Chint NHR17-63/3 fuse-type isolating switch - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

eléctrico/

Chint NHR17-63/3 fuse-type isolating switch

Chint NHR17-63/3 is a fuse-type isolating switch, mainly used in industrial power distribution systems, with short-circuit protection and circuit isolation functions. The following is an analysis of its core information: I. Product Positioning and Core Parameters 1. Basic FunctionsUsed as a power switch, isolating switch, and emergency switch, it can provide protection in power ...

  • Detalles del producto

Chint NHR17-63/3 is a fuse-type isolating switch, mainly used in industrial power distribution systems, with short-circuit protection and circuit isolation functions. The following is an analysis of its core information:

I. Product Positioning and Core Parameters

1. Basic Functions

Used as a power switch, isolating switch, and emergency switch, it can provide protection in power distribution circuits and motor circuits with high short-circuit currents.

Compliant with international standard IEC 60947-3 and Chinese standard GB/T 14048.3, garantizando seguridad y confiabilidad.

2. Parámetros clave

Rated insulation voltage: 1000V, adecuado para entornos de alto voltaje.

Rated operating voltage: up to 690V, covering most industrial scenarios.

Rated current: 63A (conventional heating current), capable of carrying stable loads.

Pole number: 3 polos, suitable for three-phase circuits.

Short-circuit breaking capacity: ≥50kA (at 400V), able to quickly cut off fault currents.

3. Características estructurales

Adopts screw-fixed installation, with a compact structure and light weight (approximately 3.26kg for reference to the same series products), facilitating on-site construction.

Conductive material is brass, ensuring low resistance and high conductivity.

Equipped with a manual operating handle, which can intuitively display the switch status (closed/open).

II. Application Scenarios and Limitations

1. Applicable Fields

Industrial power distribution systems: such as isolation and protection of main circuits in factories and substations.

Motor control: used as a power switch in motor circuits, but direct starting/stopping of a single motor is not recommended (needs to be used with contactors).

Emergency power switching: quickly cuts off the circuit in case of failure to ensure maintenance safety.

2. Precauciones

Capacitor cabinet limitation: Specifications of 63A and below are not applicable to capacitor cabinets because they cannot withstand closing inrush currents.

– Requisitos medioambientales: Ambient temperature -5℃~+40℃, altitude ≤2000m, pollution degree 3. It should be installed in places without vibration or corrosive gases.

III. Fuse Selection and Replacement

1. Matching Fuse Models

At 400V: It is recommended to use RT19-125 or NT00 series fuses. The rated current of the fuse link can be 20-63A (needs to match the load current).

At 690V: Fuses with higher breaking capacity (such as RT16-00 series) are required, with a fuse link current range of 20-100A.

2. Replacement Steps

Power-off operation: First disconnect the upper-level power supply to ensure no voltage in the circuit.

Remove the old fuse: Loosen the fixing screws and pull out the fuse link (be careful to avoid electric shock).

Install the new fuse: Select a matching fuse link, insert it in the original direction, and tighten the screws to ensure good contact.

Test and restore: After closing, check whether the circuit is normal and whether the fuse indicator light is on.

IV. Recomendaciones de instalación y mantenimiento

1. Método de instalación

Fixed to the distribution cabinet or mounting plate with screws, ensuring the mounting surface is flat and not loose.

When wiring, use wires that meet specifications (recommended cross-sectional area ≥6mm²) and tighten the terminal screws to avoid overheating.

2. Mantenimiento diario

Regularly check whether the contacts are oxidized or ablated, and replace them in time if there is a problem.

Clean the shell once every 1-2 years to prevent dust accumulation from affecting heat dissipation.

If the fuse blows frequently, it is necessary to check whether there is an overload or short-circuit fault in the circuit.

V. Alternative Models and Upgrade Schemes

1. Alternativas de la misma serie

For higher current requirements, NHR17-100/3 (100A) or NHR17-160/3 (160A) se puede seleccionar.

For auxiliary contact functions, versions with the suffix “1” can be used (such as NHR17-63/31).

2. Competitor Comparison

Compared with Schneider’s OFA series, NHR17 has a price advantage and supports domestic fuses.

Compared with Siemens’ 3serie de vehículos recreativos, NHR17 has a higher breaking capacity at 400V (≥50kA vs 36kA).

Resumen: Chint NHR17-63/3 is a cost-effective industrial-grade fuse-type isolating switch, suitable for protection and control in medium and low-voltage power distribution systems. During selection and use, attention should be paid to fuse matching, installation environment, and maintenance requirements to ensure long-term reliable operation.