 LS ELECTRIC ABE404B-4P-400A MCCB - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

cortacircuitos/

LS ELECTRIC ABE404B-4P-400A MCCB

  Model Part Meaning ABE Series code, Meta-MEC economy MCCB, thermal-magnetic trip, low breaking capacity (economy type) 40 Frame rating current 400A 4 4 polos (4PAG), suitable for three-phase four-wire system protection B Breaking capacity class B (10kA@AC380V) 400A Rated operational current 400A, set by plug module Key Technical Parameters Item Specification Description Product Type ...

  • Detalles del producto

 

Model PartSignificado
ABEcódigo de serie, Meta-MEC economy MCCB, thermal-magnetic trip, low breaking capacity (economy type)
40Frame rating current 400A
44 polos (4PAG), suitable for three-phase four-wire system protection
BBreaking capacity class B (10kA@AC380V)
400ARated operational current 400A, set by plug module
  1. Parámetros técnicos clave
ArtículoEspecificaciónDescripción
Tipo de productoEconomía Disyuntor de caja moldeada (MCCB)Thermal-magnetic trip, fixed mount
Tensión nominalAC 600V, Ui 690VCumple con IEC 60947-2
Frecuencia nominal50/60HzUniversal frequency range
Capacidad de rupturaIcu=10kA@AC380VClass B economy breaking capacity
Tipo de viajeFixed thermal-magnetic tripProtección contra sobrecarga (inverse time) + protección contra cortocircuitos (instantaneous)
Tensión nominal de aislamientoUi=690VMaximum voltage for insulation performance
Mechanical Endurance8500 operacionesStandard operating cycles
Electrical Endurance1000 operacionesOperating cycles at rated current
Mounting TypeFixed typeStandard 35mm DIN rail or panel mount
ConexiónFront connection / Rear connectionOptional for different installations
Applicable StandardsCEI 60947-1/2, EN 60947-1/2International electrical standards
  1. Series Model List (400AF Frame)
ModelopolacosCapacidad de rupturaRango de corriente nominal
ABE402b2PAG10el250A, 300A, 350A, 400A
ABE403b3PAG10el250A, 300A, 350A, 400A
ABE404b4PAG10el250A, 300A, 350A, 400A
ABS402b2PAG25el250A, 300A, 350A, 400A
ABS403b3PAG25el250A, 300A, 350A, 400A
ABS404b4PAG25el250A, 300A, 350A, 400A
ABH402b2PAG35el250A, 300A, 350A, 400A
ABH403b3PAG35el250A, 300A, 350A, 400A
ABH404b4PAG35el250A, 300A, 350A, 400A
  1. Recommended International Brand Replacements
MarcaSerieModelo de reemplazoParámetros clave de coincidencia
SchneiderEZD SeriesEZD400E44004PAG, 400A, 10el, thermal-magnetic trip
siemens3VT Series3VT8440-1AA034PAG, 400A, 10el, thermal-magnetic trip
TEJIDOTmax SeriesT2N400 TMD 400/400 FF 4P4PAG, 400A, 10el, thermal-magnetic trip
EatonPower DefenseLZMN4-A400-I4PAG, 400A, 10el, thermal-magnetic trip
Changshu SwitchCM3 SeriesCM3-400M/4300B 400A4PAG, 400A, 10el, thermal-magnetic trip
  1. Applications & Notas de selección
  2. Aplicaciones típicas

End protection in low-voltage distribution systems, p.ej., lighting and power distribution in commercial buildings and industrial plants

Three-phase asynchronous motor protection (≤200kW, 380V)

Capacitor bank protection

Small generator outlet protection

  1. Selection Guidelines

Confirm system voltage (≤600V) and frequency (50/60Hz)

Calculate circuit rated current to ensure 400A meets long‑term operation

Evaluate short-circuit level: if >10el, use higher breaking capacity ABS (25el) or ABH (35el) serie

Consider pole requirement: 4P for neutral protection applications

Confirm mounting (fixed/drawout) and connection direction (front/rear)

  1. Características del producto & Ventajas
  2. Económico & Practical: ABE series is cost-effective for budget‑limited projects
  3. Standard Design: Complies with IEC standards, interchangeable with other brands
  4. Reliable Protection: Thermal-magnetic trip provides basic overload and short-circuit protection
  5. Flexible Installation: Supports front/rear wiring and multiple mounting methods
  6. Complete Accessories: Can be equipped with auxiliary contacts, contactos de alarma, liberación de subtensión, etc..
  7. Mantenimiento & Solución de problemas
  8. Inspección periódica: Inspect appearance and tighten terminals quarterly to avoid looseness or overheating
  9. Trip Test: Perform manual trip test annually to verify mechanical reliability
  10. Solución de problemas:

Frequent overload tripping: Check load or replace with higher rated model

Short-circuit tripping: Locate and repair short circuit before closing

Failure to close: Check mechanical jam or replace damaged parts

LS ELECTRIC ABE404B-4P-400A is an economy 4-pole MCCB with 400A rated current and 10kA breaking capacity, suitable for low-voltage distribution systems with moderate breaking requirements. Para mayor capacidad de corte, use ABS (25el) or ABH (35el) serie.

Applications of LS ELECTRIC ABE404B-4P-400A MCCB

Posicionamiento central:

This 4-pole economy MCCB (4PAG, 400A, 10el) is mainly used for end protection in low‑voltage distribution systems, especially where neutral protection is required, short-circuit current ≤10kA, and budget is limited.

  1. Commercial Building Distribution
SolicitudSuitabilitySelection Tip
Main distribution board main breaker4P protects 3-phase 4-wire; 400A fits small‑to‑medium commercial buildingsTotal load ≤320A (80% duty), short-circuit ≤10kA
Main A/C protection400A for large central A/C units (≤200kW, 380V)Match compressor inrush; recommend undervoltage release
Emergency lighting4P ensures neutral continuity for reliable emergency operationUse with EPS/UPS; front connection for easy maintenance
Elevator room power400A for multiple elevators; 4P prevents neutral faultsInstall in dedicated cabinet; ensure ventilation

Casos típicos:

3–5 story office buildings, chain supermarkets, hotels as main or important branch breaker.

  1. Industrial Plant Applications
  2. General Machinery

Main breaker for small‑medium production lines: 400A covers multiple branches; 10kA suits general industrial short-circuit levels

Motor group protection: Total power ≤200kW, used with thermal relays for precise protection

Auxiliary equipment: aficionados, zapatillas, compresores; 4P for control circuits with neutral

  1. Specific Industries

Food processing: Cost-effective for light industry; 4P ensures safety and quality

Electronic assembly: 400A for multiple lines; 4P avoids neutral drift affecting precision equipment

Warehouse power: Main breaker for lighting and forklift charging

Advertencia:

If short-circuit current >10el, upgrade to LS ABS (25el) or ABH (35el).

  1. Public & Residential Buildings
  2. Education & Médico

School main distribution: 4P protects lighting, A/C, computer rooms; 400A for whole building

Community hospital: 4P for medical equipment with neutral; economy for primary care

Stadium auxiliary systems: Lighting, audio, seats; 400A for local zones

  1. Infraestructura

Small wastewater treatment: 400A for pumps and blowers; 4P prevents control system failure

Urban landscape lighting: Main breaker for multi-loop lighting with reliable neutral

Small waste transfer station: 400A for compressors and conveyors; low operating cost

  1. Special Applications
  2. Capacitor Bank Protection

For capacitor banks ≤100kvar; 4P prevents inrush and short-circuit during switching

Recommend adding SPD for surge protection

  1. Small Generator Systems

Main breaker for generators ≤300kVA; 4P ensures safe isolation from grid

Used with synchronizing equipment for smooth switch between mains and generator

  1. Temporary Power

Construction site temporary power main breaker; 400A for cranes, welders

4P suitable for harsh site conditions; prevents electric shock from broken neutral

  1. Key Selection & Application Criteria
FactorRecomendadoNo apto para
Short-circuit level≤10kA: suitable; >10el: use ABS/ABHZonas de alto riesgo (chemical, minería) con >10el
Load typeResistive & inductive loads (iluminación, motores)Large rectifiers, arc furnaces, high nonlinear loads
Earthing systemTN-S, TT systems (4P neutral protection)IT systems (operating rooms, minas)
EnvironmentIndoor dry, ≤40°COutdoor, damp, explosive areas (needs special enclosure)
Operation frequencyOperación poco frecuente (≤12/day)Frequent duty (grúas, elevator main circuits)
  1. Application Advantages
  2. Económico: High cost-performance for budget projects
  3. Full protection: 4P design covers 3-phase + neutral for modern distribution
  4. Standard compliance: CEI 60947-2, interchangeable with major brands
  5. Instalación flexible: Front/rear wiring + 35carril DIN mm
  6. Reliable: Mecánico 8500, eléctrico 1000 operaciones

Best Combination:

Use ABE404B-4P-400A as main breaker + LS MCBs for branch protection to form a reliable two‑stage system.

For higher performance or electronic protection, upgrade to ABS (25el), ABH (35el), or ABN (electronic trip) serie.