint / Delixi three-phase phase-sequence & unbalance monitoring relays.

  1. Full Model List of RM17T Series

(3-phase supply monitoring relays, 17.5mm single-module width, DIN-Schienenmontage)

1) Basismodell: RM17TG (Nur Phasenfolge + Phasenverlust; keine Unwucht / Unterspannungsüberwachung)

RM17TG00: 1 C/O changeover contact, 208~480V AC

RM17TG20: 2 C/O-Doppelwechselkontakte, 208~440V AC

2) Multifunction Models (RM17TT / GEGENÜBER / TU / DER, 208~480V AC, 1 C/O contact uniformly)

ModellKernüberwachungsfunktionen
RM17TT00Phasenfolge + Phasenverlust (Basisversion, keine Unwucht / Unterspannung)
RM17TA00 (Aktuelles Modell)Phasenfolge + Phasenverlust + 3-phase voltage unbalance (asymmetry)
RM17TU00Phasenfolge + Phasenverlust + Unterspannung
RM17TE00Phasenfolge + Phasenverlust + Ungleichgewicht + Überspannung + Unterspannung (full function)

Abbreviation explanation:

TU = T + Unterspannung

TE = T + Everything (volle funktionen)

III. Common Specifications for the Whole Series (All Models Identical)

Spannungsbereich: AC 208~480V (operating limit 183~528V)

Kontaktbewertung: 5A / 250VAC; RM17TG00/TT/TA/TU/TE = 1 C/O; only RM17TG20 = 2 C/O

Breite: 17.5mm (1P module)

Reset-Modus: Automatic reset after fault clears; no manual reset button

  1. Upgraded Replacement Models (RM22 Series with Extra Contacts)

RM17TA00 → RM22TA33 (2 C/O contacts)

RM17TU00 → RM22TU23

RM17TE00 → RM22TE33

RM17TA00 Overall Dimensions (B × H × T)

17.5 mm × 90 mm × 72 mm

Breite: 17.5 mm (1-pole module, same width as 1P MCB)

Höhe: 90 mm

Tiefe (from DIN rail front face): 72 mm

Montage: DIN35 standard rail

Nettogewicht: Ca. 0.13 kg

✅ All models in RM17T series (RM17TT00 / RM17TU00 / RM17TE00 / RM17TG00) share identical dimensions.

Core Positioning of RM17TA00

It provides phase sequence + Phasenverlust + three-phase voltage unbalance protection, mainly for three-phase asynchronous motors. It prevents reverse rotation, motor burnout from phase loss, and overheating caused by long-term voltage imbalance. Selbstversorgt, compact 1-module DIN rail design, ideal for compact control cabinets and retrofitting projects where no PLC signal collection is needed.

  1. Industrie & Geräteanwendungen
  2. Heben & Fördern (Primäre Anwendung)

Brückenkräne, electric hoists, Förderbänder, Stapler, Aufzüge; prevents motor reverse rotation after phase reconnection and overheating damage to gearboxes and motors due to long-term unbalance.

  1. Aufzüge & Hebebühnen

Freight elevators, simple lifting platforms, parking lift power circuits; wrong phase sequence causes reverse car movement; voltage unbalance leads to excessive temperature rise of traction motors.

  1. Wasserpumpen & Pumping Stations

High-power centrifugal pumps, submersible sewage pumps, pre-power monitoring before variable-frequency drives; unbalance is frequently caused by mixed single-phase loads in water supply, sewage treatment and chiller pump systems.

  1. Luftkompressoren & HVAC Refrigeration Units

Schraubenkompressoren, Wasserkühler, Luftwärmepumpen, Kältekompressoren; compressors are highly sensitive to three-phase unbalance, which easily burns out motor windings.

  1. Verpackung, Textil & Woodworking Automation

Verpackungslinien, Textilmaschinen, Extruder, Spritzguss-Hilfsausrüstung; frequent power maintenance and phase swapping require phase sequence verification before power-on.

  1. Lüfterlasten

Abluftventilatoren, Saugzugventilatoren, drying fans; large inertia fans produce regenerated voltage after phase loss; this model supports phase loss detection under regenerated voltage conditions.

  1. Control Panels & OEM Equipment Matching

380V three-phase control cabinets, non-standard automation OEM factory-fitted protection; old equipment retrofits, hard-contact interlock without adding PLC analog modules.

  1. Auswahlgrenze: Geeignet / Ungeeignete Szenarien

✅ Empfohlen:

Three-phase motor loads with risks of voltage asymmetry overheating (core advantage over RM17TT00)

Supply voltage AC 208~480V, 50/60Hz

Begrenzter Schrankraum, nur 1 module width available

Hard-contact interlock directly wired into main contactor coil circuit

❌ Nicht empfohlen:

Überspannung + undervoltage monitoring required → choose RM17TE00

Only undervoltage protection without unbalance → choose RM17TU00

Dual independent alarm contacts required → upgrade to RM22TA33 (2C/O)

Motors behind variable-frequency drives: VFDs already have built-in phase loss & Unwuchtschutz; extra relay is generally unnecessary.

III. Typical Control Logic

Contact wired in series with the main contactor coil circuit:

Normal power supply → relay energizes and closes, contactor power permitted;

Phasenumkehr / Phasenverlust / voltage unbalance detected → relay de-energizes and opens, cutting off main power, with dry contacts available for PLC or audible-visual alarm signals.