All-in-one immersion pipe Temperaturregler (Sensor + Regler + local operator panel integrated), member of the RL…100 series. Designed for modulating HVAC hydronic systems with DC 0~10V analogue output.
Bestellcode: BPZ:RLE162
✅ Primary Applications
Hot/chilled water systems, heating circuits, heat exchangers, water-side control for air handling units, domestic hot water temperature regulation and temperature limit protection. Supports Heating / Cooling modes. Can be fitted with an outdoor temperature sensor (QAC22, LG-Ni1000) for weather compensation, remote setpoint switching, and optional legionella disinfection function.
✅ Wichtige technische Spezifikationen
Stromversorgung: AC24V, 50/60Hz, Stromverbrauch: 2 VA
Kontrollalgorithmus: P / PI selectable
Setpoint Range: -10 ~ +130 ℃, setpoint offset 0~60 K
Built-in Sensor: Immersion probe, insertion length 130 mm, PN10; threaded fitting AQE2102 included with delivery
Analogue Outputs: 2 independent DC 0…10V (1mA) for modulating actuators (SQX, SKB, SKD series)
Digitaler Ausgang: 1 potential-free normally open relay, AC24~230V, 2A (for circulating pumps, Alarm, Fans)
Eingaben: LG-Ni1000 temperature sensor + potential-free dry contact (external switchover for setpoint / eco mode)
Schutzklasse: IP65, direct pipe mounting without control cabinet
Gesamtabmessungen: 125 × 152 × 78 mm
Umgebungstemperatur: Max. 50 ℃ (surrounding environment)
✅ Kernfunktionen
- Constant temperature control + hoch / low temperature cut-off protection
- Outdoor air temperature compensation (weather-dependent supply temperature reset)
- External contact for setpoint switching (ECO energy saving / time programme)
- Optional legionella high-temperature disinfection
- Service test mode, fully configured via DIP switches
- Local knob setpoint adjustment; standalone operation without bus communication (not a DDC)
✅ Series Selection Table (RL…100 Range)
RLE162: Immersion type, dual DC 0~10V modulating outputs (dieses Modell)
RLE132: Immersion type, 3-point floating switch output (for 3-position electric valves)
RLM162: Duct-mounted temperature controller with dual 0~10V outputs
RLA162: Wall-mounted room thermostat with dual 0~10V outputs
RLA162.1: Same as RLA162, with setpoint lockout (for hotel guest rooms & office anti-overheating)
Common features across the RL…100 family:
AC24V supply, built-in LG-Ni1000 sensor, local knob setting, no LCD display, DIP switch configuration, stand-alone only (no bus), IP65 for RLE/RLM, IP30 for RLA.
RLE162 / RLE132 / RWD68 Full Comparison
Kurze Zusammenfassung:
RLE162: All-in-one pipe-mounted, dual 0~10V continuous modulation
RLE132: All-in-one pipe-mounted, 3-point floating switch output
RWD68: DIN rail cabinet-mounted standalone controller, single 0~10V analogue output
Main Comparison Table
| Artikel | RLE162 | RLE132 | RWD68 |
| Produktfamilie | Synco100 RL…100 Immersion All-in-One | Synco100 RL…100 Immersion All-in-One | Synco100 Cabinet DIN-rail (NOT RL…100 series) |
| Montage | Direct on pipe, IP65 | Direct on pipe, IP65 | Im Schaltschrank, DIN-Schiene, IP30 |
| Temperatursensor | Built-in immersion Ni1000 probe | Built-in immersion Ni1000 probe | External sensor only (must order QAE21 separately) |
| Analoger Ausgang | 2 × DC 0~10V modulating | No analogue output; only 3-point floating (Y1/Y2) | 1 × DC 0~10V modulating |
| Digitaler Ausgang | 1 Relais (NEIN, 2A) | 1 Relais (NEIN, 2A) | Multiple relay outputs |
| Setpoint Adjustment | Local knob + DIP-Schalter, no display | Local knob + DIP-Schalter, no display | LCD screen + Tasten, parameter viewing & editing |
| Outdoor Compensation | Unterstützt | Unterstützt | Unterstützt |
| Legionella Function | Verfügbar | Nicht verfügbar | Nicht verfügbar |
| Kommunikation | No bus, stand-alone only | No bus, stand-alone only | No bus, stand-alone only |
Application Selection Guidance
✅ Choose RLE162 if you need:
Dual modulating valves (primary heating valve + secondary mixing valve, Heizung + cooling split range control)
Domestic hot water with legionella disinfection
On-pipe installation without cabinet wiring
Weather-compensated supply temperature control for plate heat exchangers
✅ Choose RLE132 if you only need 3-position floating electric valves (on/off/open-close), no continuous 0~10V regulation.
✅ Choose RWD68 if:
You require visible LCD parameters, pressure/humidity monitoring, or only a single analogue output
Controller will be installed inside a control cabinet
❌ Not suitable for RLE162:
Single-valve only applications (use RWD68 for lower cost)
3-position floating valve control (select RLE132)
Druck, differential pressure or humidity measurement (use RWD68)
BMS/BA network communication (requires full DDC controller)
Duct or room temperature control (RLM162 / RLA162)
Typical Application List
- Domestic hot water storage tank with legionella disinfection (Hotels, Krankenhäuser, dormitories) ✔
- Plate heat exchanger secondary supply temperature with weather compensation + dual valve control ✔
- AHU heating & cooling coil split-range modulation (heat valve + cold valve) ✔
- Chilled water secondary circuit constant temperature + low-temperature anti-freeze protection ✔
- High-temperature mixing circuits for underfloor heating ✔
- Local retrofit projects on building heat metering branches ✔
Full RL…100 Series Model List (All-in-One Local Controllers, RLE162’s Family)
1) Immersion Pipe Type (RLE series, built-in immersion probe, IP65)
| Modell | Ausgabetyp | Hauptanwendung | Ordering Remarks |
| RLE162 | 2 × DC 0~10V AO + 1 relay DO | Dual modulating valve control; Warmwasser, heat exchangers, split-range heating/cooling; legionella + weather compensation | Flagship dual-analogue model; no LCD; DIP switch configurationhit.sbt.si… |
| RLE132 | 3-point floating (Y1/Y2) + relay DO | 3-position electric valves for heat exchangers & DHW tanks; switch-only regulation | Best-selling switch model; no 0~10V analogue output |
| RLE127 | 2-position on/off + differential temperature control | Solar collector + storage tank differential temperature pump control | No analogue output; only temperature difference start/stop |
2) Duct Mount Type (RLM series, built-in air duct sensor)
| Modell | Ausgabe | Zweck |
| RLM162 | 2 × DC 0~10V AO + relay DO | Supply air temperature control for AHU/air handling units; heating/cooling split-range control |
3) Wall-mounted Room Type (RLA series, indoor temperature control)
| Modell | Ausgabe | Zweck |
| RLA162 | 2 × DC 0~10V AO + relay DO | Two-pipe fan coil room temperature modulation |
| RLA162.1 | Same as RLA162, with setpoint limit | Hotel guest rooms & Büros; prevent excessive setpoint adjustment |
Series Unified Specifications
AC24V power, built-in LG-Ni1000 temperature sensor, local rotary knob setpoint, no LCD display, DIP switch programming, stand-alone operation without field bus, IP65 (RLE/RLM), IP30 (RLA).
RWD Series (Cabinet DIN-Rail Controllers, Not Part of RL…100 Series)
RWD62 / RWD68 / RWD82 are DIN rail mount controllers without built-in sensors; external temperature probes must be wired separately. Do not mix them up with the RLE/RLA/RLM all-in-one range.
Modellbenennungsregel (RL…100 Series)
- Prefix Letter:
RLE = Immersion (pipe immersion mounting)
RLM = Duct (air duct mounting)
RLA = Room (indoor wall mounting)
- Numerical Suffix:
127: 2-position switch + differential temperature control
132: 3-point floating switch output
162: Dual DC 0~10V continuous analogue outputs (top configuration in this series)
Einstellung & Ersatzoptionen
- RLE162, RLE132, RLE127, RLM162, RLA162 are legacy Synco100 products, production is gradually reduced, only stock available.
- Replacement solutions:
Keep original pipe-mounted all-in-one design: Continue purchasing stock of the same model.
Migrate to cabinet centralized control: Use RWD68 + QAE21 immersion temperature sensor (only single 0~10V output; dual-AO capability is lost).
Typische Verkabelungslogik
Stromversorgung: AC24V
AO1 / AO2 → 0~10V modulating electric control valves
Relay DO → Circulating pump / Fehleralarm
External Ni1000 (QAC22) → Outdoor temperature compensation
Dry contact DI → Time switch / eco setpoint switchover
Leitfaden zur Fehlerbehebung
- Keine Ausgabe: Überprüfen Sie die AC24V-Stromversorgung; confirm DIP switch mode matches heating/cooling setting.
- Incorrect temperature reading: Check probe fouling and installation location (install in steady flow area, avoid turbulent zones).
- Actuator fails to move: Measure DC 0~10V signal to isolate controller fault vs actuator fault.
- Relay not pulling in: Überlaststrom (>2A) or loose terminal wiring.