Numéro de commande: 208281, Alias: XTCEXSBR11
Positionnement: Monté sur le côté auxiliaire contact module for high-power DILM/DILH series contactors (Série Moeller)
✅ Explication du code modèle
DILM820-X: Accessory for high-frame DILM power contactors
HI11: 1NON + 1Caroline du Nord (1 make, 1 break)
ET: Side Install (side mounting; differentiated from SA & V variants)
✅ Key Contact Characteristics (Critique)
Interlocked Mirror Contact, conforme à la CEI 60947-5-1 Annex L and IEC 60947-4-1 Annex F
The NC contact is a mirror contact, designed for safety circuits, interlocking, emergency stop feedback and PLC safety signal acquisition. It is NOT a late-break NC contact
Configuration des contacts: 1 Normalement ouvert + 1 Normalement fermé
Terminaison: M3.5 screw terminals, couple de serrage: 1.2 Nm
Courant thermique conventionnel Ith: 10 UN (à 60 °C)
AC-15 control capacity:
230 V: 6 UN
400 V: 4 UN
500 V: 1.5 UN
Tension assignée d'isolement Ui: 690 V; Ump: 6 kV; Catégorie de surtension III, Degré de pollution 3
Isolation électrique: Coil-to-auxiliary contacts and auxiliary-to-main contacts meet AC 440V isolation level
✅ Compatible Base Contactors (Only for this high-power frame)
DILM250 ~ DILM1000, DILH600 ~ DILH2600, DILDC300 ~ DILDC600 DC contactors
Max.. 1 module on each side (gauche & droite), maximum 2 modules per contactor
✅ Dimensions & Poids
W15 mm × H77 mm × D77 mm, Poids net: 37 g
✅ Cross-Series Comparison (Guide de sélection)
DILM820-XHI11-SI: Side mount, bornes à vis, interlocked mirror contact (modèle standard, this part)
DILM820-XHI11V-SI: Side mount, vibration-resistant reinforced version
DILM820-XHI11-SA: Standard interlocked contact (non-mirror), not for safety EDM monitoring
✅ Certifications
CE, UL, ASC, CCC; compliant with railway standard EN 45545 and vibration standard IEC 61373. Suitable for cranes, compresseurs d'air, les fans, high-power motor circuits, safety gate interlocks and inverter bypass feedback.
✅ Applications typiques
Safety interlock circuits, contactor status feedback to PLC, forward/reverse electrical interlocking, fault feedback, safety relay input signals.
This side-mounted IEC 60947-5-1 Annex L mirror contact module (1NO+1 mirror NC) is exclusively for DILM250~DILM1000 and DILH high-power contactors. It is mainly used in safety-related control circuits, high-power motor control and fault diagnosis feedback, and cannot be replaced by standard auxiliary contacts for safety validation.
- Safety Circuits (Le plus courant, Mandatory for Safety Audits)
- EDM External Device Monitoring for Safety Relays
The mirror NC contact is wired into the EDM channel of the safety relay to monitor welding/sticking of the contactor main contacts. If the NC fails to reset after coil de-energization, the safety relay triggers a lockout. It meets ISO 13849 PLd/PLe and SIL2/3, which is the standard solution for Eaton ESR, Pilz and Schneider XPS safety circuits.
- Barrière de sécurité / Light Curtain Interlocking
The mirror NC verifies the true open state of the contactor after the safety gate is opened, preventing unexpected motor operation caused by welded main contacts.
- Emergency Stop State Verification
After E-stop cuts off the contactor coil, the mirror contact confirms the contactor is physically open, eliminating hidden risks from welded main contacts despite valid E-stop signals.
- High-Power Motor Control Circuits
- Hardware Electrical Interlock for Forward/Reverse Contactors (Preferred for Large Fans, Pumps and Hoists)
The mirror NC of each contactor is wired in series into the coil circuit of the opposing contactor, forming hardwired interlock to prevent simultaneous closure and phase-to-phase short circuit. For DILM high-power contactors, safety auditors will not approve ordinary auxiliary contacts for this interlock.
III. Performance Comparison Table
| Type de contact | Actuation Mechanism | Performance under Welded Main Contacts | Champ d'application |
| Standard NC Auxiliary Contact | Mechanically coupled only to the armature, no welding test certification | Follows armature position without standard validation | Indicator lights, ordinary PLC feedback; FORBIDDEN for EDM monitoring |
| DILM820-XHI11-SI Mirror NC | Rigid mechanical linkage + internal positive interlock, factory-tested for contact welding | NC remains open when main contacts are welded, maintaining safe contact gap | Safety relay EDM, safety interlocking, contact sticking diagnosis |
- Limites (Derived from Mechanical Design)
- Only fits DILM250~DILM1000 / DILH high-power contactors; smaller frames do not match the mechanical stroke.
- Designed exclusively for control signals: Ith=10 A, AC-15 230V=6A; cannot carry main power loads.
- The mirror NC only detects welded closed main contacts. It cannot detect poor contact or increased contact resistance.
Full Model List for DILM820-XHI Series
Seulement 3 mass-produced variants: all side-mounted 1NO+1NC positive-interlock contacts; differences are mirror (ET) / standard (sur) and vibration-resistant (V) versions.
- Règles de codage du modèle
DILM820-XHI: Side auxiliary contact module for DILM/DILH high-power contactors (DILM250 ~ DILH2600)
11: 1NON + 1Caroline du Nord (1 make + 1 break)
S: Side mounted
ET: Mirror Contact (CEI 60947-4-1 Annex F, approved for EDM welding monitoring)
sur: Standard positive interlock contact (CEI 60947-5-1 Annex L only; NOT allowed for safety relay EDM)
V: Vibration-resistant reinforced construction (chemin de fer, heavy vibrating equipment)
- Complete Product List
| Modèle | Numéro de commande. | Configuration des contacts | Taper | Application principale |
| DILM820-XHI11-SI | 208281 | 1NON + 1 mirror NC | Mirror contact (ET) | Circuits de sécurité, EDM welding detection, forward/reverse hard interlock, PLC sticking alarm (your selected model)Eaton |
| DILM820-XHI11-SA | 208282 | 1NON + 1 standard NC | Standard positive interlock (sur) | Ordinary PLC feedback, pilot lights, basic electrical interlock; strictly prohibited for EDM safety monitoringfiles.kemp… |
| DILM820-XHI11V-SI | 208283 | 1NON + 1 mirror NC | Vibration-resistant mirror contact (V+SI) | Rail vehicles, overhead cranes, mining machinery with heavy vibration; identical electrical performance to standard SI, with reinforced mechanical structurefiles.kemp… |
- Key Selection Distinction
(1) SI vs SA (Le plus critique)
ET: NC is a certified mirror contact. It stays open when main contacts are welded, satisfying ISO 13849 PLd / SIL2-3 and approved for safety relay EDM loops.
sur: Only mechanical positive interlock without welding test certification. Only for ordinary control; rejected by safety audits.
(2) V-SI Variant
Mechanically reinforced for higher shock & résistance aux vibrations (CEI 61373). Electrical specs are identical to standard SI. Used for hoisting, mining and railway rolling stock.
- Universal Installation Restrictions
Montage: Only side-fit on DILM250~DILM1000 and all DILH series contactors.
Quantité: Max.. 1 module per side, total maximum 2 modules per contactor.
Notation: Ith=10 A, AC-15 230V=6A; strictly for control circuits only, no power loads.
- No Other Variants
No XHI22 (2NON+2NC) version available.
No top-mount version; only side-mount (S) modèles.
No spring-cage terminals; all models use M3.5 screw terminals.
- Équivalent multimarque
Eaton DILM820-XHI11-SI ↔ Siemens 3RT1956-4G (mirror contact); Schneider LADN13C is only standard auxiliary contact and cannot replace the mirror type for safety EDM.