Protector de motor digital Schneider EOCRSSD-30DF7

EOCRSSD-30DF7 is a digital motor protector manufactured by Schneider Electric (formerly Samwha, Corea del Sur) with current range 3-30A and 110VAC control power supply. It provides triple protection against overload, phase loss and locked rotor. It is applicable for precise protection of three-phase low-power motors, capable of replacing traditional thermal relays to improve protection accuracy and fault diagnosis efficiency.

  1. Definición del código del modelo
Segmento de códigoDescripción
EOCRElectronic Over Current Relay, core product positioning
SSDSolid State Digital, adopting solid-state electronic components and digital control technology
30Current protection range: 3~30A (conexión directa, no external CT required)
DPantalla digital, equipped with digital tube to display real-time 3-phase average current and fault status
F7Control power specification: 110VAC±15% (50/60Hz); other options: M7(220VACACIONES), B(24VCA/CC)
  1. Especificaciones técnicas principales
CategoríaParámetrosObservaciones
Basic Info
MarcaElectricidad Schneider (Former Samwha Korea)Produced in Iksan, Korea; Authorized agent in China: Shanghai Hanshi Electric
Tipo de productoDigital Overcurrent Relay / protector de motorHigher precision (±5%) than traditional thermal relay
Parámetros eléctricos
Tensión de funcionamiento nominal600V y (UL) / 690V y (CSA, CEI 60947-4-1)Suitable for low-voltage motor circuits
Tensión nominal de resistencia al impulso6kVCumple con IEC 60947-4-1
Controlar el poder110VAC±15%, 50/60HzMatched with F7 code
Consumo de energía≤3WLow power consumption for long-term operation
Protection Parameters
Rango de corriente ajustable3~30A continuously adjustableAdjustment ratio: 10:1
Funciones de protección1. sobrecorriente (O-Time: 0.5~10s adjustable)Independent adjustable start delay D-Time
2. Phase loss (fast protection within 3s)
3. Locked rotor (combined D-Time+O-Time protection)
Modo de reinicioManual / Eléctrico (opcional)Reset required after fault for restart
Producción & Mostrar
Output Contact1 CAROLINA DEL NORTE + 1 NO (2-SPST)Calificación de contacto: 3Aire acondicionado/250 VCA
Modo de visualizaciónDigital tube displayReal-time 3-phase average current, flashing fault code indication
Físico & Ambiental
Dimensión45×75×110mm, standard DIN rail mountingCompact size saves cabinet space
Grado de protecciónIP20 (panel frontal)Adecuado para instalación dentro de armarios de control.
Temperatura de funcionamiento-20℃ ~ +60℃Adaptable to industrial temperature variation
Temperatura de almacenamiento-40℃ ~ +85℃Meet transportation and storage requirements
Proceso de dar un título
Certificaciones InternacionalesCE, UL, CSACumplir con IEC 60947-4-1, global applicable
Cumplimiento del transporte aéreoNo built-in lithium battery, conform to UN38.3Shippable as general cargo without special packaging
  1. Cross-brand Comparison
ModeloRango actualControlar el poderMostrarProtecciónGama de preciosSolicitud
Schneider EOCRSSD-30DF73~30A110VACACIONESDigital displaySobrecarga / Phase loss / Locked rotor350~450CNY3-phase low-power motors with fault diagnosis demand
ABB CM-MSS.31P3~30A24~240VAC/DCIndicator lightSobrecarga / Phase loss / Locked rotor400~500CNYGeneral industrial motors, unified brand matching
Siemens 3RB2026-1SB02.5~32A24~240VAC/DCIndicator lightSobrecarga / Phase loss300~400CNYSupporting Siemens PLC, proteccion basica
Omron K8DS-PH13~30A100~240VACDigital displaySobrecarga / Phase loss / Locked rotor380~480CNYLíneas de producción automatizadas, protección de alta precisión
Chint NR2-322.5~32ASin poder de controlNo displaySobrecarga / Phase loss50~80CNYEconomy application, low precision requirement

Puntos clave de selección

  1. Display function: EOCRSSD-30DF7 supports real-time current monitoring and fault diagnosis, superior to indicator-light-only models
  2. Protection accuracy: Electronic protector (±5%) far exceeds thermal relay (±15%), extending motor service life
  3. Control power: 110VAC F7 version fits specific regional power grids, confirm on-site power supply first
  4. Full Series Model List

EOCR-SSD Series Classification

Rango actualBase ModelPower OptionsEjemplos de modelos completos
0.5~6AEOCRSSD-05SS:24~240VAC/DCEOCRSSD-05DF7, EOCRSSD-05DM7, EOCRSSD-05DB
F7:110VACACIONES
M7:220VACACIONES
W.:380~440VAC
3~30AEOCRSSD-30SIgual que arribaEOCRSSD-30DF7, EOCRSSD-30DM7, EOCRSSD-30DW
5~60AEOCRSSD-60SIgual que arribaEOCRSSD-60DF7, EOCRSSD-60DM7, EOCRSSD-60DS

Código de pedido & Accesorios

Standard order number: EOCRSSD-30DF7

Soporte de montaje: EOCR-MNT-01 (DIN rail type)

Extension cable: EOCR-CAB-05 (5metro) / EOCR-CAB-10 (10metro)

Test kit: EOCR-TEST-KIT (including analog load & calibrator)

  1. Fallos comunes & Soluciones de mantenimiento
Fenómeno de fallaPosibles causasPasos para solucionar problemasSolucionesMedidas preventivas
No digital display1. Control power disconnected1. Measure terminal voltage1. Connect 110VAC correctlyCheck power spec before installation
2. Wrong wiring polarity2. Comprobar el cableado2. Adjust connection (AC non-polar)
3. Internal fuse blown3. Inspect internal fuse3. Replace 0.5A fuse
False tripping1. Low current setting1. Confirm motor rated current1. Set current to 1.1 times rated valueSet parameters per motor nameplate
2. Short start delay2. Extend D-Time2. D-Time = motor start time +1s
3. Power harmonic interference3. Test power THD3. Instalar filtro de potencia
Failure to trip1. Excessively high current setting1. Check current setting1. Set current to 0.9 times rated valueRegular contact inspection, avoid overload
2. Damaged output contacts2. Test contact continuity2. Replace contact module
3. Internal circuit failure3. Inspect internal components3. Contact after-sales service
Garbled display1. Fluctuación de voltaje1. Test power stability1. Install voltage stabilizerMantener alejado de los inversores, ensure good grounding
2. Interferencia electromagnética2. Check grounding2. Optimize grounding
3. Program error3. Power cycle restart3. Restaurar la configuración de fábrica

Ciclo de mantenimiento

  1. Daily inspection: Check display status and alarm indicator
  2. Monthly maintenance: Dust cleaning, apretar los terminales del cableado
  3. Quarterly calibration: Verify protection parameter accuracy
  4. Annual overhaul: Inspect internal components, replace aging parts
  5. Escenarios de aplicación & Cases

Escenarios aplicables

Automatización industrial: máquinas herramienta cnc, transportadores, equipo de impresion

Tratamiento de agua: bombas de agua, fans with frequent startup and variable load

climatización: Compresores de aire, ventiladores de torre de enfriamiento

Building materials industry: Mezcladores, heavy-duty conveyors

Power system: Standby generators, protección de transformador pequeño

Non-recommended Scenarios

High voltage motors (>690V): Adopt dedicated high-voltage protectors

Explosion-proof environment: Extra explosion-proof housing required with higher cost

Ultra-low current (<0.5A): Choose EOCRSSD-05S or match external CT

Casos típicos

Caso 1: Water Pump Motor Protection in Steel Plant

Problem: Frequent false tripping of old thermal relays causing unplanned shutdowns without fault identification

Solución: Install EOCRSSD-30DF7, set current 15A (motor rated 13.5A), start delay 5s

Effect: False shutdown rate reduced by 62%, fault diagnosis time shortened from 2h to 5min, annual maintenance cost saved about 80,000 CNY

Caso 2: Mixer System in Pharmaceutical Factory

Problem: Motor burnout caused by mixer locked rotor leading to heavy losses

Solución: Adopt EOCRSSD-30DF7, set locked rotor protection (D-Time=3s, O-Time=1s)

Effect: Power cut within 3s once locked rotor occurs, 100% motor intact rate, avoid production stop losses

  1. Reglas de selección

Reglas de selección rápida

  1. Coincidencia actual: Set protection current within 0.9~1.1 times motor rated current
  2. Delay setting: Start delay (D-Time) = actual motor startup time + 1 segundo
  3. Fuente de alimentación: Prioritize matching on-site control power to avoid extra transformer cost
  4. Display demand: Choose D-type for fault diagnosis, non-D-type for basic protection only
  5. Cumplimiento del transporte aéreo & Certificaciones
  6. Air Freight Regulation

No built-in lithium batteries or supercapacitors, fully compliant with UN38.3 air transport standards

Can be delivered as general goods, no MSDS or special shipping documents needed

Packaging suggestion: Anti-static bag + hard carton to prevent vibration damage