Schneider EOCRSS-60NW7PQ

Basic Product Information

Marke: SAMWHA EOCR (Schneider Korea)

Produkttyp: EOCR-SS Series Knob-type Electronic Motor Protector (Replaces traditional thermal overload relays)

  1. Model Code Breakdown of EOCRSS-60NW7PQ
SegmentCodeDefinition
EOCRSSSerieSS Economy Integrated Through-Core Motor Protector
60Aktuelle BewertungBuilt-in CT, adjustable rated current: 5.0~60A, compatible with 1.5~30kW three-phase motors
NProtection ModeType N Fail-Safe: Contacts open and contactor trips upon protector power loss or fault; Type R does not trip when power fails
W7StromversorgungW7 = Wide Voltage AC 180~480V (Suitable for 380/400/440V industrial three-phase power grids)
PKontaktkonfigurationP = Standard changeover contacts: 95(NC)/97(NEIN) (1 Normalerweise geöffnet + 1 Normalerweise geschlossen)
QAdditional FunctionQ = Built-in Modbus-RTU RS485 communication; supports PLC/DCS remote monitoring, real-time current reading and fault code retrieval
  1. EOCR-SS Series Knob-type Electronic Motor ProtectorGrundlegende technische Spezifikationen

3.1 Aktuell & Time Adjustment

Aktueller Bereich: 5~60A (10:1 wide adjustment ratio)

D-Zeit (Start Stall Delay): 0.2~30s adjustable to avoid false tripping caused by high motor starting current

O-Zeit (Overload Trip Delay): 0.2~30s adjustable to match motor thermal characteristic curves

3.2 Schutzfunktionen

  1. Überlast & Überstromschutz (O-Time delayed trip)
  2. Three-Phase Phase Loss Protection (Instant trip)
  3. Stallschutz (D-Zeit + O-Time dual delay)
  4. Three-Phase Current Unbalance Protection

3.3 Elektrische Spezifikationen

Operating Power Supply: AC 180~480V (W7 wide voltage)

Ausgangskontakte: 5A/250VAC changeover contacts (95NC, 96COM, 97NEIN)

Kommunikation: RS485 Modbus RTU (Exclusive to Q suffix models)

Dielektrische Spannungsfestigkeit: 2kV for 1 Minute

Stromverbrauch: ≤250mA

3.4 Umfeld & Installation

Betriebstemperatur: -20℃~+60℃; Lagertemperatur: -30℃~+80℃

Luftfeuchtigkeit: 30%~85%RH, nicht kondensierend

Montage: Standard 35mm DIN rail or screw fixing

Hauptstromkreis: Two through-core CTs (Pass L1 and L2 through protector windows)

  1. Front Panel Knobs & Indicators
  2. LOAD(A): Motor rated current adjustment knob (5~60A)
  3. D-TIME: Start delay (Prevent false tripping during startup)
  4. O-ZEIT: Overload trip delay
  5. Green PWR LED: Power supply normal
  6. Red TRIP LED: Fault tripping (Number of flashes indicates fault type)
  7. RESET: Manual reset button; PRÜFEN: Unit self-test button
  8. Key Differences of PQ Suffix (vs Standard 60NW7)
  9. Built-in RS485 Modbus communication: Remotely read real-time operating current, fault logs and protector status; receive remote reset commands from upper computer
  10. PCB of Q model integrates communication terminals, supporting multi-protector bus networking
  11. Ideal for automated production lines, Pumpstationen, central air conditioning and centralized monitoring control rooms
  12. Typische Anwendungsszenarien

380V three-phase fans, Wasserpumpen, Luftkompressoren, belt conveyors and mixing motors

Motors with rated current 5~60A, no external current transformer required

Control cabinets requiring PLC remote motor data collection and remote fault reset

  1. Verkabelungsrichtlinien
  2. Hauptstromkreis: Run motor phase wires L1 and L2 through the two CT windows of the protector; L3 does not need to pass through
  3. Power Terminals A1/A2: Connect to AC380V control power supply
  4. Steuerkreis: 96COM as common terminal; wire 95NC normally closed contact in series with contactor coil (Type N opens on power loss); connect 97NO normally open contact to fault alarm indicator light
  5. RS485 Communication: A/B differential bus, daisy-chain wiring for multiple devices
  6. Fehlerbehebungsmatrix
FehlerphänomenGrundursacheLösungen
TRIP LED stays lit and cannot be resetContinuous overload / motor stallBelastung reduzieren, increase set current, check mechanical jamming
TRIP LED flashes twicePhasenverlustInspect main circuit fuses, contactor contacts and motor wiring
Keine Reaktion nach dem Einschalten, PWR LED offAbnormal power supply to A1/A2Measure 380V power supply, replace the protector
No Modbus communication dataA/B wires reversed / duplicate device addressesSwap RS485 A/B polarity, set unique address for each device
  1. Alternative Models in the Same Series
  2. Non-communication version: EOCRSS-60NW7P (No RS485, geringere Kosten)
  3. 24–240V power supply version: EOCRSS-60NS7PQ (S7 = 24~240V AC/DC)
  4. Höhere Stromstärke: For motors over 60A, select EOCRSS-100 series with external CT