Harmony RM22-L Niveaukontrollrelais (Conductive Electrode Liquid Level Monitoring)
Modellinterpretation: RM22 series modular control relay; LG = liquid level single detection; 11 = 1 Wechslerkontakt (C/O); MR = power supply 24~240V AC/DC; MT version for 380~415V AC power supply
✅ Kernfunktionen
Designed for conductive liquids (Wasser, Abwasser, usw.) for automatic liquid level control. Two operating modes available:
- Fill Mode (Wasserversorgung) : When liquid level falls below Min electrode → relay energizes, starts fill pump; when liquid level reaches Max electrode → relay de-energizes, stops pump.
- Drain Mode (Sump Pumping) : When liquid level reaches Max electrode → relay energizes, starts drain pump; when liquid level drops below Min electrode → relay de-energizes, stops pump.
It adopts resistance probe detection, judging liquid level based on liquid conductivity, not float switch. Adjustable detection sensitivity.
📋 Electrical Specifications
Versorgungsspannung: 24~240 V AC/DC (Universell für Wechselstrom & Gleichstrom), 50/60Hz; operating range 20.4~264V
Stromverbrauch: AC 5VA / DC 1.5W
Ausgangskontakt: 1 changeover contact 1C/O (11-12 normalerweise geschlossen, 11-14 normalerweise offen), AC-15/DC-13, 8A@250VAC
Einschaltverzögerung: 0.6S
Probe circuit: Max. 12V AC at electrodes, electrode current ≤1mA; maximum probe cable length 1000m
Empfindlichkeit: St standard sensitivity 5kΩ~100kΩ, continuously adjustable via potentiometer
Montage: DIN-Schiene, width 22.5mm
Schutz: Sealing transparent protective cover to prevent on-site misadjustment; built-in diagnostic test button + status LED indicator
📌 Terminaldefinition
| Terminal | Beschreibung |
| A1,A2 | Relay working power supply |
| Min | Low liquid level electrode |
| Max | High liquid level electrode |
| C | Common reference electrode (reference pole) |
| 11 | Contact common terminal |
| 12 | Normally closed NC |
| 14 | Normally open NO |
Verkabelungshinweis: 3 electrodes inside tank: C common pole, Min minimum liquid level, Max maximum liquid level. Only applicable to conductive liquids; not for insulating oil and other non-conductive media.
🛠️ Typische Anwendungen
Wasserversorgung & drainage tanks, sewage pools, Kühltürme, water purification equipment, automatic pump start/stop, DIN rail mounting inside control cabinet.
⚠️ Modelldifferenzierung & Ersatzreferenz
- RM22LG11MR: 24~240V AC/DC, single changeover contact
- RM22LG11MT: 380~415V AC power supply version
- RM22LA32MR: Dual-contact version, two-channel output
Legacy-Ersatz: RM35LM series (eingestellt, replace with RM22LG for new projects)
Funktionsprinzip von Schneider RM22LG11MR
Grundprinzip: AC resistive conductive liquid level detection (Conductivity type)
A low-voltage AC sensing signal is applied between electrodes. The device measures liquid resistance between two electrodes and compares it with the sensitivity threshold set on the front panel. The internal circuit drives output relay action.
Low voltage AC signal on probe side to avoid electrolytic corrosion of electrodes caused by DC.
- Detection Circuit
Das Relais gibt ein Niederspannungs-Wechselstrom-Erfassungssignal aus (ca. 12V AC, Strom <1mA) zwischen C (gemeinsame Elektrode), Min (niedriges Niveau), Max (hohes Niveau).
Die Elektrode ist in Flüssigkeit eingetaucht → Die leitende Flüssigkeit bildet einen Pfad zwischen C und der Elektrode, geringer Widerstand;
Elektrode liegt oberhalb der Flüssigkeit → Stromkreis offen, extrem hoher Widerstand;
Potentiometer stellt die Empfindlichkeitsschwelle ein (5kΩ~100kΩ) : Gemessener Widerstand < Schwelle → Flüssigkeit erkannt; Widerstand > Schwelle → keine Flüssigkeit erkannt.
👉 Gilt nur für leitfähige Flüssigkeiten. Gilt nicht für Öl, ultrareines Wasser (sehr geringe Leitfähigkeit) und Isolierflüssigkeiten.
- Zwei Betriebsmodi (3-Punktkontrolle des Flüssigkeitsstandes mit Hysterese-Speicherlogik)
1) Fill Mode (Wasseraufbereitung)
Flüssigkeitsstand unter Min-Elektrode: C-Min-Schaltkreis offen → internes Relais zieht an, 11-14 NEIN schließt, starts fill pump.
Flüssigkeitsstand steigt, taucht Min ein, erreicht aber nicht Max: C-Min leitfähig, Der interne Speicher speichert den Status, Pumpe läuft weiter.
Liquid level reaches Max electrode: C-Max conductive → relay resets, 11-14 öffnet sich, Pumpe stoppt.
If liquid level drops but remains above Min, pump will not start. Two-point start/stop prevents frequent pump cycling.
2) Drain Mode (Sumpfentwässerung)
Liquid level reaches Max electrode: C-Max conductive → relay energizes, 11-14 NEIN schließt, starts drain pump.
Liquid level falls, leaves Max but still higher than Min: memory holds status, pump keeps draining.
Flüssigkeitsstand unter Min-Elektrode: C-Min open → relay resets, Pumpe stoppt.
- Single Level Mode (Optional, 2 Elektroden)
Use only C+Max or C+Min for single-point alarm / Kontrolle. Small delay can be enabled to suppress false triggering caused by liquid wave and foam.
- Internal Signal & Ausgabe
- A1/A2 supplies power to relay (24~240V AC/DC wide range), power circuit is electrically isolated from probe measurement circuit;
- Measurement circuit continuously acquires resistance between electrodes;
- Logic unit judges status based on mode and electrode signals, Laufwerke 1 Wechslerkontakt (1C/O, 11 gemeinsam,12 NC,14 NEIN);
- Front panel LED indicates output status; Die integrierte Testtaste simuliert den Status für die Schleifeninbetriebnahme.
- Wichtige Designmerkmale
- AC-Erkennung: An den Elektroden liegt keine Gleichspannung an, verhindert Elektrolyse, Blasenbildung, Elektrodenkorrosion und beschleunigte Ablagerungen.
- Einstellbare Widerstandsschwelle: An Abwasser anpassen / Sauberes Wasser mit unterschiedlicher Leitfähigkeit über den Empfindlichkeitsknopf.
- Hysterese-Speicherlogik: Erfordert Anerkennung von hoch & Punkte mit niedrigem Niveau, vermeidet häufiges Schalten des Relais aufgrund geringfügiger Flüssigkeitsschwankungen.
- Maximale Elektrodenkabellänge bis zu 1000 m. Achten Sie bei langen Kabeln auf Störungen durch Streukapazität; Bei hohen Empfindlichkeitseinstellungen kann es zu Fehlauslösungen kommen.
- Prinzipielle Fehlerkorrespondenz
Elektrodenverkalkung → äquivalenter Flüssigkeitswiderstand steigt über den Schwellenwert → Flüssigkeit vorhanden, aber das Gerät meldet keine Flüssigkeit;
Conductive foam layer → electrode not touching actual liquid level but circuit conducts → false liquid level detection;
Poor contact of C electrode → measurement reference lost, all liquid level detection invalid.
Troubleshooting for Schneider RM22LG11MR
Pre-diagnosis method: T test button on front panel. Press T when powered on to toggle relay output status, to distinguish unit failure or external electrode / Verkabelungsfehler.
Fehler 1: No response after power on, power LED off
Symptom: A1/A2 supply voltage normal, no LED light, relay no action
Ursachen
- Loose A1/A2 wiring, schlechter Anschlusskontakt; wrong polarity for DC supply
- Input voltage out of 24~240V AC/DC operating range
- Internal power circuit damaged (lightning surge, transient overvoltage, Kurzschluss)
Lösungen
- Ausschalten, measure voltage at A1/A2, Klemmen festziehen; check polarity for DC supply
- Verify supply within rated range; check upstream MCB and fuse
- Ersetzen Sie das Gerät bei korrekter Versorgungsspannung, wenn die LED immer noch aus ist
Fehler 2: Das Relais funktioniert nicht, wenn die Elektrode eingetaucht ist (Flüssigkeit erkannt, aber keine Reaktion)
Symptom: Flüssigkeit bedeckt die Max/Min-Elektrode, Relaisstatus unverändert, Pumpe startet/stoppt nicht
Ursachen
- Elektrode mit Ablagerungen bedeckt / Schlamm, Der Flüssigkeitsäquivalentwiderstand überschreitet die Empfindlichkeitsschwelle
- Schlechter Kontakt der gemeinsamen C-Elektrode (am häufigsten), Messreferenz verloren
- Defektes Elektrodenkabel, Lose Verkabelung an den Min/Max/C-Klemmen
- Empfindlichkeit zu niedrig eingestellt (Die Widerstandsschwelle ist zu klein, als dass das Abwasser leiten könnte)
- Mittlere Leitfähigkeit zu niedrig (ultrareines Wasser, isolierende Flüssigkeit, Nicht für dieses Modell geeignet)
Lösungen
- Elektroden entfernen, sauber / Politurablagerungen und Schlamm; regelmäßige Elektrodenwartung
- Vorrangige Prüfung der C-Elektrode: Stellen Sie sicher, dass C in Flüssigkeit eingetaucht ist und die Verkabelung sicher ist
- Ausschalten, Testen Sie den Kabeldurchgang, Ziehen Sie die Min/Max/C-Klemmen fest
- Erhöhen Sie die Empfindlichkeit entsprechend (Widerstandsschwelle erhöhen, adjustable from 5kΩ~100kΩ)
- For low-conductivity water / Öl, use float level switch instead
Fehler 3: Relay false action when liquid level below electrode (detects liquid with no actual liquid), pump starts unexpectedly
Symptom: Liquid level below electrodes, relay reports liquid present, pump starts mistakenly
Ursachen
- Conductive foam / scum on liquid surface closes electrode circuit (common in sewage tank)
- Long electrode cable, stray capacitance causes false trigger (>300m is high risk)
- Sensitivity set too high, minor leakage triggers detection
- Electrode cable routed in parallel with power cable, elektromagnetische Störungen
- Terminal condensation / leakage between electrodes
Lösungen
- Raise electrode mounting position to avoid foam; install foam baffle
- Reduce sensitivity; use shielded cable for long signal wire, shield single-end grounded; getrennt von Stromkabeln
- Clean terminal condensation, improve cabinet moisture resistance
Fehler 4: Häufiges Starten und Stoppen der Pumpe, Relais klappert / Schwingung
Symptom: Flüssigkeitsstand innerhalb des zulässigen Bereichs stabil, Das Relais wird wiederholt aktiviert und deaktiviert, Pumpe läuft schnell
Ursachen
- Starke Flüssigkeitsturbulenzen, Die Flüssigkeitsoberfläche streicht wiederholt über die Elektroden; intermittierende Leitung durch Schaum
- Verschmutzte Elektroden, instabiler Elektrodenwiderstand
- Falscher Betriebsmodus, Hystereselogik deaktiviert (nur einzelne Elektrode verdrahtet)
Lösungen
- Elektroden ausfahren, Installieren Sie die Überspannungsschutzhülse; Montieren Sie die Elektroden im Ruhebereich des Tanks
- Elektroden reinigen, Passen Sie die Empfindlichkeit fein an und vermeiden Sie kritische Einstellungen
- Standardmäßige 3-Elektroden-Verkabelung (C+Min+Max), Aktivieren Sie die integrierte Hysterese-Speicherlogik, Vermeiden Sie eine Einzelpunktsteuerung
Fehler 5: Relais-LED normal, aber Ausgangskontakt keine Aktion, Pumpe startet nicht
Symptom: Füllstandsanzeige-LED korrekt, aber nachgeschaltetes Schütz / Pumpe funktioniert nicht
Ursachen
- Falsche Verdrahtung der Ausgangskontakte (11/12/14 Klemmen falsch angeschlossen)
- Die Kontaktlast überschreitet den Nennwert von 8 A, Kontakterosion / Schweißen / offener Stromkreis
- Kein Strom im nachgeschalteten Steuerkreis
Lösungen
- Schalten Sie das Gerät aus und überprüfen Sie die Kontaktverkabelung: 11 gemeinsam, 12 NC,14 NEIN
- Drücken Sie die T-Testtaste und messen Sie den Durchgang zwischen 11-14; offener Stromkreis = Kontakt beschädigt, Relais austauschen
- Steuerstromversorgung der Pumpe prüfen / Schütz
Fehler 6: Kontaktschweißen, Pumpe läuft ständig und kann nicht stoppen
Symptom: Der Flüssigkeitsstand erreicht die Stoppposition, Ausgang bleibt geschlossen, Pumpe lässt sich nicht abschalten
Ursachen
- Langfristige Überlastung, Ein Lichtbogen verursacht Kontaktschweißen
- Keine Überspannungsabsorption für die Schützspule, Gegen-EMF beschädigt Kontakte
Lösungen
- Ersetzen Sie RM22LG11MR sofort, wenn die Kontakte verschweißt sind
- Fügen Sie RC-Dämpfer oder Freilaufdiode für induktive Last hinzu (Schützspule) zum Schutz interner 8A-Kontakte
Empfohlene Reihenfolge zur Fehlerbehebung vor Ort
- Einschalten, Überprüfen Sie die Power-LED; LED aus → Überprüfen Sie die Stromversorgung A1/A2
- Drücken Sie die T-Testtaste und beobachten Sie das Umschalten des Ausgangs
Ausgang schaltet durch T um: Einheit gesund, Fehler in der Elektrode, Kabel oder flüssiges Medium
Keine Antwort von T: Relaiseinheit beschädigt, direkt ersetzen
- Stellen Sie sicher, dass die gemeinsame C-Elektrode vollständig eingetaucht und die Verkabelung festgezogen ist
- Reinigen Sie die Elektroden und stellen Sie den Empfindlichkeitsknopf ein
- Check if signal cable runs together with power cable; use shielded cable for long distance
- Confirm mode selection: Fill (Wasserversorgung) / Abfluss (Drainage)
Vorbeugende Wartung
- Sewage application: Clean electrodes every 3~6 months to prevent scaling
- Keep electrode cable length within 500m where possible; reduce sensitivity and adopt shielded cable if longer
- Ensure cabinet moisture-proof to avoid terminal condensation leakage
- Install surge absorption device for inductive load (Schütz) to protect 8A contacts
Schneider RM22 Harmony Modular Monitoring Relay Full Series List
Gemeinsame Merkmale der Serie: DIN-Schienenmontage, width 22.5mm (RM22TG20:17.5mm); equipped with T test button, Status-LED, sealable transparent cover; Kontaktbewertung: 8A@250VAC; suffix MR=24~240V AC/DC universal supply; MT=380~415V AC supply
- RM22L Conductivity Level Monitoring Relay (series of your model)
Conductive electrode liquid level detection for high/low level control of water tank and sewage sump
|RM22LG11MR|1C/O (1 Umstellung)|24~240V AC/DC|Standardmodell, your reference unit, sensitivity 5k~100kΩ|
|RM22LG11MT|1C/O|380~415V AC|High voltage supply level relay|
|RM22LA32MR|2C/O (2 Umstellung)|24~240V AC/DC|Dual-channel output, 3 sensitivity levels: LS/St/HS|
|RM22LA32MT|2C/O|380~415V AC|Dual-contact high voltage supply level relay|
- RM22T 3-phase Power Monitoring Relay (Phasenfolge / Phasenverlust / 3-Phasenunsymmetrie / Überspannung & Unterspannung)
Monitor 3-phase power supply for motor, Wasserpumpe, air compressor protection
|RM22TA31|2C/O|Phasenfolge, Phasenverlust, 3-Phasenunsymmetrie|200~240VAC|
|RM22TA33|2C/O|Phasenfolge, Phasenverlust, 3-Phasenunsymmetrie|380~480VAC|
|RM22TU21|2C/O|Phasenfolge, Phasenverlust, Unterspannung|200~240VAC|
|RM22TU23|2C/O|Phasenfolge, Phasenverlust, Unterspannung|380~480VAC|
|RM22TR31|2C/O|Phasenfolge, Phasenverlust, Ungleichgewicht, overvoltage/undervoltage with delay|200~240VAC|
|RM22TR33|2C/O|Phasenfolge, Phasenverlust, Ungleichgewicht, overvoltage/undervoltage with delay|380~480VAC|
|RM22TG20|2C/O|Phasenfolge, Phasenverlust (Kompaktversion,17.5mm)|183~528VAC|
- RM22U Single-phase / DC Voltage Monitoring Relay (Überspannung & Unterspannungsüberwachung)
AC/DC single-phase voltage monitoring for DC panel and single-phase power protection
|RM22UA32MR|2C/O|1~100V AC/DC|24~240V AC/DC|
|RM22UA33MR|2C/O|15~500V AC/DC|24~240V AC/DC|
|RM22UA33MT|2C/O|15~500V AC/DC|380~415V AC|
|RM22UB34MR|2C/O|Wide range single phase voltage|24~240V AC/DC|
- RM22J Current Monitoring Relay (AC current monitoring, Überlast / undercurrent)
Work with current transformer CT for motor load current monitoring
|RM22JA21MR|1C/O|0.1~5A AC|24~240V AC/DC|
|RM22JA32MR|2C/O|0.1~5A AC|24~240V AC/DC|
- Modellkodierungsregel (RM22XXYYZZ)
- RM22: Series code Harmony modular monitoring relay
- XX: Function group
LG: Flüssigkeitsstand, single sensitivity
DER: Flüssigkeitsstand, multi-range sensitivity
TA/TU/TR/TG: 3-phase power monitoring
UA/UB: Single-phase voltage monitoring
UND: Current monitoring
- JJ: Contact quantity
11: 1 Wechslerkontakt (1C/O)
32: 2 Wechslerkontakte (2C/O)
- ZZ: Power supply code
HERR: 24~240V AC/DC universal (most widely used in engineering)
MT: 380~415V AC 3-phase high voltage supply
- Legacy Model Replacement (RM35 → RM22)
RM35LM old level relay → RM22LG / RM22LA
RM35TA/TU old 3-phase protection relay → RM22TA/TR/TU
RM35 series discontinued, select RM22 for new projects
- Schnellauswahltabelle
| Anwendung | Empfohlenes Modell |
| Tank / sump conductivity level, single pump start-stop | RM22LG11MR (your reference model) |
| Liquid level control requiring two independent alarm/output channels | RM22LA32MR |
| 3-Phasenmotor: Phasenverlust + Phasenfolge + Unwuchtschutz | RM22TA33 |
| 3-phase power: Phasenverlust + Phasenfolge + über & undervoltage full protection | RM22TR33 |
| Motor load current monitoring (CT sensing) | RM22JA21MR |
| DC panel, single phase over & Unterspannungsalarm | RM22UA33MR |