Schneider ACE850FO Communication Interface Module - Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-mail: kent@bestcontactor.com

À propos Contact |

 Schneider ACE850FO Communication Interface Module - Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur

API/

Schneider ACE850FO Communication Interface Module

(Numéro de pièce.: 59659) The ACE850FO is a fiber-optic multi-protocol communication interface module dedicated to Sepam series protective relays. It is compatible with Sepam 40/60/80 series protection IEDs, equipped with dual 100BASE-FX fiber Ethernet ports for substation bay-level networking. It supports RSTP ring topology and is suitable for switchgear cabinets with severe electromagnetic interference. Comparison within ...

  • Détails du produit

(Numéro de pièce.: 59659)

The ACE850FO is a fiber-optic multi-protocol module d'interface de communication dedicated to Sepam series protective relays. It is compatible with Sepam 40/60/80 series protection IEDs, equipped with dual 100BASE-FX fiber Ethernet ports for substation bay-level networking. It supports RSTP ring topology and is suitable for switchgear cabinets with severe electromagnetic interference.

Comparison within the same series: ACE850TP is the RJ45 copper version; ACE850FO is the fiber SC version.

Statut: Marked End-of-Life (EOL). Last order date: 2026-12-31; soutien & maintenance until 2030-12-31.

Définition du modèle

ACE850: Sepam communication interface family

FO = Fiber Optic, fiber optic variant

Matériel / Numéro de pièce: 59659

Spécifications techniques de base

  1. Fiber Port Specifications

Vitesse: 100BASE-FX

Type de fibre: Multi-mode fiber

Wavelength: 1300 nm

Connecteur: CS

Dual fiber ports: S-LAN (Supervision Network) and E-LAN (Engineering Network); ring topology supported

  1. Supported Protocol Stack

CEI 61850 MMS / GOOSE

Modbus-TCP

RSTP (IEEE802.1d 2004 Rapid Spanning Tree, redondance en anneau)

SNMP, FTP, HTTP, SNTP, ARP

  1. Compatible Host IEDs: Sepam 40 / Sepam 60 / Sepam 80 (including Sepam80 NPP)
  2. Alimentation: Powered from the Sepam unit itself; no separate power required
  3. Default Login Credentials

Utilisateur: Admin

Password: ACE850

Définition du port

S-LAN: Supervision network, connects to SCADA backend, carries IEC61850 and Modbus TCP traffic

E-LAN: Engineering maintenance port, used for SFT2841 software local/remote commissioning and parameter download

Both ports share identical hardware; functions are differentiated by software. Star and fiber ring network topologies are supported.

Scénarios d'application typiques

Fiber networking of Sepam protection relays in medium-voltage switchgear for EMI immunity

IEC61850 digital protection at substation bay level

Dual-network redundancy and fast self-healing fiber ring for IEDs

Migration & Directives de remplacement

ACE850FO is discontinued. New projects are not recommended for procurement; spare parts are limited to existing stock. New design options:

  1. Upgrade to new-generation Sepam protection relays with built-in IEC61850 fiber ports, eliminating external ACE850 modules
  2. Retrofit for existing Sepam40/80: evaluate full IED replacement or third-party optical-electrical converters (GOOSE latency must be validated)

Liste de contrôle de dépannage

  1. Optical link: Inspect SC connector endface cleanliness, verify multi-mode fiber matching and optical power. 100BASE-FX does not work with single-mode fiber.
  2. Ring network: RSTP configuration. Avoid multiple root bridges within one ring; guard against GOOSE storm.
  3. Communication: Distinguish S-LAN and E-LAN. E-LAN is for SFT2841 commissioning only; do not permanently connect to SCADA supervision network.
  4. Login: Password reset requires factory reset, which erases all network configuration.

Logiciel de support

SFT2841: Configuration and commissioning software for Sepam protection relays. Connect to the E-LAN port of ACE850 for parameter download and oscillography retrieval.

Full Model List for Schneider Sepam 40 / 60 / 80 Series Protection IEDs (Compatible with ACE850FO)

Prefix definition:

S: Feeder / incoming line protection

T: Transformer protection

M.: Protection moteur

G: Protection du générateur

B: Busbar protection

C: Capacitor protection

All models use the same hardware platform; protection functions are determined by embedded application firmware. Communication extension via ACE850TP (cuivre) / ACE850FO (fiber SC). Whole series EOL discontinued.

Sepam 40 Série (Économique, basic distribution protection, 13 modèles)

S40: Feeder protection (basic overcurrent & défaut à la terre)

S41: Directional feeder protection

S42: Dual-source / busbar ATS, parallel incoming line protection

S50: Protection contre la tension (PT cabinet, busbar voltage monitoring)

S51: Tension + protection contre les surintensités

S52: Entrant + jeu de barres, automatic transfer

S53: Directional residual earth fault protection

S54: Sensitive earth fault protection

T40: Distribution transformer protection (moyen & petits transformateurs)

T42: Transformateur + automatic transfer

T50: Transformer voltage monitoring protection

T52: Transformateur + incoming interlock

M41: Medium-voltage motor protection

G40: Small generator protection

Positionnement: Basic medium-voltage switchgear, limited I/O, low sampling rate for fault recording, suitable for simple distribution networks.

Sepam 60 Série (Amélioré, complex distribution applications, 8 modèles)

S60: Feeder protection

S62: Parallel incoming line / busbar ATS

M61: Medium-voltage motor protection (heavy-duty motors)

T60: Transformer protection

T62: Transformateur + incoming interlock

G60: Protection du générateur

G62: Generator paralleling protection

C60: Capacitor bank protection

Positionnement: More I/O and stronger logic than Sepam40; supports advanced custom logic. Three HMI panel options available.

Sepam 80 Série (Haut de gamme, programmable, 16 modèles, most commonly paired with ACE850FO)

S80: Basic feeder protection

S81: Directional overcurrent feeder protection

S82: Parallel incoming line / busbar ATS

S84: Incoming protection with directional residual and islanding detection

T81: Transformer protection

T82: Transformateur + automatic transfer

T87: Main transformer protection with Buchholz and temperature monitoring

M81: Medium-voltage motor protection

M87: High-power motor with temperature and bearing monitoring

M88: Motor-transformer unit protection

G82: Protection du générateur

G87: Full generator protection (loss of excitation, puissance inverse, etc.)

G88: Generator paralleling protection

B80: Basic busbar protection

B83: Busbar differential protection

C86: Capacitor bank protection (multi-section capacitor, protection contre le déséquilibre)

Positionnement: Top-tier Sepam family. Supports Logipam custom programmable logic, 36 samples per cycle fault recording, abundant I/O resources. Widely used in digital substations for GOOSE over ACE850FO.

Cross-Series Comparison for Selection

ArticleSepam40Sepam60Sepam80
Programmable LogicLimitedMoyenFull Logipam programming
Enregistrement des défauts12 échantillons/cycle12 échantillons/cycle12/36 samples optional
Capacité d'E/SFaibleMoyenHaut
ACE850FO Compatible✅✅✅
Utilisation typiqueMangeoire simple, small transformerComplex distribution, moteurMain transformer, jeu de barres, générateur, digital bays

Informations supplémentaires

  1. Unified commissioning software: SFT2841. Connect PC to ACE850FO E-LAN for parameter download and fault record retrieval.
  2. Matériel: Native RS485 on IED; IEC61850 / GOOSE over fiber requires external ACE850FO (59659).
  3. EOL Status: Sepam 40/60/80 IEDs and ACE850FO are discontinued. New projects recommended to adopt Easergy P3 / P5 series.

Application Scenarios of Sepam 40 / 60 / 80 Protection IEDs (Par série, Industrie & Bay Type, ACE850FO Fiber Digital Retrofit)

Plage de tension: 3kV~35kV medium-voltage distribution network, industrial and municipal user substations, excluding 110kV/220kV transmission grid. All series EOL, widely deployed in legacy retrofit projects; new projects use Easergy P3/P5 as replacement.

Sepam 40 Series|Economical, basic distribution protection

Positionnement: Protection de base, limited I/O, logique simple. For bays with simple protection requirements and budget constraints.

Typical Bay Applications

  1. General feeder outgoing (S40/S41): Plant / park simple outgoing protection, overcurrent and residual earth fault
  2. PT voltage cabinet (S50): Busbar voltage monitoring, surtension/sous-tension, frequency supervision
  3. Small distribution transformer (T40): 10kV/0.4kV distribution transformer protection, simple instantaneous overcurrent, overload and earth fault
  4. Busbar tie / dual-source basic ATS (S42/T42): Simple automatic transfer for single busbar sectionalized scheme with basic logic
  5. Moyen & small MV motors (M41): Ordinary fans and pump motor protection
  6. Small diesel generator (G40): Standalone emergency generator protection

Target Industries

Commercial complexes, hôpitaux, small manufacturing plants, distribution kiosks, simple wastewater treatment plants

Normally deployed with RS485 Modbus; ACE850FO is added for IEC61850/GOOSE fiber networking.

Sepam 60 Series|Enhanced, complex distribution, medium logic requirements

Positionnement: More I/O points, stronger interlock logic, multi-condition interlock supported, better recording performance than Sepam40.

Typical Bay Applications

  1. Feeder & incoming protection (S60/S62): Directional protection, busbar ATS, dual-source interlock, main incoming cabinets in industrial plants
  2. Medium-voltage motors (M61): Heavy-duty pumps, concasseurs, compressors with RTD temperature monitoring
  3. Transformateurs de distribution (T60/T62): Distribution transformers with temperature interlock and trip blocking
  4. Banques de condensateurs (C60): Reactive power compensation capacitor protection, unbalance and overvoltage protection
  5. Paralleling small generators (G60/G62): Protection for multiple small generators in parallel operation

Target Industries

Pharmaceutical plants, paper mills, medium-sized waterworks, 10kV substations for data centers, rail auxiliary substations

ACE850FO is commonly used in digital retrofit to build fiber ring networks for fast GOOSE interlock.

Sepam 80 Series|High-end programmable, Logipam, complex primary equipment protection (Most common ACE850FO pairing)

Positionnement: Top product line. Supports custom Logipam programming, high sampling fault recording, bus differential, full generator protection. Preferred for digital substation retrofit.

Typical Bay Applications

  1. Entrant / critical feeder (S80/S81/S82/S84): Directional residual, islanding detection, breaker failure, complex ATS logic
  2. Transformateurs de puissance (T81/T82/T87): Main distribution transformers, interfacing Buchholz, oil temperature, pressure relief non-electrical signals
  3. High-power MV motors (M81/M87/M88): Acier & mining heavy-duty motors, bearing temperature monitoring, stall and rotor protection
  4. Generators (G82/G87/G88): Diesel & biogas generators, loss of excitation, puissance inverse, overexcitation, sous-fréquence, multi-unit paralleling
  5. Busbar protection (B80/B83): Busbar differential protection for fast fault clearing on sectionalized single busbar
  6. Large capacitor banks (C86): Multi-section capacitor banks with segmented unbalance protection

Target Industries

Pétrochimique, coal chemical, métallurgie & acier, exploitation minière, large data centers, power plant auxiliary power, aéroports, ports, large pumping stations. Widely used in legacy digital retrofit projects (fiber ring + IEC61850 GOOSE interlock) with ACE850FO.

Cross-Series Industry Summary

Industrie: Pétrochimique, métallurgie & acier, exploitation minière, papier, pharmaceutique, ciment, heavy manufacturing auxiliary power

Infrastructure: Aéroports, ports, transport ferroviaire, tunnels, municipal water & wastewater plants

Building power distribution: Large commercial complexes, tertiary hospitals, 10kV user substations for data centers

Énergie: On-site power plants, diesel generator stations, distributed energy grid-connection bays

Guide de sélection rapide

  1. Surintensité de base & earth fault only, no complex interlock → Sepam40
  2. ATS, surveillance de la température du moteur, capacitor protection, medium complexity interlock → Sepam60
  3. Bus differential, transformer non-electrical protection, high-power motor, generator paralleling, custom logic, IEC61850/GOOSE fiber ring → Sepam80 + ACE850FO

Notes d'ingénierie

  1. Core value of ACE850FO: GOOSE cross-cabinet interlock for Sepam80 ring deployment, replacing hardwired secondary wiring with superior EMI performance in switchgear environments
  2. Limitation: IEDs are EOL discontinued. Non autorisé pour les nouveaux projets; only for legacy substation retrofit and spare replacement
  3. Communication: Native Modbus RTU on IED; IEC61850, GOOSE and RSTP fiber ring require external ACE850FO / ACE850TP

Sepam 60 Series Full Model List (Schneider EOL Protection IEDs, compatible with ACE850FO fiber module)

Prefix definition:

S = Feeder / incoming protection

T = Transformer protection

M = Motor protection

G = Generator protection

C = Capacitor protection

Sepam60 shares unified hardware platform; protection functions are implemented by embedded firmware. Native RS485 Modbus RTU; IEC61850, GOOSE and fiber ring require ACE850FO (59659) or ACE850TP copper module.

Model Details & Fonctions principales

  1. S60|Feeder / Incoming Protection

General incoming and feeder cabinets, phase overcurrent, residual earth fault, tension & frequency monitoring, basic logic interlock; suitable for plant outgoing and single busbar incoming bays.

  1. S62|Directional Incoming / Jeu de barres, Automatic Transfer

Directional overcurrent and directional residual earth fault protection. Supports busbar ATS, dual-source interlock and loop incoming discrimination. Widely used for single busbar sectionalized incoming and bus tie cabinets; the most popular model in Sepam60.

  1. T60|Distribution Transformer Protection

10kV distribution transformer protection, instantaneous overcurrent, surcharge, residual current and oil temperature monitoring for conventional plant distribution transformers.

  1. T62|Transformer + Incoming Interlock / ATS

Transformer protection plus source automatic transfer logic. Able to interface transformer non-electrical signals (température, pression). Designed for critical distribution transformers.

  1. M61|Medium-Voltage Motor Protection

Medium-voltage heavy-duty motors (pompes, les fans, concasseurs). Décrochage, surcharge, unbalance and earth fault protection. Prend en charge jusqu'à 16 RTD inputs for stator / bearing temperature measurement. The only motor model in Sepam60.

  1. G60|Standalone Generator Protection

Protection for standalone diesel generators. Surintensité, surtension/sous-tension, underfrequency and overload for independent emergency generator sets.

  1. G62|Generator Paralleling Protection

Generator grid paralleling protection with reverse power, out-of-step and synchronisation-related logic for multi-generator parallel operation.

  1. C60|Capacitor Bank Protection

Medium-voltage reactive compensation capacitor cabinet protection, surintensité, surtension, residual and unbalance protection for single-section capacitor banks.

Common Hardware Specifications of Sepam60

Entrées analogiques: 4 current inputs, 3 voltage inputs

E/S numériques: 28 DEPUIS, 16 FAIRE

Temperature measurement: Max.. 16 RTD channels

Logique: Built-in logic equation editor (Note: Sepam60 does not support full Logipam ladder programming available on Sepam80)

Enregistrement des défauts: 12 échantillons par cycle

IHM: 3 optional panels (basique / standard / grand écran)

Commissioning software: SFT2841

Engineering Selection Tips

  1. EOL status: Sepam60 IED discontinued. New projects recommended Easergy P3. ACE850FO can be fitted for GOOSE fiber networking in legacy retrofit.
  2. Compare with Sepam40: Capacité d'E/S plus élevée, more RTD channels and stronger custom logic.
  3. Compare with Sepam80: No advanced Logipam programming, no bus differential and no high sampling oscillography.

Précédent:

Suivant:

Laisser une réponse

Laisser un message