Standard designation: E3H 3200 R3200 PR123/P-LSIG an air circuit breaker from ABB’s SACE EMAX series, frame size E3H. Model Segment Description E3H Frame designation (E3 = 3200A frame, H = high breaking capacity) 3200 Frame rated current (3200A) R3200 Trip unit rated current (3200A) PR123/P Intelligent trip unit (PR123/P is high-end type with LCD display) ...

  • Detalles del producto

Standard designation: E3H 3200 R3200 PR123/P-LSIG an disyuntor de aire from ABB’s SACE EMAX series, frame size E3H.

Segmento de modeloDescripción
E3HFrame designation (E3 = 3200A frame, H = high breaking capacity)
3200Frame rated current (3200A)
R3200Trip unit rated current (3200A)
PR123/PIntelligent trip unit (PR123/P is high-end type with LCD display)
LSIGProtection configuration (L=overload, S=short-time delay, I=instantaneous, G=ground fault)
-PAGMounting type (P = withdrawable, F = fixed)

Global Order Code: 1SDA060849R1 (withdrawable) / 1SDA056503R1 (fixed)

Trade Description: ABB SACE EMAX E3H 3200A 3P/4P LSIG Intelligent Air Circuit Breaker

  1. Key Technical Specifications
ArtículoValorNotas
Frame SizeE3 (3200A)Max rated current up to 3200A
Rated Operational Current (En)3200AWith PR123/P-LSIG trip unit
Tensión nominal de aislamiento (interfaz de usuario)1000V y50/60Hz, three-phase system
Tensión nominal de resistencia al impulso1000VCumple con IEC 60947-2
Ultimate Short-Circuit Breaking Capacity (uci)100kA @ 415V ACHigh breaking, arc-free design
Service Short-Circuit Breaking Capacity (ics)100kA @ 415V AC (100% uci)Full selective protection
Funciones de protección4-step LSIG protectionl, S, I, G as defined above
Tipo de unidad de disparoPR123/Ppantalla LCD, programmable, event logging
MontajeWithdrawable (PAG) / Fijado (F)Withdrawable allows hot-swap maintenance
polacos3P o 4P4P includes neutral pole protection
ConexiónRear horizontal (HR) / Front horizontal (FR) / Vertical (V)Flexible panel integration
Mechanical Endurance20,000 operacionesHigh-reliability design
Electrical Endurance2,000 operaciones (at rated short-circuit)Cumple con IEC 60947-2
Dimensiones432×396.5×461mm (withdrawable)Compact footprint
PesoAprox.. 85kilos (withdrawable)Standard configuration
Ingress ProtectionIP30Dust-resistant, suitable for switchgear
Impulse Withstand Voltage12kVHigh insulation for industrial environments
Temperatura de funcionamiento-25°C a +70°CWide-temperature design
Control Voltage220VCA/CC (estándar)Optional 110V/24V AC/DC
  1. Aplicaciones

This breaker is widely used in industrial and building power distribution systems:

  1. Industrial Main Distribution: Main incomers, substation LV sections, large motor control centers (MCC)
  2. Edificios Comerciales: Main switchboards in shopping malls, hoteles, hospitals for critical loads
  3. Centros de datos: UPS I/O, server room main distribution, high-reliability protection
  4. Energía Renovable: PV inverters, wind turbine converters, suitable for high-harmonic environments
  5. Infraestructura: Metro, airports, ports, withstands frequent operation and harsh conditions
  6. OEM Equipment: Large industrial furnaces, rolling mills, marine electrical systems
  7. Características clave

Protección inteligente: PR123/P-LSIG 4-step protection with precise selectivity to minimize outages

Alta confiabilidad: 100kA capacidad de corte, arc-free design for personnel and equipment safety

Configuración flexible: Withdrawable/fixed, 3P/4P, multiple terminations for various installations

Smart Monitoring: LCD real-time display, event logging for diagnostics and preventive maintenance

Expandability: Supports PR120/V (voltage monitoring), PR120/K (load control), PR120/D (directional protection)

Comunicación: Optional Modbus, Profibus, Ethernet/IP for IIoT integration

Eco-certified: RoHS and REACh compliant, low power consumption (<50W control circuit)

  1. Detailed Protection Functions (PR123/P-LSIG)
ProtecciónDescripciónAdjustable RangeSolicitud
Sobrecarga (l)tiempo inverso, prevents overheating0.4–1.0In, 0.1–60smotores, transformadores, cables
Short-Time Delay (S)Definite/inverse time for selectivity2–10In, 0.05–3sCascaded distribution, no upstream tripping
Instantáneo (I)No-delay trip for severe faults5–20InEmergency short-circuit protection
Ground Fault (GRAMO)Detects earth current, shock/fire prevention0.2–0.8In, 0.1–1sPersonnel and insulation safety
Phase Unbalance (Ud.)Monitors phase current difference10%–50% unbalanceThree-phase motor protection
Subtensión (ultravioleta)Detects voltage drop60%–90%Un, 0.1–10sCritical equipment voltage stability
Sobretensión (VO)Detects overvoltage105%–120%Un, 0.1–10sGrid fluctuation protection
Overtemperature (OT)Internal trip unit thermal protectionFactory setSelf-protection in harsh environments
  1. Alternativas

6.1 ABB Same-Series Alternatives

ModeloCaracterísticasSolicitud
E3H 3200 R2500 PR123/P-LSIG2500Una corriente nominal3200A frame with lighter load
E3H 3200 R3200 PR122/P-LSIGPR122/P (basic trip unit)Budget-friendly full protection
E3H 3200 R3200 PR123/P-LSIWithout ground fault protectionSystems not requiring earth fault protection
E3N 3200 R3200 PR123/P-LSIGE3N (medium breaking 65kA)Lower short-circuit duty

6.2 Cross-Brand Alternatives

MarcaAlternative ModelMatching Specs
SchneiderMT32H100 LSIG3200A, 100el, LSIG
siemens3WL3225-3CB36-4GA03200A, 100el, LSIG
Interruptor ChangshuCW3-3200/3P 100kA LSIGDomestic high-performance alternative
chintNA1-3200X-3200M/3PEconomic domestic alternative
  1. Selección & Notas de instalación
  2. Marco & Rated Current Match: E3H max 3200A; select trip rating 630A-3200A based on load
  3. Protection Configuration:

LSIG: Full protection for main incomers and critical loads

LSI: Without ground fault for general distribution

LI: Basic overload + instantaneous for feeders

  1. Mounting Type:

Withdrawable (PAG): For frequent maintenance, online replacement

Fijado (F): Space-limited, low-maintenance sites

  1. Termination:

HR: Rear connection

FR: Front connection

V: Vertical for busbar systems

  1. Accesorios:

Contactos auxiliares: Up to 10NO+10NC

Undervoltage release: Loss-of-voltage protection

Shunt trip: Remote tripping

Communication modules: Smart monitoring

  1. Referencia de precio (Tax-included, RMB)
ConfigurationGama de preciosNotas
Withdrawable 3P28,000 - 35,000With PR123/P-LSIG
Withdrawable 4P30,000 - 38,000With neutral protection
Fixed 3P25,000 - 32,000~10% lower than withdrawable
Fixed 4P27,000 - 35,000With neutral protection
Modbus Communication Module2,000 - 3,000Optional extra
  1. Ventajas principales
  2. Full Selectivity: LSIG with precise settings minimizes outage area
  3. Alta confiabilidad: 100kA breaking + arc-free design
  4. Smart Monitoring: LCD and event logs for easy diagnostics
  5. Flexible Layout: Multiple mounting, polo, and connection options
  6. IIoT Ready: Industrial communication for intelligent power management

Complete List of ABB SACE EMAX Series & Cross-Brand Comparison

  1. EMAX Naming Convention & Parámetros principales

1.1 Desglose del modelo

Segmento de modeloDescripciónEjemplo
E1/E2/E3/E4/E6/X1Frame size (E1=1600A, E2=2500A, E3=3200A, E4=4000A, E6=6300A, X1=630A)E3H
H/NBreaking class (H=high, N=medium)h
RXXXTrip rated currentR3200
PR121/PR122/PR123Trip unit type (PR123 = high-end with LCD)PR123/P
LSIG/LSI/LIProtection setLSIG
P/FMontajePAG

Standard Example: E3H 3200 R3200 PR123/P-LSIG-P

Global Order Code: 1SDA060849R1 (withdrawable) / 1SDA056503R1 (fixed)

1.2 Breaking Capacity Classes

ClaseBreaking Capacity at 400VSolicitud
norte65elGeneral industry & comercial
h100elIndustria pesada & main distribution
V150elHigh fault current areas (petrochemical, metalurgia)
  1. Full EMAX Model List

2.1 Standard Range (X1/E1/E2/E3/E4/E6)

MarcoMarco actualRango actualBreakingStandard TripProtecciónMontajeTypical Order Code
X1630A250–630Anorte (42el)PR121/PLSIGP/F1SDA052101R1
E11600A630–1600Anorte (65el), h (100el)PR122/PLSIGP/F1SDA053101R1
E22500A1250–2500Anorte (65el), h (100el)PR122/PLSIGP/F1SDA054101R1
E33200A1600–3200Anorte (65el), h (100el), V (150el)PR123/PLSIGP/F1SDA056503R1
E44000A2000–4000Anorte (65el), h (100el), V (150el)PR123/PLSIGP/F1SDA058101R1
E66300A3200–6300Ah (100el), V (150el)PR123/PLSIGP/F1SDA060101R1

2.2 Special Application Versions

SuffixSignificadoSolicitudEjemplo
/corriente continuaDC dedicatedSolar, wind, energy storageE3H 3200 R3200 PR123/P-LSIG/DC
/VFVFD output ratedInverter side protectionE2H 2500 R2500 PR122/P-LSIG/VF
/LTTLow temp tolerant-40°C a +70°CE1H 1600 R1600 PR122/P-LSIG/LTT
/EEnhanced voltage690–1150V ACE3H 3200 R3200 PR123/P-LSIG/E

2.3 Trip Unit Comparison

Trip UnitCaracterísticasMostrarLogCommSolicitud
PR121/PBasic LI/LSILED10 eventsNingunoSimple distribution
PR122/PStandard LSIGLED20 eventsModbus optionalGeneral industry
PR123/PAdvanced LSIG+LCD100 eventsModbus/ProfibusCritical loads & centros de datos
  1. ABB EMAX vs Other Brands (Direct Match)

3.1 Full Cross-Brand Table

ABB EMAX ModelFrame/InBreakingProtecciónSchneidersiemensChangshuchint
E1H 1600 R1600 PR122/P-LSIG1600A/1600A100elLSIGMT16H100 LSIG3WL1120-3CB36-4GA0CW3-1600/3P 100kA LSIGNA1-1600X-1600M/3P LSIG
E2H 2500 R2500 PR122/P-LSIG2500A/2500A100elLSIGMT25H100 LSIG3WL1225-3CB36-4GA0CW3-2500/3P 100kA LSIGNA1-2500X-2500M/3P LSIG
E3H 3200 R3200 PR123/P-LSIG3200A/3200A100elLSIGMT32H100 LSIG3WL1332-3CB36-4GA0CW3-3200/3P 100kA LSIGNA1-3200X-3200M/3P LSIG
E4H 4000 R4000 PR123/P-LSIG4000A/4000A100elLSIGMT40H100 LSIG3WL1440-3CB36-4GA0CW3-4000/3P 100kA LSIGNA1-4000X-4000M/3P LSIG
E6H 6300 R6300 PR123/P-LSIG6300A/6300A100elLSIGMT63H100 LSIG3WL1663-3CB36-4GA0CW3-6300/3P 100kA LSIGNA1-6300X-6300M/3P LSIG
E3N 3200 R2500 PR122/P-LSI3200A/2500A65elLSIMT32N100 LSI3WL1325-3CB36-4GA0CW3-3200/3P 65kA LSINA1-3200X-2500M/3P LSI
X1N 630 R630 PR121/P-LI630A/630A42elLIMT06N100 LI3WL1063-3CB36-4GA0CW3-630/3P 42kA LINA1-630X-630M/3P LI

3.2 Key Model Matching (with Order Codes)

ABB CodeModelo completoSchneider CodeSiemens CodeMatch Specs
1SDA056503R1E3H 3200 R3200 PR123/P-LSIG-FLV432630 (MT32H100)3WL1332-3CB36-4GA03200A, 100el, LSIG, fixed
1SDA060849R1E3H 3200 R3200 PR123/P-LSIG-PLV432631 (MT32H100)3WL1332-3CB36-4GA13200A, 100el, LSIG, withdrawable
1SDA054101R1E2H 2500 R2500 PR122/P-LSIG-PLV432531 (MT25H100)3WL1225-3CB36-4GA12500A, 100el, LSIG, withdrawable
1SDA053101R1E1H 1600 R1600 PR122/P-LSIG-PLV432431 (MT16H100)3WL1120-3CB36-4GA11600A, 100el, LSIG, withdrawable
1SDA052101R1X1N 630 R630 PR121/P-LI-PLV432031 (MT06N100)3WL1063-3CB36-4GA1630A, 42el, LI, withdrawable
  1. Selección & Replacement Guidelines

4.1 Technical Matching Rules

CategoríaMatching PrincipleNotas
Frame/InDirect match or downsize630A frame cannot exceed 630A
Capacidad de ruptura≥ system short-circuit currentH-class (100kA+) recommended for industry
ProtecciónMatch or upgradeLSIG can replace LSI; not vice versa
MontajeSame type preferredWithdrawable can replace fixed; may need cabinet mods
Control VoltageIdentical or universal220V AC/DC preferred for flexibility
ConexiónSame orientationFront/rear/vertical must align

4.2 Brand Strength Comparison

MarcaCore StrengthsTypical Use
ABB EMAXUp to 150kA breaking, PR123 smart trip, arc-free, 30,000 mech cyclesCritical loads, centros de datos, heavy industry
Schneider MTMultiple breaking levels, Micrologic precision, modular, global supportCommercial, OEM, renewables
Siemens 3WL690V rated, protección contra sobretensiones, thermal-magnetic options, full commsInfraestructura, rail, petrochemical
Changshu CW330–40% lower cost, form-fit compatible, domestic supplyProyectos sensibles a los costos
Chint NA1Ultra-economical, full LSIG option, simple maintenanceResidential, light industry, rural grids

4.3 Referencia de precio (Tax-included, RMB)

MarcoABB EMAXSchneider MTSiemens 3WLChangshu CW3Chint NA1
630A8,000–12,0007,500–11,0008,500–12,5004,000–6,0003,000–5,000
1600A15,000–22,00014,000–20,00016,000–23,0008,000–12,0006,000–10,000
3200A28,000–35,00027,000–34,00029,000–36,00015,000–20,00012,000–18,000
6300A50,000–65,00048,000–62,00052,000–68,00028,000–38,00025,000–35,000
  1. Recomendaciones de selección
  2. Critical Loads: Use ABB EMAX or Schneider MT with PR123/Micrologic trips
  3. Cost Efficiency: 630A-1600A → Changshu CW3 or Chint NA1
  4. Cross-Brand Replacement:

630A-3200A: Direct form-fit replacement

4000A+: Consult manufacturer for cabinet compatibility

  1. Upgrades:

Replace old ACBs (ME/DW15) with EMAX/MT/3WL

Add communication for smart power management