Model Positioning & Differenze fondamentali

BMXDRA1605H: 16-channel relay output module of the Modicon X80 series, Harsh Environment / Hardened type. The suffix “H” stands for Hardened, designed specifically for extreme industrial environments.

BMXDRA1605: 16-channel relay output module of the Modicon X80 series, Standard type, suitable for normal industrial environments.

  1. Detailed Technical Parameter Comparison
ArticoloBMXDRA1605H (Harsh Environment)BMXDRA1605 (Standard)Note
Operating Temperature-25°C ~ +70°C0°C ~ +60°CH version has wider temperature range for extreme cold & heat
Environmental Resistance3C4 (corrosive gas), 3S4 (dust/sand), 3B2 (fungi), salt spray class 2Standard protectionH version passes stricter environmental tests for chemical, marine, desert applications
Output Configuration16 relay outputs (8 groups of DPDT, 2 channels share a common terminal)SameIdentical output circuit structure
Corrente nominale3UN (Ith conventional free-air thermal current)2UN (Ith)H version has higher rated current & load capacity
Intervallo di tensione24A DC (19~30V) / 24~240V AC (19~264V)SameSame AC/DC load voltage support
Tempo di risposta≤8ms (on) / ≤10ms (off)SameSame relay operating speed
Electrical DurabilityAC-15: 100,000 operazioni (2A@250V AC)SameSame contact service life
DC-13: 100,000 operazioni (0.6A@30V DC)
Dielectric Strength2000V AC/1 min (50/60Hz)SameSame electrical isolation performance
Protection DegreeIP20SameSame module enclosure protection
MontaggioStandard 35mm DIN rail, occupies 1 slotSameCompatible with same Modicon X80 rack system
Terminal Block20-point removable terminal block (BMXFTB2000 series)SameUses same terminal accessories
CertificationsIncluding marine, ATEX, IEC-Ex and other special environment certificationsStandard industrial certificationsH version suitable for hazardous areas & special industries
  1. Application Differences
BMXDRA1605H ApplicationsBMXDRA1605 Applications
1. Outdoor control panels or unconditioned field equipment1. Control cabinets in standard industrial buildings
2. Low-temperature environments (-25°C): cold storage, polar equipment, high-altitude areas2. Indoor automation systems with controlled temperature
3. High-temperature environments (+60~+70°C): metallurgia, glass, cement and other high‑heat industries3. Manufacturing in normal temperature range (0~60°C)
4. Corrosive environments: chimico, electroplating, offshore platforms, coastal areas4. Automated production lines in ordinary environments
5. Dust/sand environments: minerario, building materials, desert‑area equipment5. Clean rooms, food & beverage, pharmaceutical industries
6. Marine engineering requiring salt spray protection6. General commercial & civil building automation
  1. Raccomandazioni per la selezione
  2. Environment First Principle: BMXDRA1605H must be selected if operating temperature exceeds 0~60°C, or there is risk of corrosive gas, heavy dust, or mold growth.
  3. Load Capacity: For loads up to 3A, the H version provides higher current margin and more reliable long‑term operation.
  4. Cost Balance: The standard version (BMXDRA1605) is lower‑cost and offers sufficient performance in normal environments with better cost‑effectiveness.
  5. Compatibilità: Both modules are fully compatible with Modicon M340/M580 PLC systems and X80 racks. They can be directly interchanged without program modification.

Complete Model List of Modicon X80 Series BMXDRA/BMXDRC Relay Output Modules

BMXDRA1605H and BMXDRA1605 belong to the discrete relay output module portfolio of Schneider Electric Modicon X80 series. The series offers multiple configurations to meet various industrial requirements. Below is the full model list and key parameter comparison:

  1. Core Model Classification & Riepilogo
ModelloChannelsContact TypeAmbienteCaratteristiche principali
BMXDRA08058NO (Normalmente aperto)StandardBasic 8-channel relay output
BMXDRA0805H8NOHarsh EnvironmentHardened, operating temp -25°C~+70°C
BMXDRA0804T8NOAll‑ClimateWide temp, dedicated for 100~150V DC
BMXDRA08158NOStandardHigh isolation, 24~125V DC/24~240V AC
BMXDRA160516NOStandardBasic 16-channel relay output
BMXDRA1605H16NOHarsh EnvironmentHardened, operating temp -25°C~+70°C
BMXDRC08058NO/NCStandard8-channel dual‑contact relay output
  1. Detailed Technical Parameter Comparison
ArticoloBMXDRA0805BMXDRA0805HBMXDRA0804TBMXDRA0815BMXDRA1605BMXDRA1605HBMXDRC0805
Channels888816168
Configurazione dei contatti8×NO (4 groups, 2 channels share common)8×NO (4 groups, 2 channels share common)8×NO (4 groups, 2 channels share common)8×NO (individually isolated)16×NO (8 groups, 2 channels share common)16×NO (8 groups, 2 channels share common)8×NO/NC (DPDT)
Operating Temp0°C~+60°C-25°C~+70°C0°C~+60°C (TC treated)0°C~+60°C0°C~+60°C-25°C~+70°C0°C~+60°C
Protezione ambientaleStandard3C4/3S4/3B2/salt spray class 2All‑climate treatedStandardStandard3C4/3S4/3B2/salt spray class 2Standard
Corrente nominale2UN3UN2UN2UN2UN3UN2UN
Intervallo di tensione24V DC/24~240V AC24V DC/24~240V AC100~150V DC only24~125V DC/24~240V AC24V DC/24~240V AC24V DC/24~240V AC5~150V DC/24~240V AC
Tempo di risposta≤8ms(on)/≤10ms(off)SameSameSameSameSameSame
Vita elettrica100k operationsSameSameSameSameSameSame
Dielectric Strength2000V AC/1 minSameSameSameSameSameSame
Montaggio35Guida DIN da mmSameSameSameSameSameSame
Terminal Block20-point removableSameSameSameSameSameSame
Compatible SystemsM340/M580 PLCSameSameSameSameSameSame
  1. Caratteristiche principali & Applications by Model

3.1 BMXDRA0805 Series (8‑channel Standard)

BMXDRA0805: Basic 8‑channel NO relay output for normal industrial environments (0°C~+60°C), per esempio., solenoid valves, contactors on production lines.

BMXDRA0805H: Harsh environment hardened version, same functions as BMXDRA0805, stable at -25°C~+70°C, tested against corrosion, polvere, fungi, salt spray; ideal for chemical, marine, metallurgia.

3.2 Special‑Purpose 8‑Channel Models

BMXDRA0804T: All‑climate (TC) modulo, dedicated for 100~150V DC systems, for industrial equipment with special power supplies.

BMXDRA0815: High‑isolation 8‑channel NO relay output with wider DC voltage range (24~125V DC), better isolation for precision equipment control.

BMXDRC0805: Only model with NO/NC (DPDT) contatti, one channel with both NO and NC; suitable for complex switching control circuits.

3.3 BMXDRA1605 Series (16‑channel Standard)

BMXDRA1605: Basic 16‑channel NO relay output, 8 groups with shared common terminals, for medium‑to‑large automation systems such as assembly lines and HVAC.

BMXDRA1605H: Harsh environment hardened version, same functions as BMXDRA1605, -25°C~+70°C wide temp, 3A rated current (higher than standard), stronger load capacity for outdoor/unconditioned panels.

  1. Model Naming Convention
ParteSenso
BMXModicon X80 series identifier
DRA/DRCDiscrete relay output module (DRA = single contact, DRC = double contact)
8月16日Number of channels (08 = 8 canali, 16 = 16 canali)
05/04T/15Function code (05 = standard, 04T = 100~150V DC dedicated, 15 = high isolation)
HSuffix for Hardened / Harsh Environment version
  1. Selection Advice
  2. Channel Count: Choose 8 channels for small systems, 16 channels for medium systems; mixed use improves flexibility.
  3. Adattabilità ambientale: H‑type hardened modules must be used if temperature exceeds 0°C~+60°C or special environmental stresses exist.
  4. Contact Type: Choose DRA series (NO) for simple on/off control; choose DRC series (NO/NC) for switching control.
  5. Load Characteristics:

Normal loads (≤2A): all models suitable

Heavy loads (2~3A): prefer H‑type (3A rated current)

Special voltage systems: select dedicated models with matching voltage range (per esempio., BMXDRA0804T for 100~150V DC)

All models are fully compatible with Modicon M340/M580 PLC systems and X80 racks. Direct interchange is supported without program changes, facilitating system upgrade and maintenance.