Schneider PM750MG Multifunction Power Meter

Interrumpido (discontinued in China on 2014-12-31). No new original units available from manufacturer. Only second-hand or surplus stock parts on market. METSEPM53 series is the preferred replacement. Model Code Explanation PM750: High-end multifunction power monitor of PM700 series MG: Modbus RS485 communication version, equipped with digital I/O, harmonic measurement and min/max value logging Core Functions ...

  • Detalles del producto

Interrumpido (discontinued in China on 2014-12-31). No new original units available from manufacturer. Only second-hand or surplus stock parts on market. METSEPM53 series is the preferred replacement.

Explicación del código del modelo

PM750: High-end multifunction power monitor of PM700 series

mg: Modbus RS485 communication version, equipped with digital I/O, harmonic measurement and min/max value logging

Funciones principales

  1. True RMS full electrical measurement: 3-fase / single-phase voltage, actual, potencia activa/reactiva/aparente, factor de potencia, frecuencia; phase-wise & total active energy kWh, reactive energy kvarh, demanda / peak demand, máximo & minimum value recording.
  2. Power quality: Total Harmonic Distortion (THD), harmonic analysis up to 15th order, sampling rate 32 samples per cycle.
  3. Interfaz de E/S: 2 entradas digitales (DE), 1 static digital output (HACER). DO configurable for pulse output (energy pulse), alarm output or remote control. DI for status acquisition or demand synchronization trigger.
  4. Alarm function: 15 groups of user-defined threshold alarms (sobretensión, subtensión, sobrecorriente, power limit violation, etc.), local indication + alarm report via communication.
  5. Comunicación: RS485, Modbus RTU protocol, up to 19200bps, compatible with PLC, SCADA and energy management systems.
  6. Mostrar: LCD retroiluminado, 6-line display, panel cutout mounting.

Especificaciones eléctricas clave

ArtículoPresupuesto
Measuring VoltageLine-to-line: 10~480 VCA; Phase-to-neutral:10~277V AC, 45~65Hz
Entrada actualCT secondary 0.005~6A (5A/1A CT both supported)
Fuente de alimentaciónC.A.:115~415V; corriente continua:125~250V; Power consumption ≤5VA
ExactitudCurrent ±0.4%; Voltage ±0.3%; Power ±0.5%; Active energy Class 0.5S (IEC62053-22)
DE12~36VDC, nominal 24 VCC, 2.5kV isolation
HACERStatic transistor output, supports pulse / alarm mode

Aplicación típica

LV/MV switchgear, factory power distribution room, distribución de energía en edificios, computer room incoming cabinet. Used for power monitoring, energy consumption statistics, power quality monitoring and status acquisition; commonly used as spare parts for legacy project retrofits.

OEM Replacement Models (Llave)

PM750MG → METSEPM5330 (Modbus RS485); For Ethernet version: METSEPM5340 (Modbus TCP)

PM53 series is upgraded replacement for PM750, full & enhanced function coverage, identical panel cutout size for direct mounting. Modbus register addresses are incompatible, reconfiguration required. High-end alternative: PM8240/PM8243.

Lista de verificación de solución de problemas comunes

  1. No current / reversed current reading: CT S1/S2 reversed; CT secondary shorting link not removed; CT ratio not configured in meter.
  2. Modbus communication failure: Missing termination resistor, A/B wire reversal, mismatched address/baud rate; unstable meter supply.
  3. DO no action: Verify DO mode configuration (pulse/alarm) and polarity of external circuit.
  4. Abnormal harmonic reading: Cableado suelto, insufficient PT/CT accuracy, heavy distortion on load side.

Notas complementarias

Dimensión de recorte: 92×92mm, panel flush mounting

Estándares: CEI 62053, ANSI C12.20; compatible with 3P3L /3P4L / sistemas monofásicos

Second-hand spare note: LCD backlight aging, damaged RS485 transceiver chip, parameter loss due to internal battery depletion.

  1. PM750MG Modbus RTU Register Summary (Holding Registers, 4xxxx, 16poco; Energy values as 32bit, ocupa 2 registros consecutivos)

Protocol Notes: Modbus RTU, register starts at 40001 (Schneider estándar). Some software uses 0-based addressing (40000), pay attention to offset. For float /32bit unsigned integer, palabra alta primero. Energy registers come with multiplier register; readings must be multiplied by multiplier factor.

Firmware version: V3.050 (common firmware for PM700 series)

Modbus Address(4xxxx)Tipo de datosNombreDescripción
40001UINT16V1 Phase VoltageTensión de fase, multiplier register 40013
40002UINT16V2 Phase Voltage
40003UINT16V3 Phase Voltage
40004UINT16V12 Line Voltage
40005UINT16V23 Line Voltage
40006UINT16V31 Line Voltage
40007UINT16I1 Phase A CurrentActual, multiplier register 40014
40008UINT16I2 Phase B Current
40009UINT16I3 Phase C Current
40010UINT16Frequency Hz
40011UINT16Total Active Power kWPower multiplier 40015
40012UINT16Total Reactive Power kvar
40013UINT16Voltage Multiplier (10^n)p.ej. value=2 → ×100
40014UINT16Current Multiplier (10^n)
40015UINT16Power Multiplier (10^n)
40016UINT16Total Power FactorRange 0~1000, divide by 1000
4,002,040,021UINT32Total Active Energy kWh40020=High word,40021=Low word; multiplier 40108
4,002,240,023UINT32Total Reactive Energy kvarh
4,002,440,025UINT32Total Apparent Energy kVAh
40030UINT16Phase A THDCurrent total harmonic distortion
40031UINT16Phase B THD
40032UINT16Phase C THD
40040UINT16DI StatusBit0=DI1,Bit1=DI2
40041UINT16DO StatusBit0=DO1
40045UINT16Alarm Status WordAlarm mask
40108UINT16Energy Multiplier (10^n)Energy reading ×10^n, Importante!

Energy Calculation Example: 40020=0012, 40021=ABCD; 40108=2 → 0x0012ABCD ×10² = 1254860 ×100 = 125486000 Wh = 125486 kWh

Harmonics: 1~15th harmonic magnitudes, registers start at 40050, per-phase harmonic amplitude.

Communication Basic Parameters (PM750MG)

Protocolo: Modbus RTU

Velocidad de baudios: 2400/9600/19200

Paridad: Ninguno / Odd / Even; Stop bit:1

dirección de esclavo: 1~247

RS485 Terminals: A, B; 120Ω termination resistor at bus end

  1. PM750MG vs METSEPM5330 Function & Wiring Migration Comparison Table
ArtículoPM750MG (Old Meter)METSEPM5330 (Replacement Meter)Migration Notes
Tamaño de recorte92×92mm92×92mmIdentical panel cutout, direct mounting
Fuente de alimentaciónAC115~415V / DC125~250VAC100~415V / DC110~250VPower circuit can be reused directly
Entrada de voltaje10~480V line voltage10~480V line voltagePT secondary wiring unchanged; support 3P3L/3P4L
Entrada actualCT secondary 0.005~6ACT secondary 0.005~6ACT S1/S2 wiring unchanged, CT ratio must be reconfigured on new meter
DE2DE (24VCC)2DE (24VCC)External DI wiring can be kept
HACER1-channel static transistor output2-channel relay DO⚠️Major difference! PM750MG uses transistor DO; PM5330 is dry contact relay. Original DO pulse/alarm circuit needs redesign, higher load capacity.
Medición armónicaUp to 15th harmonicUp to 31st harmonicPM5330 enhanced power quality capability
Alarm Groups15 grupos35 gruposAlarm logic can be migrated, register addresses for alarms are fully different
ComunicaciónRS485 Modbus RTURS485 Modbus RTUPhysical A/B wiring unchanged. Register mapping is fully incompatible! PLC/SCADA program must be rewritten, old register addresses cannot be reused.
Energy TariffSingle tariff4 tarifasSupport time-of-use metering
ExactitudActive energy Class 0.5SActive energy Class 0.5SSame accuracy class
Registro de datosmáx. & Min valuesmáx. & mín. + Event logPM5330 supports event logging

Retrofit Risk Checklist (Mandatory for Site Replacement)

  1. DO circuit modification: PM750MG transistor output cannot drive heavy load. PM5330 uses relay. If original DO sends pulse to acquisition module, verify dry-contact pulse compatibility with acquisition device.
  2. Host software program reconstruction: Register address, data arrangement and multiplier logic are all different. All tags for PLC / KingView / ForceControl / SCADA must be reconfigured; old program cannot be copied directly.
  3. Parameter re-entry: relación TC, relación PT, system type (3P3L/3P4L), umbral de alarma, Modbus address and baud rate all require manual setup. Parameters from PM750MG cannot be imported into PM5330.
  4. Real-time clock: PM750MG internal battery loses parameters on power loss; PM5330 retains parameters after power loss, only clock resets.

III. Terminal Wiring Comparison

PM750MG Terminal Layout

  1. L1 L2 L3 N Voltage Input
  2. CT1 CT2 CT3 Current Input
  3. Terminales de potencia
  4. DI1 DI2 COM
  5. DO+ DO(Transistor)
  6. RS485 A B

METSEPM5330 Terminal Layout

  1. L1 L2 L3 N Voltage
  2. CT1 CT2 CT3 Current
  3. Fuerza
  4. DI1 DI2 COM
  5. DO1, DO2 (Relé, independent dry contact)
  6. RS485 A B

Voltaje, actual, DI and RS485 cables may remain untouched; DO wiring must be rewired.

  1. On-site Replacement Procedure
  2. Power off and confirm safety; record original PM750MG parameters (CT/PT ratio, system type, alarm settings, parámetros de comunicación).
  3. Remove old meter, keep voltage, Connecticut, DI and RS485 cables.
  4. Install METSEPM5330, connect voltage, Connecticut, DI and RS485; rework DO wiring separately.
  5. Power up, configure CT/PT ratio, system wiring type, Modbus address, baud rate and alarm thresholds.
  6. Verify real-time measurements: Voltaje, actual, fuerza; confirm CT polarity is correct.
  7. Modify PLC / SCADA Modbus program, debug communication.
  8. Compare accumulated energy readings, run continuous test to verify metering accuracy.

Schneider PowerLogic PM700 Series Full Model List (All discontinued)

Series basics: 92×92mm panel mounting, True RMS measurement, THD, min/max logging. Suffix Definition

mg: With RS485 Modbus RTU communication

California: North American ANSI version (rarely used in China; Chinese projects prefer models without CA suffix)

PAG: 2-channel solid-state pulse output

Lista completa de modelos

  1. PM700 Base model, sin comunicación, sin salida de pulso
  2. PM700CA North American base version
  3. PM700MG Base measurement + Modbus RS485
  4. PM700MGCA NA version + Modbus
  5. PM700P Base model + 2 solid-state pulse outputs, sin comunicación
  6. PM700PCA NA version with pulse output
  7. PM700PMG Base + salida de pulso + Modbus RS485
  8. PM700PMGCA NA version, legumbres + Modbus
  9. PM710 Base measurement + Modbus RS485, no DI/DO
  10. PM710CA NA PM710
  11. PM710MG Mainstream domestic PM710 (Modbus)
  12. PM710MGCA NA PM710MG
  13. PM750 Top tier, Modbus RS485, 2DI+1DO, función de alarma
  14. PM750MG Most common domestic model (modelo objetivo, Modbus version)
  15. PM750CA NA PM750
  16. PM750MGCA NA PM750MG

Comparison of 4 Modelos principales (Common for China Projects)

ModeloConfiguración centralSolicitud
PM700Basic electrical +THD/min-max, No comms, no pulseLocal display only, no SCADA connection
PM700PBasic electrical +THD, 2 pulse outputs, No commsEnergy pulse acquisition, no network
PM710MGBasic electrical +THD, Modbus RS485, No DI/DORemote power acquisition, no status points needed
PM750MGFull electrical +THD+15th harmonic, Modbus RS485, 2DI+1DO+threshold alarmsMonitoreo de energía, remote status acquisition, salida de alarma (largest installed base in China)

Discontinuación & Replacement Summary

APAC discontinuation date: 2015-04-30; Americas:2015-08-30. No new original production, solo excedente / repuestos de segunda mano.

PM700 / PM700P / PM710 → METSEPM51xx (PM5100 series)

PM750 / PM750MG → METSEPM53xx (METSEPM5330 RS485; METSEPM5340 Ethernet TCP)

Observaciones complementarias

  1. This series does NOT have PM720/PM730/PM740. Many documents are misleading. PM700 series only has four base platforms: PM700, PM700P, PM710, PM750.
  2. CA suffix = North American ANSI variant, differs in wiring logic & clasificación de voltaje. Avoid CA-suffix spares for China retrofits.
  3. All models share identical 92×92mm cutout and panel appearance; only internal I/O and communication hardware differ.