Bestell-Nr.: 6ED1052-1FB08-0BA1
Serie: LOGO! 8.3, intelligent logic controller with display
Status: Auslaufmodell (Beschädigen 07, 2024)
Ersatz: 6ED1052-1FB08-0BA2 (LOGO!8.4, MQTT supported)
✅ Wichtige Spezifikationen
Stromversorgung: AC/DC 115~230V (100–253V wide range)
Eingaben: 8 digitale Eingänge (AUS), no built-in analog channels
Ausgänge: 4 Relaisausgänge (TUN), max. 10A pro Kanal
Programmkapazität: 400 function blocks
Kommunikation: Integrated Ethernet LAN port, Integrierter Webserver, Datenprotokollierung, Cloud-Verbindung
Lagerung: MicroSD card support for program backup, log export and firmware update
HMI: On-board LCD and operation keys, local programming and monitoring available
Erweiterung: Compatible with full LOGO! Erweiterungsmodule (digital, analog, TDE-Textanzeige)
Programmiersoftware: LOGO!Soft Comfort V8.3 or higher
Montage: DIN-Schienenstandard
📌 Order Code Breakdown
6ED1052: LOGO! Basiseinheit
1FB08: 230V-Stromversorgung, Relaisausgang, mit Anzeige, 8D/4C; 08 = LOGO!8 hardware platform
0BA1: Versionskennung (8.3); 0BA2 = 8.4; 0BA3 = enhanced new version (800 function blocks)
📎 Replacement Differences
6ED1052-1FB08-0BA2: Fully compatible I/O hardware, newly added MQTT protocol. Requires V8.4+ software. Existing programs can be migrated directly. Pinout is identical for cabinet drop-in replacement.
Next geneation: 6ED1052-1FB08-0BA3, expanded to 800 function blocks, touchscreen variant.
🛠️ Typische Anwendungen
HLK-Lüfter, Wasserpumpen, Steuerung der Lichtsequenz, shutters/roller doors, kleine Fördergeräte, Pumpstationen, simple constant temperature & Feuchtigkeitskontrolle, local building interlock, replacing traditional time relays and intermediate relay circuits.
⚠️ Sourcing Notes
No new production from OEM. Available stock consists of surplus spares or used units. Für neue Projekte, select 0BA2 by default.
Migration Notes: LOGO! 6ED1052-1FB08-0BA1 (8.3) → 0BA2 (8.4)
Pinbelegung, Einbaumaß, I/O count and power rating are identical. Wiring can remain unchanged without terminal modification. Main risks lie in software version, project conversion, Kommunikation, web pages, SD-Karte, TDE and the newly added MQTT.
- Mandatory Software Version Requirements (Der häufigste Fallstrick)
- LOGO!Soft Comfort V8.4 (with V8.4.1 patch) ist erforderlich. V8.3 software cannot recognize or download programs to 0BA2 units.
- Recommended workflow:
Upload and back up the original program from 0BA1 using V8.3. Save the raw `.lld` file permanently and do not overwrite it.
Open the project in V8.4, go to Tools → Change Device, target hardware: `LOGO! 230RCE 6ED1052-1FB08-0BA2`
Save as V8.4 format `.lsc`. Projects saved in V8.4 cannot be opened in V8.3. Keep the original backup separately.
- Do not copy program files directly from the 0BA1 SD card to 0BA2: program files are version-incompatible and will trigger errors. Ethernet download is preferred.
- Programm & Function Block Compatibility (Most Standard Logic Works)
✅ Kompatibel: Timer, Zähler, comparators, analoge Funktionen, relay logic, pulse generators, Datenprotokollierung, Modbus TCP (client/server), UDF user-defined function blocks
⚠️ Items to verify:
- Custom Web Pages (LOGO! Web Editor)
0BA1 pairs with LWE V1.1; 0BA2 requires LWE V1.2.1
Old web projects may have abnormal variable IDs, layout or refresh rate after import. Always test web pages online after download. MQTT tags are invisible on legacy web pages and need reconfiguration.
- Datenprotokollierung: CSV log format is compatible, but parsing rules for negative values and timestamps are slightly adjusted. Verify logs after running for a period.
- Password Protection: Project passwords carry over during migration. Upload is impossible if the password is lost. Confirm the password before migration.
- Function block limit: Both versions support 400 blocks, no capacity shortage.
- Communication Focus (MQTT exclusive to 0BA2; Modbus TCP unchanged)
- Modbus TCP: Register mapping, IP, Hafen, slave ID and timeout parameters generally remain unchanged. Read/write tests are mandatory after replacement. Der 8.4 firmware fixes certain abnormal Modbus frames. Some older HMI/SCADA may experience intermittent disconnection; increase timeout on the master side.
- MQTT is only available on 0BA2: 0BA1 has no MQTT function. Ignore if your original project does not use MQTT. Add MQTT client configuration within V8.4 if cloud connectivity is required later.
- IP-Adresse: Reuse the original IP, subnet mask and gateway to minimize changes to SCADA, HMI and touch panels. Factory default IP matches 0BA1, but connect via PC directly to set IP before powering on in the system to avoid IP conflict.
- Ethernet MAC address changes: Update MAC binding rules if your master system uses MAC whitelisting.
- Erweiterungsmodule & TDE Text Display
Erweiterungsmodule (6ED1055 suffix 0BA2): Vollständig kompatibel, no replacement required, backplane bus is identical.
TDE-Textanzeige (6ED1055-4MH08-0BA0/0BA1): Works with 0BA2 host. Re-download TDE configuration in V8.4, otherwise texts and variables will fail to refresh.
Notiz: TDE designed for 0BA3 (LOGO!9) cannot be used with 0BA2.
- SD Card Notes
Format remains FAT32, standard MicroSD card supported.
Program files stored on the 0BA1 SD card cannot run directly on 0BA2. SD cards are only used for 0BA2 backup, firmware upgrade and log export within V8.4 environment.
Firmware: 0BA2 only accepts V8.4 firmware packages. 8.3 firmware cannot be flashed. Place firmware file in root directory without renaming.
- Recommended On-site Replacement Procedure to Reduce Downtime Risk
- Before shutdown: Upload full program from 0BA1 with V8.3 and save raw backup. Record IP, Modbus register map, web pages, TDE texts, real-time clock and daylight saving settings.
- Ausschalten, remove 0BA1 and install 0BA2. Terminals are pin-to-pin compatible with no wiring changes.
- Open converted project in V8.4 and confirm hardware model is updated to 0BA2.
- Disconnect field loads first, Einschalten, download program, verify RTC, DI status and DO logic.
- Test all communications: Modbus, web server and TDE display.
- Enable field loads only after offline logic validation. Laufen Sie ununterbrochen für 30 minutes to check timing stability and communication drops.
- Create a local SD card backup on the new 0BA2 unit.
- Common Errors & Fehlerbehebung
- Download error [Device type mismatch]: The project hardware is still set to 0BA1. Change device model in software.
- V8.3 cannot open converted project: Expected version isolation. Only the original `.lld` backup can be opened in V8.3.
- Blank web page / stale variables: LWE version mismatch. Reopen web project in V1.2.1 and download again.
- Intermittent Modbus disconnection: Increase master communication timeout or upgrade 0BA2 firmware to latest V1.84.03.
- TDE display not updating: Re-download TDE configuration, do not download host program only.
- Is Program Modification Required?
Pure logic, Timing, Beleuchtung, pump and fan interlock: No program modification required for direct migration.
Projects with Modbus acquisition, web monitoring or TDE display: Full communication and screen validation is mandatory.
Cloud / MQTT deployment: Add MQTT client configuration after migration in V8.4.
LOGO!8 Host List (6ED1052-xxx08)
Zwei Typen: Basic with display (prefix 1) and Pure o-type without display (prefix 2). Suffix version: 0BA0(8.2), 0BA1(8.3 eingestellt), 0BA2(8.4 aktiv), 0BA3(LOGO!9 new release).
- Bestellcode-Regeln
6ED1052 1FB08 0BA1
- 7Charakter: 1 = with LCD display; 2 = o-type without display
- Leistungscode:
MD = 12/24VDC
CC = 24VDC transistor output (CE)
HB = 24V AC/DC relay output (RCE)
FB = 230V AC/DC relay output (RCE, Ihr Modell)
- 08 = LOGO!8 hardware platform
- Suffix 0BAx = firmware version:
0BA0: 8.2
0BA1: 8.3 (eingestellt, your original unit)
0BA2: 8.4 (MQTT supported, drop-in replacement for 0BA1)
0BA3: LOGO!9, bis zu 800 function blocks
- Basic Units with Display (Präfix 1)
230RCE (AC/DC 115–230V, 8DI/4 relay 10A, Ihr Modell)
6ED1052-1FB08-0BA0 (8.2)
6ED1052-1FB08-0BA1 (8.3, eingestellt, original model)
6ED1052-1FB08-0BA2 (8.4, Direkter Ersatz, MQTT)
6ED1052-1FB08-0BA3 (LOGO!9 erweitert)
24RCE (AC/DC 24V, Relaisausgang)
6ED1052-1HB08-0BA0 / 0BA1 / 0BA2 / 0BA3
12/24RCE (DC12–24V, Relaisausgang, 4 channels configurable as AI)
6ED1052-1MD08-0BA0 / 0BA1 / 0BA2 / 0BA3
24CE (DC24V, transistor 0.3A, 4 built-in AI inputs)
6ED1052-1CC08-0BA0 / 0BA1 / 0BA2 / 0BA3
- Pure o-type without Display (Präfix 2)
230RCEo (no-display counterpart of your model)
6ED1052-2FB08-0BA0 / 0BA1 / 0BA2 / 0BA3
24RCEo
6ED1052-2HB08-0BA0 / 0BA1 / 0BA2 / 0BA3
12/24RCEo
6ED1052-2MD08-0BA0 / 0BA1 / 0BA2 / 0BA3
24CEo
6ED1052-2CC08-0BA0 / 0BA1 / 0BA2 / 0BA3
- Version Comparison Table
| Version | Suffix | Software | Status | Hauptmerkmale |
| LOGO!8.2 | 0BA0 | V8.2 | Auslaufmodell | No MQTT |
| LOGO!8.3 | 0BA1 | V8.3 | Auslaufmodell (original unit) | 400 function blocks, no MQTT |
| LOGO!8.4 | 0BA2 | V8.4 | Aktiv | Pin-compatible with 0BA1, MQTT cloud, Direkter Ersatz |
| LOGO!9 | 0BA3 | V9.0 | Neu | 800 function blocks, same I/O hardware |
- Compatible Expansion Modules (Common for 0BA0/1/2)
Digital expansion DM8 / DM16:
6ED1055-1FB00-0BA2 (DM8 230R, 4DI+4DO relay)
6ED1055-1HB00-0BA2 (DM8 24R)
6ED1055-1CB00-0BA2 (DM8 24V transistor)
Analog expansion AM2:
6ED1055-1MA00-0BA2 (AM2 analog input)
- TDE Text Display
6ED1055-4MH08-0BA1 (works with 0BA1 / 0BA2 host)
- Sourcing Recommendation for 6ED1052-1FB08-0BA1
- Spare replacement: Purchase 6ED1052-1FB08-0BA2. Wiring unchanged; only switch hardware model in V8.4.
- New project expansion: Select 0BA3 for larger program capacity.
Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter



















NH42-63-318x560.png)



