Schneider A9DA2616

Schneider A9DA2616 (Acti9 Idd40t 1p+N C16 30mA y) Residual Current Operated Circuit Breaker with Overcurrent Protection (RCBO)

  1. Interpretación del modelo

A9DA2616 = Acti9 Series iDD40T Product Type 1P+N Pole Configuration C-type Tripping Curve 16A Rated Current 30mA Residual Current AC-type Residual Current Detection

  1. Parámetros técnicos básicos (Compliant with IEC 61009-1/GB 16917.1)
ParámetroEspecificación
Tipo de productoDisyuntor accionado por corriente residual con protección contra sobrecorriente (RCBO, integrating three protections: sobrecarga, cortocircuito, y corriente residual)
Configuración de polos1P+N (1 Pole + Neutral, phase line breaks, neutral line remains conducting permanently)
Corriente nominal (En)16A
Curva de disparoC-type (instantaneous tripping at 5~10 In), suitable for lighting, socket, and general motor loads
Rated Residual Operating Current (IΔn)30mamá (personal safety protection level)
Residual Current TypeAC-type (detects sinusoidal AC leakage current, suitable for conventional environments)
Tensión nominal (Ue)230V y (1P+N), 50/60Hz
Capacidad de ruptura de cortocircuito (Icn)6el (400V) / 4500A (230V)
Rated Residual Operating Time (at IΔn)≤0.3s
Vida útil mecánica10,000 operaciones
Electrical Service Life5,000 operaciones
Método de montaje35carril DIN mm (18mm width)
Especificación de cableadoSolid wire: 1~25 mm²; Flexible wire: 1~16 mm² (with cable lugs)
Terminal Torque2.0 Nuevo Méjico
Temperatura de funcionamiento-25℃ ~ +70℃
Clase de protecciónIP20 (for use inside distribution boxes)
Rated Impulse Withstand Voltage (Uimp)4kV
  1. Functions & Applications

Funciones principales

Protección contra sobrecarga: Realizes inverse-time protection via the thermal bending of bimetallic strips.

Protección contra cortocircuitos: Achieves instantaneous protection through electromagnetic release.

Protección de corriente residual: Rapidly trips within ≤0.3s when detected residual current exceeds 30mA, preventing electric shock accidents.

Escenarios de aplicación típicos

  1. Branch circuit protection for residential/commercial buildings (p.ej., lighting and socket circuits)
  2. Electrical safety protection for crowded places such as offices and shops
  3. Power supply protection for small household appliances and office equipment
  4. Replacement for traditional MCB + RCCB combinations, ahorro de espacio en la caja de distribución

Selection Tips

AC-type is suitable for pure AC load environments, such as traditional lighting and resistive loads.

For loads containing DC components (p.ej., switching power supplies, LED lighting), A-type or B-type residual current circuit breakers are recommended.

30mA is the standard value for personal safety protection and shall not be used for equipment protection (300mA is usually selected for equipment protection).

  1. Instalación & Puntos clave de mantenimiento
  2. Especificaciones de cableado: Top-in bottom-out (bidirectional wiring with bottom-in top-out supported). Connect phase line to L pole and neutral line to N pole; reverse connection is strictly prohibited.
  3. Residual Current Test: Después de la instalación, press the test button (T button) to confirm the normal operation of the residual current protection function.
  4. Inspección periódica: Press the test button once a quarter to verify the effectiveness of the residual current protection function.
  5. Fault Handling:

Overload/Short-circuit Tripping: Troubleshoot load or line faults before closing the breaker directly.

Residual Current Tripping: First disconnect all loads, check for leakage points one by one, and close the breaker only after repairs; forced closing with faults is strictly prohibited.

  1. Spacing Requirement: Maintain a gap of ≥3mm from adjacent components to ensure heat dissipation and wiring space.
  2. Corresponding Chint Product & Replacement Comparison

Chint Equivalent Model: NXBLE-63 1P+N C16 30mA AC

Categoría de parámetroSchneider A9DA2616Chint NXBLE-63 1P+N C16 30mAReplacement Compatibility
Core ProtectionSobrecarga + Short-circuit + Residual Current (RCBO)Sobrecarga + Short-circuit + Residual Current (RCBO)✅ Fully Matched
Pole Configuration/Tripping Curve/In1P+N/C-type/16A1P+N/C-type/16A✅ Fully Matched
IΔn/IΔ Type30mA/AC30mA/AC✅ Fully Matched
Capacidad de ruptura6el6el✅ Fully Matched
Installation Dimensions18milímetros (ancho) × 91mm (height) × 65mm (depth)18milímetros (ancho) × 91mm (height) × 65mm (depth)✅ Identical Dimensions
Especificación de cableadoSolid wire: 1~25 mm²Solid wire: 10~16 mm²⚠️ Schneider Terminals Have Larger Capacity
Temperatura de funcionamiento-25℃ ~ +70℃-30℃ ~ +70℃✅ Chint Has Better Low-temperature Adaptability
Additional FunctionsVisiTrip Fault IndicationRed-Green Window Indication (Red for Closed, Green for Open)⚠️ Different Indication Methods
Período de garantía24 Months18 Months⚠️ Warranty Difference

Key Replacement Precautions

  1. ✅ Installation Compatibility: Both are mounted on 35mm DIN rails with 18mm width, enabling direct interchange.
  2. ✅ Protection Characteristics: C-type curve, 16A rated current, and 30mA residual current protection are fully consistent; no load adjustment is required.
  3. ⚠️ Wiring Adaptation: Schneider terminals support larger wire diameters; keep the original wire diameter during replacement to avoid loose connections.
  4. ⚠️ Function Identification: The VisiTrip indication window of Schneider shows red after tripping; it is necessary to train operators to recognize the new marks.
  5. Resumen & Recomendaciones de selección

Schneider A9DA2616 is a 1P+N 16A RCBO in the Acti9 series iDD40T product line. It integrates triple protection functions and is suitable for personal safety protection in conventional environments.

Recomendaciones de selección:

For international brand reputation and reliable performance: Choose Schneider A9DA2616, which provides more comprehensive fault indication and bidirectional wiring functions.

For cost-effectiveness: Choose Chint NXBLE-63 1P+N C16 30mA, which features more favorable pricing and performance meeting national standards.

For special environments (p.ej., low temperature < -25℃): Prioritize Chint products for their better low-temperature adaptability.