Modicon TM5 24VDC I/O Módulo de distribución de energía (PDM)
It belongs to Schneider TM5 distributed remote I/O series, compatible with M258 / LMC058 controllers. It supplies power to the TM5 backplane bus, and provides segmented 24V field power for I/O modules. It isolates different I/O power domains and expands backplane power capacity.
✅ Funciones principales
- Fuente de alimentación for TM5 internal power bus: máx.. output 1136mA (≤55°C); 740mamá (55~60°C)
- I/O field power segment: 24VCC, máximo. 10A, to supply field side of DI/DO/AI/AO I/O modules on the right side of this base
- Segmented power isolation: A full TM5 station can be divided into multiple independent 24V I/O power domains. Short-circuit on one segment will not shut down the entire bus.
- Diagnostic status bits for bus: Bus OK / power warning, I/O data valid, readable via PLC program.
📋 Electrical Specifications
Tensión de entrada nominal: 24VCC, rango de operación 20.4 ~ 28.8VDC
Max current of I/O power segment: 10A. Sin fusible incorporado; external Type T slow-blow fuse (max 10A/250V) is mandatory.
Protección contra polaridad inversa: No disponible. Never reverse +24V and 0V wiring.
Aislamiento: 500Vac RMS isolation between TM5 bus circuit and I/O power segment
Max power dissipation: 1.91W., module self-consumption 25mA@24V
Clase de protección: IP20 (montaje en gabinete solamente)
Dimensiones: W12.5mm × H99mm × D75mm, peso aproximado. 30gramo
Module ID code: 7104 (decimal)
Temperatura ambiente de funcionamiento: -10 ~ +55°C (full current); derating from 55~60°C
🧩 Hardware & Configuración
Compatible bus bases: TM5ACBM01R / TM5ACBM05R; Terminal block TM5ACTB12PS
Montaje: Carril DIN, slotted on TM5 bus base, mixed installation with TM5 I/O modules
Software: Experto en máquinas (SoMachine). Module status word is available for reading bus power warning and network status.
⚠️ TM5SPS2 vs TM5SPS2F (Key Selection Guide)
TM5SPS2: External fuse required, max 10A for I/O segment
TM5SPS2F: Built-in 6.3A fuse, I/O segment limited to 6.3A, no external fuse needed
📌 Aplicaciones típicas
Maquinaria de embalaje, manejo de materiales, machine tool distributed remote I/O islands. Deploy TM5SPS2 for backplane power shortage or segmented protection for sensor/actuator power.
🛠️ Troubleshooting Guide
- Bus warning bit triggered: Check 24V voltage drop, fusible quemado, overload or short circuit in I/O segment
- Module no communication: Verify TM5 bus connector, base address and module ID recognition
- No field power to I/O modules: Check external 24V input at PS2 terminals and external fuse status
Nota: All 0V connections must be tied together and connected to Functional Earth (FE) to meet EMC requirements. Only PELV safety extra-low voltage power is permitted; mains AC voltage cannot be directly connected.
📎 Alternativas & Comparación de series
TM5SPS1: I/O power segmentation only, no TM5 backplane bus power supply
TM5SPS2F: Same function with built-in 6.3A fuse
TM5SBER2: TM5 remote I/O receiver module with integrated bus power supply
Schneider TM5SPS2 Wiring Instructions
TM5SPS2 must be used with TM5ACTB12PS (12-bloque de terminales de resorte de pasador). The terminal block snaps under the TM5ACBMxx bus base, and the electronic module plugs onto the base. Terminal numbers are printed on the terminal block.
- Definición de terminal (12-pin TM5ACTB12PS)
| Número de terminal. | Nombre de la señal | Descripción | Fuse Requirement |
| 1 | PS1 +24V | TM5 backplane bus positive supply (feeds internal TM5 bus) | Series Type T slow-blow 1A fuse (250V) río arriba |
| 2 | PS1 0V | TM5 backplane bus negative | Common ground with PS1 power supply |
| 3 | CAROLINA DEL NORTE | No conectado, no wiring allowed | — |
| 4 | CAROLINA DEL NORTE | No conectado, no wiring allowed | — |
| 5 | PS2 +24V | I/O field power segment positive (supplies all DI/DO/AI/AO I/O modules to the right of this module) | Series Type T slow-blow fuse max.10A (250V) río arriba |
| 6 | PS2 0V | I/O field power segment negative | Common ground with PS2 power supply |
| 7 | CAROLINA DEL NORTE | No conectado | — |
| 8 | CAROLINA DEL NORTE | No conectado | — |
| 9 | CAROLINA DEL NORTE | No conectado | — |
| 10 | CAROLINA DEL NORTE | No conectado | — |
| 11 | CAROLINA DEL NORTE | No conectado | — |
| 12 | CAROLINA DEL NORTE | No conectado | — |
✅ Quick distinction between two power rails:
PS1 (Pin1/2) = TM5 backplane bus power; PS2 (Pin5/6) = I/O field load power. Two separate 24V supplies can be used for isolated power segmentation.
- Two Typical Wiring Schemes
Esquema 1: Single 24V Power Supply (Estándar)
+24V from power supply is split into two branches: one through 1A T-fuse → Terminal 1; another through 10A T-fuse → Terminal 5
Power 0V: Tie Terminal 2 and Terminal 6 together, connect to power supply 0V. Link 0V to Functional Earth (FE) for EMC compliance.
Notas: Bus power and I/O power share the same source. Short circuit on I/O side will not directly damage the bus, but the power supply capacity must cover both backplane and I/O loads.
Esquema 2: Two Independent 24V Supplies (Isolated Segmentation, Recomendado)
PS1 (Pin1/2): Independent 24V supply with 1A slow-blow fuse, dedicated for TM5 backplane bus
PS2 (Pin5/6): Separate 24V supply with 10A slow-blow fuse for sensors and actuators of right-side I/O modules
The 0V of the two power supplies must be interconnected and connected to FE functional earth
Ventaja: Short circuit in I/O circuit will blow only the PS2 fuse, while TM5 backplane bus remains online. Suitable for high-reliability machines.
- Especificación del cable (Terminal de resorte)
Wire gauge range: 0.08 ~ 2.5 mm², recomendado:
Main power cable: 0.75~1,5 mm²
Low-current signal: 0.5 mm²
Wire temperature rating ≥80°C, stripping length approx.8mm
- Definición del indicador LED (On Module Body)
E Fault LED:
Parpadeo: Low bus voltage / insufficient PS1 voltage / bus overload. Common field mistake: only PS2 (Pin5/6) wired while PS1 (Pin1/2) is missing → E LED blinks.
Encendido fijo: PS2 I/O power segment fault, sobrecarga o cortocircuito
RUN LED: Encendido fijo: Module healthy; APAGADO: No module power or bus fault
- Critical Safety & Wiring Prohibitions
- ❌ No built-in fuse! External Type T slow-blow fuse is mandatory for PS2 (max 10A). PS1 requires 1A slow-blow fuse. Module damage may occur without proper fusing in short-circuit events.
- ❌ No reverse polarity protection. Never swap +24V and 0V; reversed polarity will permanently damage TM5SPS2.
- ❌ Only PELV/SELV safety isolated 24VDC power supplies are allowed. Mains AC cannot be connected directly.
- ❌ Do not wire NC unused terminals (3,4,7~12) to prevent accidental short circuits.
- ✅ EMC mandatory requirement: All 0V tied together and connected to FE functional earth; FE shall not be confused with protective earth PE.
- ✅ Current derating: ≤55°C ambient for full backplane 1136mA; reduced to 740mA for 55~60°C.
- Pre-power-on Wiring Check List
- Confirm PS1 (Pin1,2) 24V is connected; do not only wire PS2 (Pin5,6)
- Verify Type T slow-blow fuses with correct ratings
- All 0V commoned and bonded to FE
- Terminals fully clamped, no loose connection or exposed copper strands causing short
- Measure before power-up with multimeter: 24VDC between pin1-2; 24VDC between pin5-6, correct polarity
- Configuration Notes (Experto en máquinas / SoMachine)
When the module is inserted into the base, software recognizes Module ID:7104. Status words available:
DcOk: Boolean flag for valid bus power
Bus power warning bit: Low voltage pre-alarm, usable for PLC alarm programming
Schneider Modicon TM5 Full Series Model List & Bill of Materials
Controladores compatibles: M258 / LMC058 / LMC078; Software de programación: Experto en máquinas (anteriormente SoMachine)
System architecture: Base de autobuses + electronic module + removable spring terminal block. SPS power distribution modules are core components for power segmentation.
- Power Distribution Modules (PDM, same series as TM5SPS2)
| Modelo | Descripción | Características clave | Bases compatibles | Compatible Terminal Block |
| TM5SPS1 | I/O Power Segmentation Module | Supplies 24V field power only to right-side I/O modules. No TM5 backplane bus power supply. Sin fusible incorporado, max 10A | TM5ACBM01R / 05R | TM5ACTB12PS |
| TM5SPS1F | I/O Power Segmentation with Built-in Fuse | I/O segment power only, built-in 6.3A fuse, no backplane power supply | TM5ACBM01R / 05R | TM5ACTB12PS |
| TM5SPS2 | Autobús de plano posterior + I/O Dual Power Supply | Powers TM5 backplane bus and right-side I/O field power. Sin fusible incorporado, I/O segment max 10A | TM5ACBM01R / 05R | TM5ACTB12PS |
| TM5SPS2F | Dual Power Module with Fuse | Bus de plano posterior + I/O segment power, replaceable built-in 6.3A fuse | TM5ACBM01R / 05R | TM5ACTB12PS |
| TM5SPS3 | IPDM Interface Power Module | Dedicated power module for Sercos III bus interface | TM5ACBN1 | TM5ACTB12PS |
- Bus Transceiver Modules (Remote Station Core)
| Modelo | Descripción | Solicitud | Compatible Terminal Block |
| TM5SBET1 | TM5 Bus Transmitter | Controller-side bus transmitter, local start point | TM5ACTB12PS |
| TM5SBET7 | High-speed Bus Transmitter | Long-distance high-speed transmission | TM5ACTB12PS |
| TM5SBER2 | TM5 Bus Receiver | Remote I/O island receiver with integrated backplane + I/O power supply | TM5ACTB12PS |
- Bus Bases (Mechanical Base, modules plug onto bases)
Two base types: White straight-through bases, Grey isolated bases (for SPS power/transceiver modules)
|TM5ACBM11|White Bus Base|24V I/O power pass-through, no address rotary switch|Standard DI/DO/AI/AO modules|
|TM5ACBM15|White Bus Base|Power pass-through, with rotary address switch|Standard DI/DO/AI/AO modules|
|TM5ACBM01R|Grey Isolated Base|Isolates I/O power on left side, no address switch|SPS power modules, SBER2 receiver|
|TM5ACBM05R|Grey Isolated Base|Left I/O power isolation, with address rotary switch|SPS power modules, SBER2 receiver|
|TM5ACBN1|Sercos Dedicated Base|Sercos III bus special base, used with TM5SPS3|TM5NS31, TM5SPS3|
- Removable Spring Terminal Blocks (Must be ordered separately)
| Modelo | Patas | Color | Applicable Module Types |
| TM5ACTB06 | 6-alfiler | Blanco | Small channel DI/DO/AI modules |
| TM5ACTB12 | 12-alfiler | Blanco | General-purpose I/O modules |
| TM5ACTB12PS | 12-alfiler | Gris | SPS power modules, SBER2 receiver |
| TM5ACTB16 | 16-alfiler | Blanco | High-density I/O |
| TM5ACTB32 | 32-alfiler | Blanco | High-density I/O |
- Digital Input Modules DI
| Modelo | Canales | Presupuesto |
| TM5SDI2D | 2DE | 24VDC sink, 3-cable |
| TM5SDI4D | 4DE | 24VDC sink, 3-cable |
| TM5SDI6D | 6DE | 24VDC sink, 2-cable |
| TM5SDI12D | 12DE | 24VDC sink, 1-cable |
| TM5SDI16D | 16DE | 24VDC sink, high density |
| TM5SDI2DF | 2DE | 24VDC high-current input type |
| TM5SDI2A | 2DE | AC100~240V AC input |
| TM5SDI6U | 6DE | Universal input |
- Digital Output Modules DO
| Modelo | Canales | Presupuesto |
| TM5SDO2T | 2HACER | 24V transistor output |
| TM5SDO4T | 4HACER | 24V transistor |
| TM5SDO4TA | 4HACER | Enhanced transistor |
| TM5SDO6T | 6HACER | 24V transistor |
| TM5SDO8TA | 8HACER | Enhanced transistor |
| TM5SDO12T | 12HACER | Transistor |
| TM5SDO16T | 16HACER | High-density transistor |
| TM5SDO2R / 4R | 2/4HACER | Relay dry contact output |
| TM5SDO2S | 2HACER | Thyristor AC output |
- Mixed I/O Modules DI+DO
| Modelo | Canales | Descripción |
| TM5SDM8DTS | 8DI+4DO | 24En DC |
| TM5SDM12DT | 8DI+4DO | 12-point mixed I/O |
| TM5SMM6D2L | 6DI+2DO | Economical mixed module |
- Analog Modules AI / HACIA
| Modelo | Canales | Tipo de señal |
| TM5SAI2L | 2AI | 4~20 mA de corriente |
| TM5SAI4L | 4AI | 4~20mA |
| TM5SAI8L | 8AI | 4~20mA |
| TM5SAI2V | 2AI | ±10V voltage |
| TM5SAO2L | 2HACIA | 4~20mA output |
| TM5SAO4L | 4HACIA | 4~20mA |
| TM5SAO2V | 2HACIA | ±10V voltage output |
- Contador de alta velocidad / Encoder Modules (SE Series)
| Modelo | Canales | Tipo |
| TM5SE1IC02505 | 1 Canal | 5V differential encoder |
| TM5SE1IC01024 | 1 Canal | 24V single-ended encoder |
| TM5SE2IC01024 | 2 Canal | 24V single-ended encoder |
| TM5SE1SC10005 | 1 Canal | 5V single-ended encoder |
- Communication Interface Modules
| Modelo | Interfaz | Protocolo |
| TM5PCRS2 | RS232 | Modbus RTU |
| TM5PCRS4 | RS485 | Modbus RTU |
| TM5PCDPS | esclavo dp | Profibus-DP |
| TM5NCO1 | CANopen Slave | CANabierto |
| TM5NEIP1 | Ethernet/IP | EtherNet/IP Remote I/O |
| TM5NS31 | Sercos III | Sercos III motion bus |
- Accesorios
- TM5SD000: Dummy filler module for reserved slots
- TM5SPDG12F / TM5SPDD12F: 12-channel power distribution terminal module
- TM5SPDG5D4F: Multi-channel combined power distribution module
✅ TM5SPS2 Minimum Complete BOM for Purchase
- TM5SPS2 Power Distribution Electronic Module
- TM5ACBM01R Grey Isolated Base (no address) / TM5ACBM05R (with address rotary switch), select one
- TM5ACTB12PS Grey 12-pin spring terminal block (obligatorio, separate order item)
Assembly rule: Insert SPS module into grey isolated base TM5ACBM01R/05R; snap TM5ACTB12PS terminal block underneath the base.
✅ Quick Selection Rules
- Standard DI/DO/AI/AO → White base TM5ACBM11/15 + white terminal block ACTB06/12
- SPS power segmentation, SBER2 receiver module → Grey isolated base + Grey ACTB12PS terminal block
- Insufficient backplane power, need segment protection → TM5SPS2; prefer built-in fuse for simpler wiring → TM5SPS2F
- Sensor power segmentation only, no requirement to boost backplane power → TM5SPS1 / TM5SPS1F
contactor,cortacircuitos,sensor,Codificador,SOCIEDAD ANÓNIMA,Convertidor