LC1E630M7N is a 3‑pole AC contactor from Schneider EasyPact TVS (formerly TeSys E) serie. The breakdown is as follows:
| Parte | Significado |
| LC1 | Basic contactor series identifier |
| mi | EasyPact TVS (economic) serie, mainly for China market |
| 630 | Rated operational current 630A (AC‑3 at 440V) |
| METRO | Código de voltaje de la bobina: 220V y |
| 7 | Coil supports 50/60Hz |
| norte | Domestic version (performance is essentially the same as LC1E630M7) |
- Key Technical Specifications
| Artículo | Valor | Notas |
| polacos | 3PAG (3 NO) | Contactos principales: 3 NO |
| Corriente operativa nominal | 630A | AC‑3, 440V, 50/60Hz |
| Rated operational voltage | ≤ 690V AC | Max main circuit voltage |
| Control coil | 220V y, 50/60Hz | Inrush: aprox. 1600Virginia, Holding: aprox. 200Virginia |
| Categoría de utilización | AC‑3 | For starting, running, stopping three‑phase induction motors |
| Resistencia mecánica | Aprox.. 10 millones de operaciones | Standard conditions |
| Resistencia eléctrica | Aprox.. 100,000 operaciones | AC‑3 at 630A |
| Montaje | 35mm DIN rail or bolt fixing | W≈200mm, H≈220mm, D≈100mm |
| Contactos auxiliares | Can add 2 o 4 módulos | Not included; se vende por separado |
- Aplicaciones
- Control of medium and large three‑phase induction motors (aprox. 315kW at 440V)
- Main circuit control in industrial automation lines
- Power equipment control in building electrical and HVAC systems
- Heavy‑duty loads requiring frequent starting and stopping
- Can combine with LRE series thermal relays (p.ej., LRE630N) as a starter for motor overload protection
- Características clave
- High‑reliability design: Optimized arc extinguishing system for harsh industrial environments
- Amplia compatibilidad de voltaje: Coil operates stably at 85%–110% of rated voltage
- Diseño modular: Soporta contactos auxiliares, mechanical interlocks, supresores de sobretensiones, etc..
- Certificaciones: Complies with IEC 60947‑4‑1, ES 14048.4, etc..
- Instalación & Mantenimiento
- Clearance: ≥50mm top/bottom, ≥20mm left/right for cooling
- Alambrado: Main circuit recommended ≥185mm² copper cable; torque approx. 55Nuevo Méjico
- Maintenance interval: Every 6 months in normal environment; 3 months in dusty areas
- Solución de problemas: Check coil voltage if no pull‑in; check load and operating frequency if contact erosion
- Reemplazos & Compatible Products
- Schneider direct replacements:
LC1N630M7N: Official successor to LC1E series, same economic positioning
LC1D620M7C: Standard contactor, 620A, more stable performance
LC1F630M7: High‑performance series for severe duty
- Cross‑brand references:
TEJIDO: AF630‑30‑22 (630A, 220V y)
siemens: 3RT2076‑6AP36 (630A, 220V y)
CHINT: CJX2‑630S (630A, 220V y)
- Important Notes
- Some LC1E models are discontinued; LC1N series is recommended for new projects
- Verify load type (resistive/inductive), operation frequency, and environment during selection
- Match thermal relay rating to motor rating (630A typically controls ~315kW motors)
Better Schneider Contactors Than LC1E630M7N
Contactors superior to LC1E630M7N fall into three categories:
Reemplazo de actualización (LC1N630M7N / D3N),
Standard Enhanced (LC1D620M7C / LC1D630M7C),
High‑Performance Premium (LC1F630M7 / LC1G630M7).
Recommendation:
New projects → LC1N630M7N
Severe applications → LC1D620/630
Frequent starts / high altitude / special certs → LC1F / LC1G
- Posicionamiento & Limitations of LC1E630M7N
LC1E630M7N belongs to Schneider EasyPact TVS (economic) series – a domestic 3‑pole contactor, 630A (AC‑3, 440V), coil 220V AC 50/60Hz.
Limitaciones:
Some ratings discontinued (06A–95A phased out)
Electrical endurance approx. 100,000 operaciones (AC‑3), lower than standard/high‑performance models
Narrower ambient temperature range; limited special certifications (marine, railway)
- Graded Recommendations
2.1 Reemplazo de actualización: LC1N630M7N (EasyPact D3N)
Official replacement for LC1E, improved economic version.
| Advantage | Improvement |
| Actuación | Electrical endurance ↑ ~20%; mechanical endurance 12 millón |
| Design | More complete modularity, better accessory compatibility |
| Fiabilidad | Upgraded arc chamber for harsh environments |
| Instalación | Optimized terminals, stable torque, easier maintenance |
| Compatibilidad | Same footprint as LC1E for drop‑in replacement |
2.2 Standard Enhanced: LC1D620M7C / LC1D630M7C (TeSysD)
Schneider’s mainstream standard series, balanced performance and cost.
| Key Benefit | Especificación |
| Higher durability | Resistencia eléctrica 150,000 operaciones (AC‑3); mechanical 15 millón |
| Wide environment | ‑25°C to +70°C; altitude ≤4000m (vs ≤2000m for LC1E) |
| Special certs | Supports marine (DNV), railway, etc.. |
| Safety features | 1NO + 1NC standard; mirror contacts available |
| Rating range | LC1D620 (620A), LC1D630 (630A) |
2.3 High‑Performance Premium: LC1F630M7 (TeSys F) / LC1G630M7 (TeSys Giga)
For severe duty: frequent starts, heavy loads, extreme environments.
| Serie | Key Advantages | Aplicaciones |
| TeSys F (LC1F) | • Electrical endurance: 200,000 operaciones (AC‑3) | Metallurgy, minería, compresores grandes |
| • Higher current margin (630A → short‑time 700A) | Frequent operation (≥1200 operations/h) | |
| • Lower holding power (≈180VA) | ||
| TeSys Giga (LC1G) | • Up to 300,000 operaciones (AC‑3) | Offshore platforms, high altitude (>4000metro), ‑40°C |
| • Rated insulation voltage 1000V, stronger breaking capacity | Critical high‑reliability equipment | |
| • IP20 standard, some IP65 |
- Core Specification Comparison
| Artículo | LC1E630M7N | LC1N630M7N | LC1D620M7C | LC1F630M7 |
| Corriente nominal (AC‑3, 440V) | 630A | 630A | 620A | 630A |
| Resistencia eléctrica (AC‑3) | 100k | 120k | 150k | 200k |
| Resistencia mecánica | 10METRO | 12METRO | 15METRO | 20METRO |
| Coil holding power | 200Virginia | 190Virginia | 185Virginia | 180Virginia |
| Ambient temp | ‑5°C ~ +60°C | ‑10°C ~ +65°C | ‑25°C ~ +70°C | ‑30°C ~ +75°C |
| Certificaciones | Básico | Básico + partial industrial | Full industrial | Lleno + marine |
| Price level | Económico | Económico +10% | Estándar +30% | De primera calidad +50% |
Nota: k = 1000 operaciones; M = 1 millones de operaciones
- Selection Advice
- New projects first choice: LC1N630M7N – perfect drop‑in replacement, better performance, affordable
- General industrial use: LC1D620M7C – higher reliability for automation and HVAC
- Severe duty: LC1F630M7 – frequent starts (>600/h), carga pesada, temperatura alta
- Critical/extreme environment: LC1G630M7 – offshore, high altitude, low temperature, maximum reliability
- Important Warnings
- Although LC1E is not fully discontinued, Schneider officially recommends LC1N for better supply continuity
- 630A contactors typically control ~315kW (440V) three‑phase motors; match load, duty cycle, and environment
- Use matched thermal relays: LRE630N (LC1E/LC1N) or LRD630 (LC1D/LC1F)
contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares